COMMERCIAL INSPECTION- 1125 E SAN MARNAN DR- 1-19-21 FOR BILLING INQUIRY: (319)291-4323
L Description I Total Price
INSPECTION 100,000 $600.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
4725 02/09/2021 03/15/2021 2021-00000203 $610.00
Less Prepayment $0.00
Total Due-* $610.00
City of Waterloo
sain 'Man
) faro
\\3c3
WATERLOO ��
E#7
INSPECTION REPORT ii �A #
MENARDS,1051-.E SAN MARNAN DR,BLDG 1051 E SAN MARNAN DR,WATERLOO IA 50702
DETAILS
Inspection Date:01/19/2021 I Inspection Type:Annual Inspection(1Yr) I Inspection Number: 1538 ; Shift: N/A I Station: N/A I
Unit: N/A ' Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A i Fee:$610.00
STATUS CODE DESCRIPTION
FAIL 1010.1.3-Door opening force The force for pushing or pulling open interior swinging egress doors,other than fire
doors,shall not exceed 5 pounds(22 N).These forces do not apply to the force
required to retract latch bolts or disengage other devices that hold the door in a
closed position. For other swinging doors,as well as sliding and folding doors,the
door latch shall release when subjected to a 15-pound(67 N)force.The door shall be
set in motion when subjected to a 30-pound(133 N)force.The door shall swing to a
full-open position when subjected to a 15-pound(67 N)force.
Inspector:JEFF SIEBEL-Comments:repair exit door#17, Must open with less than 15#
force.
FAIL 1031.3-Obstructions A means of egress shall be free from obstructions that would prevent its use,
including the accumulation of snow and ice.
Inspector:JEFF SIEBEL-Comments:remove obstructions to exit door#14
FAIL 315.3.1 -Ceiling clearance Storage shall be maintained 2 feet(610 mm)or more below the ceiling in
nonsprinklered areas of buildings or not less than 18 inches(457 mm)below
sprinkler head deflectors in sprinklered areas of buildings.
Inspector:JEFF SIEBEL-Comments:reduce storage at area 502 to a minimum of 18"
below fire sprinkler head deflector.Maintain all storage below allowable height as
labeled on fire sprinkler risers.
FAIL 315.3.2-Means of egress Combustible materials shall not be stored in exits or enclosures for stairways and
ramps.
Inspector:JEFF SIEBEL-Comments:also ref section 807. Remove hanging combustible
materials from next to stair egress path from mezzanine.
FAIL 5.2.1 -Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Inspector:JEFF SIEBEL-Comments:Provide annual fire sprinkler inspection report
including fire pump with all discrepancies corrected. Report must be uploaded online
to the compliance engine.
Printed on 01/29/2021 @ 14:57
Page 1 of 4
•
STATUS CODE DESCRIPTION
FAIL 507.5.3-Private fire service Private fire service mains and water tanks shall be periodically inspected,tested and
mains and water tanks maintained in accordance with NFPA 25 at the following intervals: 1.Private fire
hydrants of all typelnspection annually and after each operation;flow test and
maintenance annually.2. Fire service main piping:Inspection of exposed,annually;
flow test every 5 years.3. Fire service main piping strainerinspection and
maintenance after each use.Records of inspections,testing and maintenance shall be
maintained.
Inspector:JEFF SIEBEL-Comments:provide annual private fire hydrant inspection
report with all discrepancies corrected.contractor must upload online to the
compliance engine.
FAIL 604.4.2-Records Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service, name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEFF SIEBEL-Comments:Provide documentation of testing of all
emergency egress and exit lights with all discrepancies corrected.
FAIL 604.6-Emergency lighting Emergency lighting shall be inspected and tested in accordance with Sections 604.6.1
equipment through 604.6.2.1.
Inspector:JEFF SIEBEL-Comments:Provide current annual emergency generator
load bank testing and engine service report with all discrepancies corrected.
FAIL 903.3.3-Obstructed locations Automatic sprinklers shall be installed with due regard to obstructions that will delay
activation or obstruct the water distribution pattern.Automatic sprinklers shall be
installed in or under covered kiosks,displays,booths,concession stands or
equipment that exceeds 4 feet(1219 mm)in width. Not less than a 3-foot(914 mm)
clearance shall be maintained between automatic sprinklers and the top of piles of
combustible fibers. Exception: Kitchen equipment under exhaust hoods protected
with a fire-extinguishing system in accordance with Section 904.
Inspector:JEFF SIEBEL-Comments:Review fire sprinkler coverage under shed
displays. Provide corrections.
FAIL 906.6-Unobstructed and Portable fire extinguishers shall not be obstructed or obscured from view.In rooms
unobscured or areas in which visual obstruction cannot be completely avoided, means shall be
provided to indicate the locations of extinguishers.
Inspector:JEFF SIEBEL-Comments:remove obstructions to fire extinguisher on patio
column.maintain a minimum of 36"clearance.
Printed on 01/29/2021 @ 14:57
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEFF SIEBEL-Comments: Provide current annual fire alarm inspection
report with all discrepancies corrected.Contractor must upload online to the
compliance engine.
FAIL Table 8.1.1.2-Fire pump Fire pump being tested(run)?Weekly for diesel/monthly for electric.
inspection,testing,and
maintenance Inspector:JEFF SIEBEL-Comments:provide current annual fire pump
inspection/testing report.Contractor must upload to the compliance engine.
GENERAL NOTES
JEFF SIEBEL-01/29/2021 @ 14:55 Annual Inspection$610
JEFF SIEBEL-01/28/2021 @ 15:28 annual inspection$610
REINSPECTION DATE
02/16/2021
CONTACT SIGNATURE
Matt Victor 11v1w`
Signed on:01/29/2021 @ 14:55 ,
�1
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:01/29/2021 @ 14:55