COMMERCIAL INSPECTION-2834 ANSBOROUGH AVE-3-19-21 FOR BILLING INQUIRY: (319)291-4323
L Description Total Price
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
20752 03/23/2021 04/26/2021 2021-00000230 $100.00
Less Prepayment $0.00
Total Due— $100.00
City of Waterloo
�pSERL�O
ATERLOO FIRE RESCUE
INSPECTION REPORT
HY-VEE,2834ANSBOROUGHAYE,BLD 34ANSBOROUGHAVE,WATERLOO/A 50701 4400
DETAILS
Inspection Date:03/19/2021 I Inspection Type:Annual Inspection(1 Yr) I Inspection Number:4182 I Shift: N/A I Station: N/A I
Unit: N/A 1 Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A I Fee:$100.00
STATUS CODE DESCRIPTION
FAIL 1010.1.9.4-Bolt locks Manually operated flush bolts or surface bolts are not permitted. Exceptions: 1.On
doors not required for egress in individual dwelling units or sleeping units.2.Where
a pair of doors serves a storage or equipment room, manually operated edge-or
surface-mounted bolts are permitted on the inactive leaf.3.Where a pair of doors
serves an occupant load of less than 50 persons in a Group B, F or S occupancy,
manually operated edge-or surface-mounted bolts are permitted on the inactive
leaf.The inactive leaf shall not contain doorknobs,panic bars or similar operating
hardware.4.Where a pair of doors serves a Group B, F or S occupancy,manually
operated edge-or surface-mounted bolts are permitted on the inactive leaf provided
such inactive leaf is not needed to meet egress capacity requirements and the
building is equipped throughout with an automatic sprinkler system in accordance
with Section 903.3.1.1.The inactive leaf shall not contain doorknobs,panic bars or
similar operating hardware.5.Where a pair of doors serves patient care rooms in
Group 1-2 occupancies,self-latching edge-or surface-mounted bolts are permitted on
the inactive leaf provided that the inactive leaf is not needed to meet egress capacity
requirements and the inactive leaf shall not contain doorknobs,panic bars or similar
operating hardware.
Inspector:JEFF SIEBEL-Comments:remove slide bolt lock from dock doors.Slide
locks are strictly prohibited. Repeat violation.
FAIL 1031.2-Reliability Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
tri
Inspector:JEFF SIEBEL Comments:remove obstructions to exit door from electrical
room.Install permanent signage stating"Fire Door Do Not Block"on outside of door.
„ _ sue%
Printed on 03/22/2021 @ 10:15
Page 1 of 5
STATUS CODE DESCRIPTION
FAIL 315.3.1 -Ceiling clearance Storage shall be maintained 2 feet(610 mm)or more below the ceiling in
nonsprinklered areas of buildings or not less than 18 inches(457 mm)below
sprinkler head deflectors in sprinklered areas of buildings.
Inspector:JEFF SIEBEL-Comments:reduce storage in closet by offices to a minimum
of 18"below fire sprinkler deflector.
FAIL 315.3.2-Means of egress Combustible materials shall not be stored in exits or enclosures for stairways and
ramps.
Inspector:JEFF SIEBEL-Comments:remove firewood from under fire escape stairs
from office area.
FAIL 5.2.1 -Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Inspector:JEFF SIEBEL-Comments:provide annual fire sprinkler inspection with all
discrepancies corrected.contractor must upload online to the compliance engine.
FAIL 509.2-Equipment access Approved access shall be provided and maintained for all fire protection equipment
to permit immediate safe operation and maintenance of such equipment.Storage,
trash and other materials or objects shall not be placed or kept in such a manner
that would prevent such equipment from being readily accessible.
f.
Inspector:JEFF SIEBEL-Comments:remove obstructions to fire sprinkler riser.
