COMMERCIAL FIRE INSPECTION - 201 RATH ST-08/04/26 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24755 08/12/2026 09/16/2026 2027-00000072 $80.00
Less Prepayment $0.00
Total Due—* $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
a,.,„,, Waterloo Fire Rescue
1 Inspection Report 425 E.3rd Street
Rome's Place-201 Rath ST,BLDG 201 Rath St,Waterloo IA 50703
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
0810412026 Annual Inspection(1Yr) 44i 7 S5 j j;- 17362
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
0 36 L 25 ® 27
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
08/26/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-08105/2026 @ 14:51
•$80 annual inspection fee
BRAD BALDWIN-08/05/2026 @ 14:51
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-08105/2026 @ 14:51
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-08/0512026 @ 14:51
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-08/05/2026 @ 14:52
Hood exhaust suppression system due for required inspection on 9120126.
SIGNATURES
Contact signature Inspector signature
No signature
post i `",`7 i'�j
Report completed post inspection -11 �,11 C�
Rome Mabry(2025) Date: BRAD BALDWIN 08105/2026
CHECKLISTS
GENERATED ON 8/5/26, 3:27 PM 1 OF 12
Means of Egress
Status Code Description
Fail 1010.2.5-Bolt locks.
Manually operated flush bolts or surface bolts are not Location:South exit door
permitted.Exceptions:1.On doors not required for egress in
Comments:Remove slide bolt lock from door immediately.
individual dwelling units or sleeping units.2.Where a pair of
doors serves a storage or equipment room,manually
operated edge-or surface-mounted bolts are permitted on the
inactive leaf.3.Where a pair of doors serves an occupant load
of less than 50 persons in a Group B,F or S occupancy,
manually operated edge-or surface-mounted bolts are
permitted on the inactive leaf.The inactive leaf shall not
contain doorknobs,panic bars or similar operating hardware.
4.Where a pair of doors serves a Group B,F or S occupancy,
manually operated edge-or surface-mounted bolts are
permitted on the inactive leaf provided that such inactive leaf
is not needed to meet egress capacity requirements and the
building is equipped throughout with an automatic sprinkler
system in accordance with Section 903.3.1.1.The inactive leaf
shall not contain doorknobs,panic bars or similar operating
hardware.5.Where a pair of doors serves patient care rooms
in Group 1-2 occupancies,self-latching edge-or surface-
mounted bolts are permitted on the inactive leaf provided that
the inactive leaf is not needed to meet egress capacity
requirements and the inactive leaf shall not contain
doorknobs,panic bars or similar operating hardware.
•
I!
11
CAUTION
•
imiLZ
ATCFI
Fail 1032.2-Reliability.
ORequired exit accesses,exits and exit discharges shall be Location:South exit door
continuously maintained free from obstructions or Comments:Remove yellow chain from doorway
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied.An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
GENERATED ON 8/5/26, 3:27 PM 2 OF 12
Additional Codes
Status Code Description
Fail 102.4-Application of building code.
0 The design and construction of new structures shall comply Location:Electric permit(mini-splits)
with the International Building Code,and any alterations, Comments:Licensed contractor(Custom Electrical Services)shall
additions,changes in use or changes in structures required obtain inspection of permit for(3)new mini splits installed.
by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
Fail 603.1.1-Equipment and fixtureswiring.
OElectrical equipment and fixtures All electrical equipment, Location:Mini splits(3)
wiring,devices and appliances shall be tested;and listed by Comments:Provide documentation of proper listing of Mini Splits
an approved agency and labeled;and installed,used and (x3)equipment installed.Equipment shall be properly installed per its
maintained in accordance with NFPA 70 and all instructions listing.
included as part of such listing.
Fail 603.1.1-Equipment and fixtureswiring.
V Electrical equipment and fixtures All electrical equipment, Location:Chest freezer near bar.
wiring,devices and appliances shall be tested;and listed by Comments:Appliances including heating elements or motors shall
an approved agency and labeled;and installed,used and plug directlyto permanent outlet.Currentlyfreezer plugged
maintained in accordance with NFPA 70 and all instructions p g p rip to a
power strip that is hanging by wires.Remove power strip to
included as part of such listing.
appliance.
Fail 603.1.1-Equipment and fixtureswiring.
0 Electrical equipment and fixtures All electrical equipment, Location:South window LED lights
wiring,devices and appliances shall be tested;and listed by Comments:provide documentation of listing of LED lighting.Lighting
an approved agency and labeled;and installed,used and shall be properly listed and used properly accordingly to its listing.
