COMMERCIAL INSPECTION- 1000 FLETCHER AVE-3-19-21 FOR BILLING INQUIRY: (319)291-4323
L Description I Total Price j
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
12205 03/23/2021 04/26/2021 2021-00000232 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
WATERLOO FIRE RESCUEfk
INSPECTION REPORT
IRV WARREN GOLF COURSE,1000 FLETCHER AVE,BLDG 1000 FLETCHER AVE,WATERLOO IA
S0701 4420
DETAILS
Inspection Date:03/19/2021 I Inspection Type:Annual Inspection(1Yr) I Inspection Number:4284 I Shift: N/A Station: N/A I
Unit: N/A I Lead Inspector:JEFF SIEBEL Other Inspectors: N/A I Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 604.2.5-Exit signs Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:repair egress/exit light by end of bar.
FAIL 605.3-Working space and A working space of not less than 30 inches(762 mm)in width,36 inches(914 mm)in
clearance depth and 78 inches(1981 mm)in height shall be provided in front of electrical
service equipment.Where the electrical service equipment is wider than 30 inches
(762 mm),the working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1.Where other dimensions are required or allowed by NFPA 70.2.Access
openings into attics or under-floor areas which provide a minimum clear opening of
22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments:remove obstructions to electrical panel and fire
extinguisher in storage room by office.
FAIL 609.3.3.1 -Inspection Hoods,grease-removal devices,fans,ducts and other appurtenances shall be
inspected at intervals specified in Table or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
Inspector:JEFF SIEBEL-Comments:Provide documentation of kitchen hood exhaust
system cleaning inspection with all discrepancies corrected.Contractor must upload
online to the compliance engine.
FAIL 609.3.3.3-Records Records for inspections shall state the individual and company performing the
inspection,a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the cleaning
and when the cleaning took place.Such records shall be completed after each
inspection or cleaning and maintained.
Inspector:JEFF SIEBEL-Comments: Provide documentation of kitchen hood exhaust
system cleaning and fire suppression inspections with all discrepancies corrected.
Contractor must upload online to the compliance engine.
Printed on 03/22/2021 @ 11:08
Page 1 of 2
b
i
STATUS CODE DESCRIPTION
FAIL 904.12.6.2-Extinguishing Automatic fire-extinguishing systems shall be serviced at least every six months and
system service after activation of the system. Inspection shall be by qualified individuals,and a
certificate of inspection shall be forwarded to the fire code official upon completion.
Inspector:JEFF SIEBEL-Comments: Provide documentation of kitchen hood exhaust
system fire suppression inspection with all discrepancies corrected.Contractor must
upload online to the compliance engine.All appliances must be under the exhaust
hood/fire suppression system at all times.
GENERAL NOTES
JEFF SIEBEL-03/22/2021 @ 11:07 annual inspection$80
REINSPECTION DATE
04/12/2021
CONTACT SIGNATURE
Monte Meyer
Signed on:03/22/2021 @ 11:05 c ��
8-CY\
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:03/22/2021 @ 11:06 f ��
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 03/22/2021 @ 11:08