Loading...
HomeMy WebLinkAbout106 E 3RD ST " r, INVOICEEDATE DUE DATE INVOICE# TOTAL DUE IJJ I h �1�•,► -ge_% 02/09/2021 03/15/2021 2021-00000191 $100.00 .,qr �tor�oo �o Customer#: 13018 Please Make Check Payable and Remit To: City of Waterloo A TTN: City Clerk/Accounts Receivable CEDAR RIVER TOWER 715 Mulberry St 106 E 3RD ST WATERLOO, IA 50703 WATERLOO,IA 50703 Amount Enclosed: DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT KEEP THIS PORTION FOR YOUR RECORDS COMMERCIAL INSPECTION- 106 E 3RD ST- 1-26-21 FOR BILLING INQUIRY: (319)291-4323 L Description Total Price' INSPECTION 20,000 $90.00 OCCUPANCY FEE $10.00 CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES 13 018 02/09/2021 03/15/2021 2021-00000191 $100.00 Less Prepayment $0.00 Total Due $100.00 City of Waterloo WATERLOO FIRE RESCUE INSPECTION REPORT CEDAR RIVER TOWERS,106 E 3RD ST,BLDG 106 E 3RD ST, WATERLOO IA 50703 DETAILS Inspection Date:01/26/2021 l Inspection Type:Annual Inspection(1Yr) Inspection Number:3282 Shift: N/A Station: N/A Unit: N/A l Lead Inspector:JEFF SIEBEL I Other Inspectors:BARRY STRATTON I Fee:$100.00 STATUS CODE DESCRIPTION FAIL 1031.2-Reliability Required exit accesses,exits and exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency where the building area served by the means of egress is occupied.An exit or exit passageway shall not be used for any purpose that interferes with a means of egress. Inspector:JEFF SIEBEL-Comments:remove all storage including loose carts etc.from egress paths on 1st floor. FAIL 1103.9-Carbon monoxide Existing Group 1-1,1-2,1-4 and R occupancies shall be equipped with carbon monoxide alarms alarms in accordance with Section 915,except that the carbon monoxide alarms shall be allowed to be solely battery operated. Inspector:JEFF SIEBEL-Comments:Rooms are all electric.Provide CO alarms where gas equipment installed. FAIL 4.6-Support of nonsprinkler Sprinkler system components shall not be used to support non-sprinkler system system components components unless expressly permitted by NFPA 13. Inspector:JEFF SIEBEL-Comments: Remove wires from fire sprinkler pipe in AHU room 1st floor. FAIL 5.2.1 -Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor system inspection Inspector:JEFF SIEBEL-Comments: Provide annual fire sprinkler inspection with all discrepancies corrected.Contractor must upload online to the compliance engine. Printed on 01/26/2021 @ 15:43 Page 1 of 5 STATUS CODE DESCRIPTION FAIL 504.3-Stairway access to New buildings four or more stories above grade plane,except those with a roof slope roof greater than four units vertical in 12 units horizontal(33.3-percent slope),shall be provided with a stairway to the roof.Stairway access to the roof shall be in accordance with Section 1011.12.Such stairway shall be marked at street and floor levels with a sign indicating that the stairway continues to the roof.Where roofs are used for roof gardens or for other purposes,stairways shall be provided as required for such occupancy classification. Inspector:JEFF SIEBEL-Comments:provide permanent"Roof Access"signs on doors leading to the roof as discussed. FAIL 604.2.12-Means of egress Emergency power shall be provided for means of egress illumination in accordance illumination with Sections 1008.3 and 1104.5.1. Inspector:JEFF SIEBEL-Comments: Replace/repair all egress lights including:A.by 907 B.Landing 8th floor stairway A and B.C.By 707.D.By 702 E.Stairway A level 7.F. Stairway B 5th floor landing.G.egress light by 502 hanging by wires.H by 401.I. stairway b 4th floor landing.J. by room 202 K. bottom of stairway b 1st floor. FAIL 604.4.2-Records Records of the inspection,testing and maintenance of emergency and standby power systems shall include the date of service, name of the servicing technician,a summary of conditions noted and a detailed description of any conditions requiring correction and what corrective action was taken.Such records shall be maintained. Inspector:JEFF SIEBEL-Comments: Provide documentation of testing and inspection of all emergency egress and exit lights with all discrepancies corrected with signature and date. FAIL 604.6-Emergency lighting Emergency lighting shall be inspected and tested in accordance with Sections 604.6.1 equipment through 604.6.2.1. Inspector:JEFF SIEBEL-Comments: Provide annual generator load bank test and generator engine service report. FAIL 605.3-Working space and A working space of not less than 30 inches(762 mm)in width,36 inches(914 mm)in clearance depth and 78 inches(1981 mm)in height shall be provided in front of electrical service equipment.Where the electrical service equipment is wider than 30 inches (762 mm),the working space shall be not less than the width of the equipment. Storage of materials shall not be located within the designated working space. Exceptions: 1.Where other dimensions are required or allowed by NFPA 70.2.Access openings into attics or under-floor areas which provide a minimum clear opening of 22 inches(559 mm)by 30 inches(762 mm). Inspector:JEFF SIEBEL-Comments:Remove obstructions maintain a minimum of 36" clearance at all times:A. room 608 B. Main electrical room 1st floor to electrical panel and disconnects. Provide permanent signage for no storage maintain 36"clearance" Printed on 01/26/2021 @ 15:43 Page 2 of 5 STATUS