COMMERCIAL INSPECTION- 1117 E 4TH ST-2-18-21 FOR BILLING INQUIRY: (319)291-4323
L Description I Total Price J
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
21299 03/23/2021 04/26/2021 2021-00000218 $80.00
Less Prepayment $0.00
Total Due--f $80.00
City of Waterloo
Ear 10 ,
.0
WATERLOO isg..4toi 4 A h4P
E RESCUE
INSPECTION REPORT • 3 ���E
ALPS CORNER,1117 E 4TH ST,BLDG 1117 E 4TH ST,WATERLOO/A 50703
-,
DETAILS
Inspection Date:02/18/2021 1 Inspection Type:Annual Inspection(1Yr) 1 Inspection Number:4301 1 Shift: N/A Station: N/A
Unit: N/A I Lead Inspector:JEFF SIEBEL 1 Other Inspectors: N/A I Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 605.3-Working space and A working space of not less than 30 inches(762 mm)in width,36 inches(914 mm)in
clearance depth and 78 inches(1981 mm)in height shall be provided in front of electrical
service equipment.Where the electrical service equipment is wider than 30 inches
(762 mm),the working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1.Where other dimensions are required or allowed by NFPA 70.2.Access
openings into attics or under-floor areas which provide a minimum clear opening of
22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments:remove obstructions to electrical panel.maintain
a minimum of 36"clearance. Multiple repeating violation.
FAIL 605.4-Multiplug adapters Multiplug adapters,such as cube adapters,unfused plug strips or any other device
not complying with NFPA 70 shall be prohibited.
Inspector:JEFF SIEBEL-Comments:remove multi-plug adapter from behind counter
left hand side.
FAIL 605.4.3-Installation Relocatable power tap cords shall not extend through walls,ceilings,floors, under
doors or floor coverings,or be subject to environmental or physical damage.
Inspector:JEFF SIEBEL-Comments:properly mount power strip to wall or floor for
poker machines.must not hang by cord.
FAIL 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1.In new
and existing Group A,B,E,F,H,I,M,R-1,R-2,R-4 and S occupancies. Exception:In
Group R-2 occupancies,portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A:10-B:C.2.Within 30 feet(9144 mm)
of commercial cooking equipment.3. In areas where flammable or combustible
liquids are stored,used or dispensed.4.On each floor of structures under
construction,except Group R-3 occupancies,in accordance with Section 3315.1.5.
Where required by the sections indicated in Table 906.1.6.Special-hazard areas,
including but not limited to laboratories,computer rooms and generator rooms,
where required by the fire code official.
Inspector:JEFF SIEBEL-Comments:provide a currently serviced2A-10BC fire
extinguisher and properly mount 4"to 5'above the floor in an accessible location.
Printed on 02/18/2021 @ 15:32
Page 1 of 2
STATUS CODE DESCRIPTION
FAIL 906.9.1 -Extinguishers Portable fire extinguishers having a gross weight not exceeding 40 pounds(18 kg)
weighing 40 pounds or less shall be installed so that their tops are not more than 5 feet(1524 mm)above the
floor.
Inspector:JEFF SIEBEL-Comments:
GENERAL NOTES
JEFF SIEBEL-02/18/2021 @ 15:30 annual inspection 80$
JEFF SIEBEL-02/18/2021 @ 15:31 correct re-occurring violation immediately to avoid$100 re-inspection.
REINSPECTION DATE
03/15/2021
CONTACT SIGNATURE
Ali
Signed on:02/18/2021 @ 15:28 Gij?c, /47/ 4')
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:02/18/2021 @ 15:28
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 02/18/2021 @ 15:32