INSPECTION REPORT
501 W 4TH,309 W 4TH ST,BLDG 50'W 4TH ST, WATERLOO IA 50702 `\ I
rr\\
DETAILS
Inspection Date:01/08/2021 I Inspection Type:Annual Inspection(1Yr) -tion Number:1245 I Shift: N/A Station: N/A
Unit: N/A I Lead Inspector: BROCK WELIVER I Other Inspectors:)EFF Sit $80.00
STATUS CODE DESCRIPTION
FAIL 1004.3-Posting of occupant Every room or space that is an assembly occupancy shall have the occupant load of
load the room or space posted in a conspicuous place, near the main exit or exit access
doorway from the room or space. Posted signs shall be of an approved legible
permanent design and shall be maintained by the owner or the owner's authorized
_ agent.
Inspector: BROCK WELIVER-Comments:Occupant Load was missing during the
inspection. ****This item has since been corrected.The Occupant Load was
calculated,updated and proper signage was given to the tenant.This sign needs to
be displayed as outlined above
FAIL 1010.1.3-Door opening force The force for pushing or pulling open interior swinging egress doors,other than fire
doors,shall not exceed 5 pounds(22 N).These forces do not apply to the force
required to retract latch bolts or disengage other devices that hold the door in a
closed position. For other swinging doors,as well as sliding and folding doors,the
door latch shall release when subjected to a 15-pound(67 N)force.The door shall be
set in motion when subjected to a 30-pound(133 N)force.The door shall swing to a
full-open position when subjected to a 15-pound(67 N)force.
Inspector: BROCK WELIVER-Comments:The front door was difficult to open during
� f /� .i.s.✓/ ,'' i ****nspection. This item was corrected as of 1-8-2021,B&B Locksmith was on scene
and was able to make adjustments to the door to help it function properly.
Printed on 01/08/2021 @ 17:40
Page 1 of 11
STATUS CODE DESCRIPTION
FAIL 1010.1.9.4-Bolt locks Manually operated flush bolts or surface bolts are not permitted. Exceptions: 1.On
doors not required for egress in individual dwelling units or sleeping units.2.Where
a pair of doors serves a storage or equipment room,manually operated edge-or
, surface-mounted bolts are permitted on the inactive leaf.3.Where a pair of doors
serves an occupant load of less than 50 persons in a Group B, F or S occupancy,
manually operated edge-or surface-mounted bolts are permitted on the inactive
leaf.The inactive leaf shall not contain doorknobs,panic bars or similar operating
-44 hardware.4.Where a pair of doors serves a Group B,F or S occupancy,manually
operated edge-or surface-mounted bolts are permitted on the inactive leaf provided
717 _— such inactive leaf is not needed to meet egress capacity requirements and the
building is equipped throughout with an automatic sprinkler system in accordance
with Section 903.3.1.1.The inactive leaf shall not contain doorknobs,panic bars or
similar operating hardware.5.Where a pair of doors serves patient care rooms in
Group 1-2 occupancies,self-latching edge-or surface-mounted bolts are permitted on
the inactive leaf provided that the inactive leaf is not needed to meet egress capacity
requirements and the inactive leaf shall not contain doorknobs, panic bars or similar
operating hardware.
Inspector: O -are Comments:Bolt Locks and Thumb Turn were found on
the back doorBR.OK TheseWELIVER items art of the Do Not Occu r ****
p py o der. These items
have been removed by the tenant as of 1630 hours on 1-8-2021.
saa
FAIL 1031.6-Finishes,furnishings Means of egress doors shall be maintained in such a manner as to be distinguishable
and decorations from the adjacent construction and finishes such that the doors are easily
recognizable as doors. Furnishings,decorations or other objects shall not be placed
so as to obstruct exits,access thereto,egress therefrom,or visibility thereof.
Hangings and draperies shall not be placed over exit doors or otherwise be located
to conceal or obstruct an exit. Mirrors shall not be placed on exit doors. Mirrors shall
not be placed in or adjacent to any exit in such a manner as to confuse the direction
of exit.
x _
Inspector: BROCK WELIVER-Comments:Coverings have been put on the front door.