CODE DESCRIPTION FAIL 605.3.1 -Labeling Doors into electrical control panel rooms shall be marked with a plainly visible and legible sign stating ELECTRICAL ROOM or similar approved wording.The disconnecting means for each service,feeder or branch circuit originating on a switchboard or panelboard shall be legibly and durably marked to indicate its purpose unless such purpose is clearly evident. Inspector:JEFF SIEBEL-Comments:Label main electrical room door. FAIL 605.6-Unapproved Open junction boxes and open-wiring splices shall be prohibited.Approved covers conditions shall be provided for all switch and electrical outlet boxes. Inspector:JEFF SIEBEL-Comments:properly contain all wiring in listed junction boxes :A.room 903 closet. B room 406 bedroom FAIL 605.7-Appliances Electrical appliances and fixtures shall be tested and listed in published reports of inspected electrical equipment by an approved agency and installed and maintained in accordance with all instructions included as part of such listing. Inspector:JEFF SIEBEL-Comments: Provide documentation of dryer vent cleaning to the outside of the building for all clothes dryers. Provide date and signature. FAIL 703.1 -Maintenance The required fire-resistance rating of fire-resistance-rated construction,including, but not limited to,walls,firestops,shaft enclosures,partitions,smoke barriers, floors,fire-resistive coatings and sprayed fire-resistant materials applied to structural members and fire-resistant joint systems,shall be maintained.Such elements shall be visually inspected by the owner annually and properly repaired, restored or replaced where damaged,altered,breached or penetrated. Records of inspections and repairs shall be maintained.Where concealed,such elements shall not be required to be visually inspected by the owner unless the concealed space is accessible by the removal or movement of a panel,access door,ceiling tile or similar movable entry to the space.Openings made therein for the passage of pipes, electrical conduit,wires,ducts,air transfer openings and holes made for any reason shall be protected with approved methods capable of resisting the passage of smoke and fire.Openings through fire-resistance-rated assemblies shall be protected by self-or automatic-closing doors of approved construction meeting the fire protection requirements for the assembly. Inspector:JEFF SIEBEL-Comments:A.replace missing/damaged smoke seals room 308 B.close ceiling hatch in 104. Printed on 01/26/2021 @ 15:43 Page 3 of 5 • • STATUS CODE DESCRIPTION FAIL 703.2-Opening protectives Opening protectives shall be maintained in an operative condition in accordance with NFPA 80.Where allowed by the fire code official,the application of field-applied labels associated with the maintenance of opening protectives shall follow the requirements of the approved third-party certification organization accredited for listing the opening protective. Fire doors and smoke barrier doors shall not be blocked or obstructed,or otherwise made inoperable. Fusible links shall be replaced promptly whenever fused or damaged.Fire door assemblies shall not be modified. Inspector:JEFF SIEBEL-Comments: Remove drop down hold open device on:A. Community room B. Kitchen. Keep trash room,boiler room,lobby and maintenance doors shut at all times.Were propped open today.At initial inspection all residents doors had hold open devices on bottom of doors but were removed today. FAIL 903.3.1 -Standards Sprinkler systems shall be designed and installed in accordance with Section 903.3.1.1,unless otherwise permitted by Sections 903.3.1.2 and 903.3.1.3 and other chapters of this code,as applicable. Inspector:JEFF SIEBEL-Comments:All fire sprinkler heads and escutcheons shall be free of debris,paint,joint compound etc.Over 90%of rooms have paint or joint compound on heads and escutcheons.Contractor must provide correction of all discrepancies report online to the compliance engine. FAIL 904.12.6.2-Extinguishing Automatic fire-extinguishing systems shall be serviced at least every six months and system service after activation of the system. Inspection shall be by qualified individuals,and a certificate of inspection shall be forwarded to the fire code official upon completion. Inspector:JEFF SIEBEL-Comments:Provide proper kitchen hood exhaust system with fire suppression system for cooktop in community kitchen or Provide permanent signage"No Cooking Frying,or Sautéing or producing of grease laden vapors"and sign agreement with City of Waterloo. FAIL 907.2.11 -Single-and Listed single-and multiple-station smoke alarms complying with UL 217 shall be multiple-station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72. alarms Inspector:JEFF SIEBEL-Comments: Replace smoke detector room 301. Did not perform correctly during inspection. GENERAL NOTES JEFF SIEBEL-01/26/2021 @ 15:41 annual commercial inspection$100 JEFF SIEBEL-01/26/2021 @ 15:42 Annual Fire Alarm 3/13/20 Hawkeye.Due March Printed on 01/26/2021 @ 15:43 Page 4 of 5 REINSPECTION DATE 02/23/2021 CONTACT SIGNATURE Krystal Easton Signed on:01/26/2021 @ 15:36 —/ K ,z'/4" (--)\(-77 INSPECTOR SIGNATURE JEFF SIEBEL Signed on:01/26/2021 @ 15:36 QUESTIONS ABOUT YOUR INSPECTION? JEFF SIEBEL Jeff.Siebel@Waterloo-ia.org 3192301224 Printed on 01/26/2021 @ 15:43 Page 5 of 5