COMMERCIAL INSPECTION- 1309 LAFAYETTE ST-3-18-21 FOR BILLING INQUIRY: (319)291-4323
L Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23198 03/23/2021 04/26/2021 2021-00000242 $80.00
Less Prepayment $0.00
Total Due—+ $80.00
City of Waterloo
‘c )S
WATERLOO FIRE RESCUE
INSPECTION REPORT „«RtpO
PRIME MART 7, 1309 LAFAYETTE Sr,BLDG 1309 LAFAYETTE STtia:t
WATERLOO IA 50703
DETAILS
Inspection Date:03/18/2021 ; Inspection Type:Annual Inspection(1Yr) I Inspection Number:4363
Unit: N/A I Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A Shift: N/A ` Station. N/A
STATUS CODE
DESCRIPTION
FAIL 505.1 -Address identification New and existing buildings shall be provided with approved
The address identification shall be legible and placed in a position that is visible from
the street or road fronting the property.Address identification characters shall
contrast with their background.Address numbers shall be Arabic numbers or
alphabetical letters. Numbers shall not be spelled out. Each character shall be not
less than 4 inches(102 mm)high with a minimum stroke width of 1/2(12.7 mm).
Where required by the fire code official,address identification shall be provided in
additional approved locations to facilitate emergency response.Where access is by
means of a private road and the building cannot be viewed from the public way,a
monument,pole or other sign or means shall be used to identify the structure.
Address identification shall be maintained.
Inspector:JEFF SIEBEL-Comments:Install address on front of building facing the
street in conrasting colors to the back ground.
FAIL 604.2.5-Exit signs
Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:Either open up rear exit or permanently remove
exit sign and properly contain wires in junction box with cover.
FAIL 605.3-Working space and A working space of not less than 30 inches(762 mm)in
width, (914
clearance depth and 78 inches(1981 mm)in height shall be provided in fro inches ont of e ct i mm)in
cal
service equipment.Where the electrical service equipment is wider than inches
(762 mm),the working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1.Where other dimensions are required or allowed by NFPA 70.2.Access
openings into attics or under-floor areas which provide a minimum clear opening of
22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments:remove obstructions to electric panels in back
room.
Printed on 03/19/2021 @ 15:23
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 906.2-General requirements Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10. Exceptions:1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall
be allowed to be once every 3 years for dry-chemical or halogenated agent portable
fire extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1. Electronic
monitoring shall confirm that extinguishers are properly positioned, properly
charged and unobstructed.2.2. Loss of power or circuit continuity to the electronic
monitoring device shall initiate a trouble signal.2.3.The extinguishers shall be
installed inside of a building or cabinet in a noncorrosive environment.2.4. Electronic
monitoring devices and supervisory circuits shall be tested every 3 years when
extinguisher maintenance is performed.2.5.A written log of required hydrostatic
test dates for extinguishers shall be maintained by the owner to verify that
hydrostatic tests are conducted at the frequency required by NFPA 10.3.In Group 1-3,
portable fire extinguishers shall be permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:provide annual service for fire extinguisher.
GENERAL NOTES
JEFF SIEBEL-03/19/2021 @ 15:17 annual inspection$80
REINSPECTION DATE
04/08/2021
CONTACT SIGNATURE
Usman Chatha
Signed on:03/19/2021 @ 15:17 l /z�y
)S\
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:03/19/2021 @ 15:18
Printed on 03/19/2021 @ 15:23