; Remove the covers so that the front door is easily identifiable in the event of an
L.L...` emergency.
Printed on 01/08/2021 @ 17:40
Page 2 of 11
STATUS CODE DESCRIPTION
FAIL 316.3-Pitfalls The intentional design or alteration of buildings to disable,injure, maim or kill
intruders is prohibited.A person shall not install and use firearms,sharp or pointed
objects, razor wire,explosives,flammable or combustible liquid containers,or
dispensers containing highly toxic,toxic,irritant or other hazardous materials in a
manner that could passively or actively disable,injure, maim or kill a fire fighter who
forcibly enters a building for the purpose of controlling or extinguishing a fire,
rescuing trapped occupants or rendering other emergency assistance.
Inspector:BROCK WELIVER-Comments: Potential Pitfall area found in the shared
tenant space in the basement
FAIL 505.1 -Address identification New and existing buildings shall be provided with approved address identification.
The address identification shall be legible and placed in a position that is visible from
the street or road fronting the property.Address identification characters shall
contrast with their background.Address numbers shall be Arabic numbers or
alphabetical letters. Numbers shall not be spelled out. Each character shall be not
less than 4 inches(102 mm)high with a minimum stroke width of 1/2(12.7 mm).
Where required by the fire code official,address identification shall be provided in
additional approved locations to facilitate emergency response.Where access is by
means of a private road and the building cannot be viewed from the public way,a
monument,pole or other sign or means shall be used to identify the structure.
Address identification shall be maintained.
Inspector:BROCK WELIVER-Comments:Address is needed on the front of the
building
Printed on 01/08/2021 @ 17:40
Page 3 of 11
STATUS CODE DESCRIPTION
FAIL 604.2.12-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination with Sections 1008.3 and 1104.5.1.
Inspector:BROCK WELIVER-Comments:Egress lights were out when tested: 1)
combo light above back door,2)egress light in middle of building near the pool table,
3)combo light above front door,4)combo light in basement
icy
Printed on 01/08/2021 @ 17:40
Page 4 of 11
STATUS CODE DESCRIPTION
FAIL 604.2.5-Exit signs Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector: BROCK WELIVER-Comments: Exit lights were out when tested: 1)combo
light above back door,2)combo light above front door,3)combo light in basement
r�
1
eta
Printed on 01/082021 @ 17:40
Page 5 of 11
,
STATUS CODE DESCRIPTION
FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BROCK WELIVER-Comments:Cover missing off of main panel in the
r---V,. '4'___,:-___ les -t
basement-replace front panel
--- - / '
FAIL 605.4.3-Installation Relocatable power tap cords shall not extend through walls,ceilings,floors,under
doors or floor coverings,or be subject to environmental or physical damage.
Inspector: BROCK WELIVER-Comments:Power tap behind the bar near the front
t
.:I door was found hanging.Secure power tap to a wall or keep power tap rested on a
horizontal surface to prevent damage.
---
%,"
-
y". 7
t
f
Printed on 01/08/2021 @ 17:40
Page 6 of 11
STATUS CODE DESCRIPTION
FAIL 605.5-Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring.
Extension cords and flexible cords shall not be affixed to structures,extended
through walls,ceilings or floors,or under doors or floor coverings,nor shall such
cords be subject to environmental damage or physical impact. Extension cords shall
be used only with portable appliances.
Inspector: BROCK WELIVER-Comments:Extension cords were found extending
through the ceiling in multiple places: 1)back room near exit door-improper wiring
from light switch extending up through ceiling,2)power cord from outlet above the
mirror wall extends through ceiling,3)wire from music equipment next to back
bathroom extends through ceiling
Printed on 01/08/2021 @ 17:40
Page 7 of 11
STATUSDESCRIPTION
CODE
FAIL 605.6-Unapproved Open junction boxes and open-wiring splices shall be prohibited.Approved covers
conditions shall be provided for all switch and electrical outlet boxes.
