COMMERCIAL INSPECTION-3561 UNIVERSITY AVE- 12-16-20 FOR BILLING INQUIRY: (319)291-4323
LDescription Total Price
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
15529 01/04/2021 02/10/2021 2021-00000163 $100.00
Less Prepayment $0.00
Total Due—÷ $100.00
City of Waterloo
oil
V
WATERLOO FIRE RESCUE \ (--3 . �pTER�O
PELT/ON'REPORT
SPACE STATION,3561 UNIVERSITY AVE,BLDG 356'UNIVERSIT
Y WATERLOO IA Sfl
DETAIL - -
Inspection Date: 12/16/2020 1 inspection Type:Annual Inspection(1Yr Ins7'e. Number: 1332 i
Unit: N/A Lead- speetor:JEFF SIEBEL ; Other Inspectors: N/A ' Fee:$100.00 Shift: N/A Station: N1A
STATUS CODE
DESCRIPTION
FAIL 1031.2-Reliability Required exit accesses,exits and exit discharges shall be continuously
int
free from obstructions or impediments to full instant use in the case o fae orined other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector:JEFF SIEBEL-Comments: Back exit door must have an approved landing
immediately outside the exit door. Obtain proper permits and inspections.
FAIL 315.3-Storage in buildings Storage of materials in buildings shall be orderly and stacks shall be
e.
of combustible materials shall be separated from heaters or heating devicesl by Storage
distance or shielding so that ignition cannot occur.
Inspector:JEFF SIEBEL-Comments:maintain orderly storage with 36"pathways for
fire fighter access.
FAIL 5.2.1 -Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Inspector:JEFF SIEBEL-Comments:provide corrections for fire sprinkler inspection
report from Contental dated 9/14/20. Contactor must upload corrections online to
the Compliance engine.
FAIL 506.1 -Where required Where access to or within a structure or an area is restricted because
of openings or where immediate access is necessary for life-saving or fire-fighting secured
purposes,the fire code official is authorized to require a key box to be installed in an
approved location.The key box shall be of an approved type listed in accordance with
UL 1037,and shall contain keys to gain necessary access as required by the fire code
official.
inspector:JEFF SIEBEL-Comments:Install knox-box from knox-box.corn for fire
fighter access.Call Fire Marshal @319-493-1136 for location.
Printed on 01/04/2021 @ 15:36
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 604.2.5-Exit signs Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:repair all exit signs including above main front
exit.
FAIL 604.4.2-Records Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service,name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEFF SIEBEL-Comments:Provide documentation of testing and repair of all
exit/egress lights including.
FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical condition
electrical hazards in permanent wiring shall be brought to the attention of the responsible code officials Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector:JEFF SIEBEL-Comments:remove extension cord feeding Dan's Discount
and all extension cords and multiplug adapters at front.
FAIL 605.3-Working space and A working space of not less than 30 inches(762 mm)in width,36 inches(914 mm)in
clearance depth and 78 inches(1981 mm)in height shall be provided in front of electrical
service equipment.Where the electrical service equipment is wider than 30 inches
(762 mm),the working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1.Where other dimensions are required or allowed by NFPA 70.2.Access
openings into attics or under-floor areas which provide a minimum clear opening of
22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments:remove obstructions to and around electrical
panels in back area.maintain a minimum of 36"clearance.
FAIL 605.3.1 -Labeling Doors into electrical control panel rooms shall be marked with a plain
ly ly visible and
legible sign stating ELECTRICAL ROOM or similar approved wording.The
disconnecting means for each service,feeder or branch circuit originating on a
switchboard or panelboard shall be legibly and durably marked to indicate its
purpose unless such purpose is clearly evident.
Inspector:JEFF SIEBEL-Comments:install permanent sign stating"electrical room"
on door to electrical area at back of store.
FAIL 605.4.2-Power supply Relocatable power taps shall be directly connected to a permanent) installed
receptacle. y
Printed on 01/04/2021 @ 15:36
Page 2 of 4
t
STATUS CODE DESCRIPTION
Inspector:JEFF SIEBEL-Comments:remove power strips and multi plug adapters and
extension cords from front desk area.
FAI
L 605.5-Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring.
Extension cords and flexible cords shall not be affixed to structures,extended
through walls,ceilings or floors,or under doors or floor coverings, nor shall such
cords be subject to environmental damage or physical impact. Extension cords shall
be used only with portable appliances.
Inspector:JEFF SIEBEL-Comments:remove extension cords from all battery chargers
and equipment in back storage area.Install permanent power with permit and
inspections.
FA
IL 605.6-Unapproved Open junction boxes and open-wiring splices shall be prohibited.Approved cover
conditions shall be provided for all switch and electrical outlet boxes. pp s
Inspector:JEFF SIEBEL-Comments:replace missing electrical panel cover at back of
store.
GENERAL NOTES
JEFF SIEBEL-01/04/2021 @ 14:52 Annual Inspection$100
JEFF SIEBEL-01/04/2021 @ 14:52 Annual fire Alarm Hawkeye 9/14/20
REINSPECTION DATE
01/18/2021