COMMERCIAL INSPECTION-503 W 4TH ST- 1-8-21 FOR BILLING INQUIRY: (319)291-4323
L Description I Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23532 02/09/2021 03/15/2021 2021-00000192 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
•
•
s-6
ATERLOO FIRE RESCUE 'J 44PTEAt
INSPECTION REPORT
CEDAR VALLEY TATTOO&PIERCING,503 W 4TH ST,BLDG 503 W 4TH ST,WATERLOO 1A 50702
DETAILS
Inspection Date:01/08/2021 I Inspection Type:Annual Inspection(1Yr) j Inspection Number:1246 I Shift: N/A I Station: N/A
Unit:326-Fire Prevention Officer ( Lead Inspector: BROCK WELIVER I Other Inspectors:JEFF SIEBEL I Fee:$80.00
STATUS CODE DESCRIPTION
Printed on 01/1 1/2021 @ 12:14
Page 1 of 9
2 v
605.1 -Abatement of Identified electrical hazards shall be abated.Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment that is modified or
Printed on 01/11/2021 @ 12:14
Page 2 of 9
STATUSDESCRIPTION
CODE
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BROCK W.ELIVER-Comments:Numerous electrical issues were found
$ z during the inspection,building owner was present and is aware of the issues.Check
with the building owner about the abatement of these issues. Lights in main hall,
electrical cord in ceiling,dead-man's panel in the basement, Romex cord to panel
z
K x
may,
z
i
-
s
-\-
j
Printed on 01/11/2021 @ 12:14
Page 3 of 9
STATUS CODE DESCRIPTION
FA I L 605.4-Multiplug adapters Multiplug adapters,such as cube adapters, unfused plug strips or any other device
not complying with NFPA 70 shall be prohibited.
% Inspector:BROCK WELIVER-Comments: Multiplug adapter was found in the front
window discontinue use
r
Printed on 01/11/2021 @ 12:14
Page 4 of 9
STATUS CODE DESCRIPTION
FAIL 605.5-Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring.
Extension cords and flexible cords shall not be affixed to structures,extended
through walls,ceilings or floors,or under doors or floor coverings, nor shall such
cords be subject to environmental damage or physical impact. Extension cords shall
be used only with portable appliances.
Inspector:BROCK WELIVER Comments: Discontinue the use of extension cords for
Y permanent wiring
X
ma's;
y
r
--
y
s i
i
77*
--- ---.c,0 -;,..,
S I$ , '
l8
it 4'
rev'" . ..
>„f
Printed on 01/1 1/2021 @ 12:14
Page 5 of 9
•
STATUS CODE DESCRIPTION
FAIL 605.6-Unapproved Open junction boxes and open-wiring splices shall be prohibited.Approved covers
conditions shall be provided for all switch and electrical outlet boxes.
Inspector: BROCK WELIVER-Comments: Numerous open wire splices were found
during the inspection. Building owner was present during the inspection and these
items were brought to his attention.Check with building owner about having these
electrical issues resolved
441
p,
FAIL 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1.In new
and existing Group A,B, E,F, H,I,M,R-1,R-2, R-4 and S occupancies. Exception:In
Group R-2 occupancies,portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A:10-B:C.2.Within 30 feet(9144 mm)
of commercial cooking equipment.3. In areas where flammable or combustible
liquids are stored, used or dispensed.4.On each floor of structures under
construction,except Group R-3 occupancies,in accordance with Section 3315.1.5.
Where required by the sections indicated in Table 906.1.6.Special-hazard areas,
`" including but not limited to laboratories,computer rooms and generator rooms,
', where required by the fire code official.
Inspector: BROCK WELIVER-Comments:Fire extinguisher needs to be examined for
use.
Printed on 01/11/2021 @ 12:14
Page 6 of 9
STATUS CODE DESCRIPTION
FAIL 906.2-General requirements Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10. Exceptions:1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall
be allowed to be once every 3 years for dry-chemical or halogenated agent portable
fire extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1. Electronic
monitoring shall confirm that extinguishers are properly positioned, properly
charged and unobstructed.2.2. Loss of power or circuit continuity to the electronic
monitoring device shall initiate a trouble signal.2.3.The extinguishers shall be
installed inside of a building or cabinet in a noncorrosive environment.2.4. Electronic
monitoring devices and supervisory circuits shall be tested every 3 years when
extinguisher maintenance is performed.2.5.A written log of required hydrostatic
test dates for extinguishers shall be maintained by the owner to verify that
hydrostatic tests are conducted at the frequency required by NFPA 10.3.In Group 1-3,
portable fire extinguishers shall be permitted to be located at staff locations.
Inspector: BROCK WELIVER-Comments:Annual testing/maintenance of extinguisher
is needed
FAIL 906.5-Conspicuous location Portable fire extinguishers shall be located in conspicuous locations where they will
be readily accessible and immediately available for use.These locations shall be
along normal paths of travel, unless the fire code official determines that the hazard
posed indicates the need for placement away from normal paths of travel.
Inspector:BROCK WELIVER-Comments:Locate the extinguisher as described above
FAIL 906.6-Unobstructed and Portable fire extinguishers shall not be obstructed or obscured from view. In rooms
unobscured or areas in which visual obstruction cannot be completely avoided, means shall be
provided to indicate the locations of extinguishers.
Inspector: BROCK WELIVER-Comments: Locate the extinguisher as described above
FAIL 906.7-Hangers and brackets Hand-held portable fire extinguishers,not housed in cabinets,shall be installed on
the hangers or brackets supplied. Hangers or brackets shall be securely anchored to
the mounting surface in accordance with the manufacturer's installation instructions.
Inspector: BROCK WELIVER-Comments: Locate the extinguisher as described above
FAIL 906.9.1 -Extinguishers Portable fire extinguishers having a gross weight not exceeding 40 pounds(18 kg)
weighing 40 pounds or less shall be installed so that their tops are not more than 5 feet(1524 mm)above the
floor.
Inspector: BROCK WELIVER-Comments:Locate the extinguisher as described above
Printed on 01/11/2021 @ 12:14
Page 7 of 9
•
STATUS CODE DESCRIPTION
FAIL 906.9.2-Extinguishers Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds(18
weighing more than 40 kg)shall be installed so that their tops are not more than 3.5 feet(1067 mm)above
pounds the floor.
Inspector: BROCK WELIVER-Comments: Locate the extinguisher as described above
GENERAL NOTES
BROCK WELIVER-01/11/2021 @ 12:07 Fire Alarm:N/A
BROCK WELIVER-01/11/2021 @ 12:07 Fire Sprinkler:N/A
BROCK WELIVER-01/11/2021 @ 12:08 Fire Extinguisher:annual service is due,see the violations listed for instructions on
how to locate a spot to hang the extinguisher
BROCK WELIVER-01/11/2021 @ 12:10 Numerous electrical items were discovered in the building,both addresses,501 &503
W 4th.The building owner was present during the inspection and was made aware of
many of these issues.Check with the building owner about the corrections for these
items.
BROCK WELIVER-01/11/2021 @ 12:10 Inspection Fee=$80
BROCK WELIVER-01/11/2021 @ 12:11 Invoice Contact/John Parsons/319-234-2727
REINSPECTION DATE
01/25/2021
CONTACT SIGNATURE
John Parsons-business Contact Refused
Refusal Reason: Not required due to Covid