Inspector: BROCK WELIVER-Comments:Open junction boxes and open wire splices
were found in multiple locations: 1)open cable plug on light switch by pool table,2)
light fixtures on both walls by the pool table,3)light fixture in the basement office,4)
multiple open junction boxes in the basement ceiling
•
_
i � r
Printed on 01/08/2021 @ 17:40
Page 8 of 11
STATUS CODE DESCRIPTION
- A
FAI
L 703.1 -Maintenance The required fire-resistance rating of fire-resistance-rated construction,including,
but not limited to,walls,firestops,shaft enclosures,partitions,smoke barriers,
floors,fire-resistive coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems,shall be maintained.Such
elements shall be visually inspected by the owner annually and properly repaired,
restored or replaced where damaged,altered, breached or penetrated. Records of
inspections and repairs shall be maintained.Where concealed,such elements shall
not be required to be visually inspected by the owner unless the concealed space is
accessible by the removal or movement of a panel,access door,ceiling tile or similar
movable entry to the space.Openings made therein for the passage of pipes,
electrical conduit,wires,ducts,air transfer openings and holes made for any reason
shall be protected with approved methods capable of resisting the passage of smoke
and fire.Openings through fire-resistance-rated assemblies shall be protected by
self-or automatic-closing doors of approved construction meeting the fire protection
requirements for the assembly.
Inspector: BROCK WELIVER-Comments:Ceiling tiles in the back room by the exit
need to be replaced
FAIL 906.2-General requirements Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10.Exceptions:1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall
be allowed to be once every 3 years for dry-chemical or halogenated agent portable
fire extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1.Electronic
monitoring shall confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2. Loss of power or circuit continuity to the electronic
monitoring device shall initiate a trouble signal.2.3.The extinguishers shall be
installed inside of a building or cabinet in a noncorrosive environment.2.4. Electronic
monitoring devices and supervisory circuits shall be tested every 3 years when
extinguisher maintenance is performed.2.5.A written log of required hydrostatic
test dates for extinguishers shall be maintained by the owner to verify that
hydrostatic tests are conducted at the frequency required by NFPA 10.3.In Group 1-3,
portable fire extinguishers shall be permitted to be located at staff locations.
Inspector: BROCK WELIVER-Comments: Fire Extinguisher is missing and one needs to
be in place.This in part of the Do Not Occupy order.****This item has been
corrected as of 1630 hours on 1-8-2021
GENERAL NOTES
BROCK WELIVER-01/08/2021 @ 17:26 Fire Alarm: N/A
BROCK WELIVER-01/08/2021 @ 17:26 Fire Sprinkler:N/A
Printed on 01/08/2021 @ 17:40
Page 9 of 11
GENERAL NOTES
BROCK WELIVER-01/08/2021 @ 17:27 Fire Extinguisher: missing during inspection.This item was corrected as of 1630 on 1-8-
2021
BROCK WELIVER-01/08/2021 @ 17:30 Do Not Occupy was posted on this address at 1500 hours on 1-8-2021 for the following
reasons: 1)bolt locks on the back door&2)lack of fire extinguisher.As of 1630 hours
on 1-8-2021 both of these items had been corrected and verified by Lt. Brock Weliver of
WFR and the Do Not Occupy was removed.
BROCK WELIVER-01/08/2021 @ 17:35 Howard Allen and his employee were present for the inspection of the building.
BROCK WELIVER-01/08/2021 @ 17:35 Occupant Load was calculated at 65
BROCK WELIVER-01/08/2021 @ 17:36 Inspection Fee=$80
BROCK WELIVER-01/08/2021 @ 17:36 Invoice Contact/Todd Goodson/319-529-4287
REINSPECTION DATE
01/22/2021
CONTACT SIGNATURE
Howard Allen Contact Refused
Refusal Reason:Not required due to Covid
INSPECTOR SIGNATURE
BROCK WELIVER
Signed on:01/08/2021 @ 17:38
•
Printed on 01/08/2021 @ 17:40
Page 10 of 11