COMMERCIAL INSPECTION-2450 CROSSROADS BLVD-2-2-21 FOR BILLING INQUIRY: (319)291-4323
L Description I Total Price
INSPECTION 50,000 $225.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
13032 02/09/2021 03/15/2021 2021-00000202 $235.00
Less Prepayment $0.00
Total Due—> $235.00
City of Waterloo
tER(
ATERLOO FIRE RESCUE ?$D5Z
INSPECTION REPORT : VI
MARCUS THEATERS,2450 CROSSROADS BLVD,BLDG 2450 CROSSROADS BLVD,WATERLOO IA
50702 4440
DETAILS
Inspection Date:02/02/2021 I Inspection Type:Annual Inspection(1Yr) I Inspection Number:4238 I Shift: N/A i Station: N/A
Unit: N/A I Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A I Fee:$235.00
STATUS CODE DESCRIPTION
FAR. 506.2-Key box maintenance The operator of the building shall immediately notify the fire code official and provide
the new key where a lock is changed or rekeyed.The key to such lock shall be secured
in the key box.
Inspector:JEFF SIEBEL-Comments:Install current key for all doors including key to
new lock on door to access fire sprinkler riser.
FAR. 509.1 -Identification Fire protection equipment shall be identified in an approved manner. Rooms
containing controls for air-conditioning systems,sprinkler risers and valves,or other
fire detection,suppression or control elements shall be identified for the use of the
fire department.Approved signs required to identify fire protection equipment and
equipment location shall be constructed of durable materials, permanently installed
and readily visible.
Inspector:JEFF SIEBEL-Comments: Install permanent signage,red with white
engraved letters stating"Fire Sprinkler Riser Room":A.On outside of door with a
keyed entry lock.B.On curtain as agreed to by fire sprinkler riser.
FAR. 604.2.12-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments: Repair egress lights:A.Above fire alarm panel B.
Hallway by Theater 2 and mop room.C.Theater 6 by row F near and far. D.egress
light in hall by theater 7/8.E.Ultra theater by G/H near hanging by wires. F. Egress
light at top of stairs in loft.
FAR. 604.2.5-Exit signs Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments: Repair exit lights:A.exit light front east exit. B.ear
theater 3 and above exit doors in hall.C.Theater 6 by row D.D.Theater 7 row D far
and near. E.Theater 9 by Row D. F.Above door to Theater 2 from upstairs.
Printed on 02/05/2021 @ 13:48
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 604.4.2-Records Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service,name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEFF SIEBEL-Comments:Provide documentation of testing of all
emergency egress and exit lights with all discrepancies corrected.(it may be helpful
to number lights).
FAIL 703.1 -Maintenance The required fire-resistance rating of fire-resistance-rated construction,including,
but not limited to,walls,firestops,shaft enclosures,partitions,smoke barriers,
floors,fire-resistive coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems,shall be maintained.Such
elements shall be visually inspected by the owner annually and properly repaired,
restored or replaced where damaged,altered,breached or penetrated. Records of
inspections and repairs shall be maintained.Where concealed,such elements shall
not be required to be visually inspected by the owner unless the concealed space is
accessible by the removal or movement of a panel,access door,ceiling tile or similar
movable entry to the space.Openings made therein for the passage of pipes,
electrical conduit,wires,ducts,air transfer openings and holes made for any reason
shall be protected with approved methods capable of resisting the passage of smoke
and fire.Openings through fire-resistance-rated assemblies shall be protected by
self-or automatic-closing doors of approved construction meeting the fire protection
requirements for the assembly.
Inspector:JEFF SIEBEL-Comments:replace missing ceiling tile in theater 12 and close
ceiling tile hatch upstairs by#11
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEFF SIEBEL-Comments:provide current annual fire alarm inspection
testing report with all discrepancies corrected. 105 days overdue.Complete
immediately.Contractor must submit online to the compliance engine.
GENERAL NOTES
JEFF SIEBEL-02/05/2021 @ 13:42 Hood Cleaning 8/14/20.Due 2/13/21
JEFF SIEBEL-02/05/2021 @ 13:43 Annual Fire Sprinkler 12/17/20 by Tri State.
JEFF SIEBEL-02/05/2021 @ 13:43 Annual Inspection$235
Printed on 02/05/2021 @ 13:48
Page 2 of 3
REINSPECTION DATE
03/04/2021
CONTACT SIGNATURE
Dayton D �//
Signed on:02/05/2021 @ 13:41 y
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:02/05/2021 @ 13:42 1,,
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 02/05/2021 @ 13:48