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
Fail 606.2-Where required.
OA Type I hood shall be installed at or above all commercial Location:Kitchen cooking equipment
cooking appliances and domestic cooking appliances used Comments:Relocate cooking equipment roducit g grease laden
for commercial purposes that produce grease vapors. vapors to be within 6 inches inside of outer edges of hood exhaust
Exceptions:1.Factory-built commercial exhaust hoods that system to avoid flame rollout.Appliances currently outside of hood
are listed and labeled in accordance with UL 710,and
coverage.
installed in accordance with Section 304.1 of the International
Mechanical Code,shall not be required to comply with
Sections 507.1.5,507.2.3,507.2.5,507.2.8,507.3.1,507.3.3,
507.4 and 507.5 of the International Mechanical Code.
2.Factory-built commercial cooking recirculating systems that
are listed and labeled in accordance with UL 710B,and
installed in accordance with Section 304.1 of the International
Mechanical Code,shall not be required to comply with
Sections 507.1.5,507.2.3,507.2.5,507.2.8,507.3.1,507.3.3,
507.4 and 507.5 of the International Mechanical Code.Spaces
in which such systems are located shall be considered to be
kitchens and shall be ventilated in accordance with Table
403.3.1.1 of the International Mechanical Code.For the
purpose of determining the floor area required to be
ventilated,each individual appliance shall be considered as
occupying not less than 100 square feet(9.3 m2).3.Where
cooking appliances are equipped with integral down-draft
exhaust systems and such appliances and exhaust systems
are listed and labeled for the application in accordance with
NFPA 96,a hood shall not be required at or above them.4.A
Type I hood shall not be required for an electric cooking
appliance where an approved testing agency provides
documentation that the appliance effluent contains 5 mg1m3
or less of grease when tested at an exhaust flow rate of 500
cfm(0.236 m3/s)in accordance with UL 710B.
GENERATED ON 8/5/26, 3:27 PM 3 OF 12
General Housekeeping
Status Code Description
Fail 304.3.1-Spontaneous ignition.
Ux Materials susceptible to spontaneous ignition,such as oily Location:Kitchen
rags,shall be stored in a listed disposal Container.Contents Comments:Provide listed container with self closing lid for disposal
of such containers shall be removed and disposed of daily, of soiled rag and towels.Soiled rags containing fats,oils or grease
shall be disposed of in container and removed from building daily
01111
GENERATED ON 8/5/26, 3:27 PM 4 OF 12
Electrical Safety
Status Code Description
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:Men's bathroom
Identified electrical hazards shall be abated.Identified Comments:Light switch cover currently taped on,cover shall be
hazardous electrical conditions in permanent wiring shall be installed properly as manufactured.
brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
Open junction boxes and open-wiring splices shall be Location:Office
prohibited.Approved covers shall be provided for all switch Comments:Install blank covering in panel opening to avoid shock
and electrical outlet boxes. hazard.
t
,
e
t' :i
s. 1\
t 4 ,
omret 't.
W
�tr
tro
Fail 603.5.2-Application and usePower supply.
Relocatable power taps and current taps shall be directly Location:Music machines&ATM
connected to a permanently installed receptacle.Exceptions: Comments:Power strips shall plug directly to a permanent outlet.
1.Where approved for use in a Group A occupancy or in a Currently daisy chained to another power strip is prohibited.
meeting room in a Group B occupancy,not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment.2.Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
GENERATED ON 8/5/26, 3:27 PM 5 OF 12
Pail 603.5.2-Application and usePower supply.
ORelocatable power taps and current taps shall be directly Location:DJ Booth
connected to a permanently installed receptacle.Exceptions: Comments:Power strip on counter currently daisy chained to
1.Where approved for use in a Group A occupancy or in a another power strip is prohibited.Power strips shall plug directly to a
meeting room in a Group B occupancy,not more than five permanent outlet,
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment.2.Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
i
o4,4
J
GENERATED ON 8/5/26, 3;27 PM 6 OF 12
Fall 603.5.2-Application and usePower supply.
ORelocatable power taps and current taps shall be directly Location:Office
connected to a permanently installed receptacle.Exceptions: Comments:REPEAT VIOLATION:Multiple daisy chained power strips
i.Where approved for use in a Group A occupancy or in a is prohibited.Each power strip shall plug directly to a permanent
meeting room in a Group B occupancy,not more than five outlet.Also,power strips shall be properly supportedlmounted to
relocatable power taps shall be permitted to be connected avoid hanging by wires
together or connected to an extension cord for temporary use
to supply power to electronic equipment.2.Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
1
L%, t ' \ \
.0.0,0° '"/jI
....0010 - Iwo,- -..z...444 - alio.
