COMMERCIAL INSPECTION-928 LA PORTE RD - 10-21-20 FOR BILLING INQUIRY: (319)291-4323
LDescription 1 Total Price j
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23519 01/04/2021 02/10/2021 2021-00000174 $80.00
Less Prepayment $0.00
Total Due--÷ $80.00
City of Waterloo
19
v pT
WATERLOOFIRE RESCUE j
£RL
/INSPECTION REPORT
l }
NAILS&SPA,928 LA PORTE RD,BLDG 928 LA PORTE RD,WATERLOO IA S07024410
( DELLA
ETAILS
Inspection ate: 10/21/20 0 Inspection Type:Annual Inspection(1 nspe tion Number:972 Shift: N/A Station: N/A
Unit: N/A L ad Inspector: FF SIEBEL ! Other Inspectors: N/A ree:$80.00
STATUS CODE DESCRIPTION
FAIL 102.3-Change of use or Changes shall not be made in the use or occupancy of any structure that would place
occupancy the structure in a different division of the same group or occupancy or in a different
group of occupancies,unless such structure is made to comply with the
requirements of this code and the International Building Code.Subject to the
� � � y � approval of the fire code official,the use or occupancy of an existing structure shall
�� - � � be allowed to be changed and the structure is allowed to be occupied for purposes in
other groups without conforming to all of the requirements of this code and the
International Building Code for those groups, provided the new or proposed use is
less hazardous, based on life and fire risk,than the existing use.
s114 Inspector:JEFF SIEBEL-Comments:remove bed and bedding immediately.Business
; may not be used to sleep in.There was a person in bed on my arrival.
�- - v
FAIL 305.1 -Clearance from Clearance between ignition sources,such as luminaires,heaters,flame-producing
ignition sources devices and combustible materials,shall be maintained in an approved manner.
Inspector:JEFF SIEBEL-Comments:remove storage from within a minimum of 36"
clearance of water heater.
""j 1
FAIL 605.4-Multiplug adapters Multiplug adapters,such as cube adapters, unfused plug strips or any other device
not complying with NFPA 70 shall be prohibited.
•
Inspector:JEFF SIEBEL-Comments: remove multi-plug adapter at front counter.
Printed on 10/22/2020 @ 09:15
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 605.4.2-Power supply Relocatable power taps shall be directly connected to a permanently installed
receptacle.
Inspector:JEFF SIEBEL-Comments:remove power strips from extension devices.
Each power strip must plug directly into wall outlet.
FAIL 605.4.3-Installation Relocatable power tap cords shall not extend through walls,ceilings,floors,under
doors or floor coverings,or be subject to environmental or physical damage.
Inspector:JEFF SIEBEL-Comments:remove power strips and cords from inside
cabinets at front counter work stations.
FAIL 605.5-Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring.
Extension cords and flexible cords shall not be affixed to structures,extended
through walls,ceilings or floors,or under doors or floor coverings, nor shall such
cords be subject to environmental damage or physical impact. Extension cords shall
be used only with portable appliances.
Inspector:JEFF SIEBEL-Comments:power cords running across aisle to work stations
must be protected with a UL listed cord protector.
FAIL 703.1 -Maintenance The required fire-resistance rating of fire-resistance-rated construction, including,
but not limited to,walls,firestops,shaft enclosures,partitions,smoke barriers,
floors,fire-resistive coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems,shall be maintained.Such
elements shall be visually inspected by the owner annually and properly repaired,
restored or replaced where damaged,altered, breached or penetrated. Records of
inspections and repairs shall be maintained.Where concealed,such elements shall
not be required to be visually inspected by the owner unless the concealed space is
accessible by the removal or movement of a panel,access door,ceiling tile or similar
movable entry to the space.Openings made therein for the passage of pipes,
electrical conduit,wires,ducts,air transfer openings and holes made for any reason
shall be protected with approved methods capable of resisting the passage of smoke
and fire.Openings through fire-resistance-rated assemblies shall be protected by
self-or automatic-closing doors of approved construction meeting the fire protection
requirements for the assembly.
Inspector:JEFF SIEBEL-Comments:replace missing ceiling tile in water heater room.
Printed on 10/22/2020 @ 09:15
Page 2 of 3
STATUS CODE DESCRIPTION
FAIL 906.2-General requirements Portable fire extinguishers shall be selected, installed and maintained in accordance
with this section and NFPA 10. Exceptions: 1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall
be allowed to be once every 3 years for dry-chemical or halogenated agent portable
fire extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1. Electronic
monitoring shall confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2. Loss of power or circuit continuity to the electronic
monitoring device shall initiate a trouble signal.2.3.The extinguishers shall be
installed inside of a building or cabinet in a noncorrosive environment.2.4. Electronic
monitoring devices and supervisory circuits shall be tested every 3 years when
extinguisher maintenance is performed.2.5.A written log of required hydrostatic
test dates for extinguishers shall be maintained by the owner to verify that
hydrostatic tests are conducted at the frequency required by NFPA 10.3.In Group 1-3,
portable fire extinguishers shall be permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:provide annual service for fire extinguisher
REINSPECTION DATE
11/12/2020
CONTACT SIGNATURE
Anh Huynh Signed on: 10/22/2020 @ 09:09 P -CJ
CI
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on: 10/22/2020 @ 09:09
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
(319)291-4319
Printed on 10/22/2020 @ 09:15