_ , Maintain a minimum of 36"clearance at all times. Repeat violation.
fi
J f z3
Z
y yi
?;,, r!7 ' i
---
m
3
#77--,:- -,,,.-
Printed on 03/22/2021 @ 10:15
Page 2 of 5
,
STATUS CODE DESCRIPTION
FAIL 605.3-Working space and A working space of not less than 30 inches(762 mm)in width,36 inches(914 mm)in
clearance depth and 78 inches(1981 mm)in height shall be provided in front of electrical
service equipment.Where the electrical service equipment is wider than 30 inches
(762 mm),the working space shall be not less than the width of the equipment.
= , ,, Storage of materials shall not be located within the designated working space.
- �- Exceptions: 1.Where other dimensions are required or allowed by NFPA 70.2.Access
openings into attics or under-floor areas which provide a minimum clear opening of
22 inches(559 mm)by 30 inches(762 mm).
# ` Inspector:JEFF SIEBEL-Comments:Remove all obstructions to electrical panels
y disconnects and transformers. Maintain a minimum of 36 inch clearance at all times.
�= Repeat violation
y
4
fa .
.t.sn,�tm6uRt dam."
5
- is'a at Y
" Sg` Si
� %ice - �t -
-ter ,= A
g
- l y _sue € /
` ;: "',. ..gam
- ,„--0,-
/ "
t
I, �3
4 ,
i
Printed on 03/22/2021 @ 10:15
Page 3 of 5
STATUS CODE DESCRIPTION
FAIL 609.3.3.1 -Inspection Hoods,grease-removal devices,fans,ducts and other appurtenances shall be
inspected at intervals specified in Table or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
Inspector:JEFF SIEBEL-Comments:Provide documentation of kitchen hood exhaust
system cleaning inspection with all discrepancies corrected. Contractor must upload
online to the compliance engine.
FAIL 609.3.3.3-Records Records for inspections shall state the individual and company performing the
inspection,a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the cleaning
and when the cleaning took place.Such records shall be completed after each
inspection or cleaning and maintained.
Inspector:JEFF SIEBEL-Comments: Provide documentation of kitchen hood exhaust
system cleaning inspection and fire suppression inspection with all discrepancies
corrected.Contractor must upload online to the compliance engine.
FAIL 904.12.6.2-Extinguishing Automatic fire-extinguishing systems shall be serviced at least every six months and
system service after activation of the system. Inspection shall be by qualified individuals,and a
certificate of inspection shall be forwarded to the fire code official upon completion.
Inspector:JEFF SIEBEL-Comments:Provide documentation of kitchen hood exhaust
system fire suppression inspection with all discrepancies corrected.Contractor must
upload online to the compliance engine.
FAIL 906.2-General requirements Portable fire extinguishers shall be selected, installed and maintained in accordance
with this section and NFPA 10. Exceptions: 1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall
be allowed to be once every 3 years for dry-chemical or halogenated agent portable
fire extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1. Electronic
monitoring shall confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2. Loss of power or circuit continuity to the electronic
monitoring device shall initiate a trouble signal.2.3.The extinguishers shall be
installed inside of a building or cabinet in a noncorrosive environment.2.4. Electronic
monitoring devices and supervisory circuits shall be tested every 3 years when
extinguisher maintenance is performed.2.5.A written log of required hydrostatic
test dates for extinguishers shall be maintained by the owner to verify that
hydrostatic tests are conducted at the frequency required by NFPA 10.3. In Group 1-3,
portable fire extinguishers shall be permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:provide annual service for fire extinguishers.
GENERAL NOTES
JEFF SIEBEL-03/19/2021 @ 08:45 annual inspection$100
Printed on 03/22/2021 @ 10:15
Page 4 of 5
GENERAL NOTES
JEFF SIEBEL-03/19/2021 @ 08:54 Annual Fire Alarm due 5/6/21
REINSPECTION DATE
04/07/2021
CONTACT SIGNATURE
Kelly Signed on:03/22/2021 @ 09:06
<-e tJ
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:03/22/2021 @ 09:06