''''' V Os\g,
i
..&... .,4 4 , ti
fir. ,
Fail 603.5.3-Installation.
0 Relocatable power tap cords shall not extend through walls, Location:Behind hostess stand at South exit door
ceilings,floors,under doors or floor coverings,or be subject Comments:Power strip shall be properly supportedlmounted to
to environmental or physical damage.
avoid hanging by wires.
y
I
- ‘, Ni„,,,,. ):A-
11
i
1
GENERATED ON 8/5/26, 3:27 PM 7 OF 12
Fail 603.6.3-Installation,
Relocatable power tap cords shall not extend through walls, Location:Speaker podium near hostess stand
ceilings,floors,under doors or floor coverings,or be subject Comments:Power strip shall be properly supported/mounted to
to environmental or physical damage.
avoid hanging by wires.
>1
Y
x f' ' x.
.0:: ! 4/ii , -,„
3
t
Fail 603.5.3-Installation.
ORelocatable power tap cords shall not extend through walls, Location:Behind music machines&ATM
ceilings,floors,under doors or floor coverings,or be subject Comments:Power strip shall be properly supportedlmounted to
to environmental or physical damage.
avoid hanging by wires.
Fail 603.5.3-Installation.
Cx Relocatable power tap cords shall not extend through walls, Location:Bar-near"Miller High Life"sign
ceilings,floors,under doors or floor coverings,or be subject Comments:Power stripshall be properly supportedlmounted
to environmental or physical damage. p p Y to
avoid hanging by wires.
k
".". ,.ski: i t,
GENERATED ON 8/5/26, 3:27 PM 8 OF 12
Fail 603.5.3-installation.
O Relocatable power tap cords shall not extend through walls, Location:DJ Booth
ceilings,floors,under doors or floor coverings,or be subject Comments:Power strip below counter shall be properly
to environmental or physical damage. supported/mounted to avoid hanging by wires.
Fail 603.6-Extension cords.
OExtension cords and flexible cordsshall not be a substitute Location:Bar
for permanent wiring and shall be listed and labeled in Comments:Remove extension cord plugged from power strip below
accordance with UL 817.Extension cords and flexible "Miller ,si n Life"High supplying
cordsshall not be affixed to structures,extended through g g power to fan.Fan shall plug directly
to a permanent outlet.
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 8/5/26, 3:27 PM g OF 12
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Hostess stand at South exit
for permanent wiring and shall be listed and labeled in Comments:Remove all extension cords and remove flexible wiring
accordance with UL 817.Extension cords and flexible noted extending into and through wall.Flexible wiring is prohibited
cordsshall not be affixed to structures,extended through from extending through concealed spaces.
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
•
lb
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:SW corner-near jukebox
for permanent wiring and shall be listed and labeled in Comments:Remove green and white extension cords plugged to
accordance with UL 817.Extension cords and flexible jukebox and LED strip lights.
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Women's bathroom
for permanent wiring and shall be listed and labeled in Comments:Remove extension cord plugged to"Jose Cuervo"sign
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 8/5/26, 3:27 PM 10 OF 12
Commercial Cooking Hood Suppression System
slaw= Code Description
Fail 606.3.3-Cleaning.
Hoods,grease-removal devices,fans,ducts and other Location:Kitchen exhaust hood
appurtenances shall be cleaned at intervals as required by Comments:Owner is self-cleaning hood exhaust system.Owner shall
Sections 606.3.3.1 through 606.3.3.3. establish an account at Compliance Engine to document hood
cleanings at required intervals and cleaning standards,Contact
Compliance Engine at(Email:npratt@mybrycer.com or Phone#(630)
701-6548).Currently 272 days past due.
Portable Fire Extingusihers
Status Corte Description
Fail 906.2-General requirements.
Portable fire extinguishers shall be selected,installed and Location:Fire extinguishers
maintained in accordance with this section and NFPA 10. Comments:Provide required annual service to extinguishers,last
Exceptions:1.The distance of travel to reach an extinguisher recorded service completed May 2025
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
Fail 906.2-General requirements.
Portable fire extinguishers shall be selected,installed and Location:Kitchen-Class K extinguisher
maintained in accordance with this section and NFPA 10. Comments:Provide annual service to extinguisher,last recorded
Exceptions:1.The distance of travel to reach an extinguisher service completed May 2024
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.1n Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
GENERATED ON 8/5/26, 3:27 PM 11 OF 12