Loading...
HomeMy WebLinkAbout324 FLETCHER ST INVOICE DATE DUE DATE INVOICE# TOTAL DUE 1Fk 11 05/26/2021 06/30/2021 2021-00000258 $80.00 1. Customer#: 3360 Please Make Check Payable and Remit To: City of Waterloo ATTN: City Clerk/Accounts Receivable KWIK STAR#732 715 Mulberry St 1626 OAK ST WATERLOO, IA 50703 LA CROSSE, WI 54602 Amount Enclosed: DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT KEEP THIS PORTION FOR YOUR RECORDS COMMERCIAL INSPECTION-324 FLETCHER 5-4-21 FOR BILLING INQUIRY: (319)291-4323 L Description I Total Price J INSPECTION 2,000 $70.00 OCCUPANCY FEE $10.00 CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES 3360 05/26/2021 06/30/2021 2021-00000258 $80.00 Less Prepayment $0.00 Total Due—> $80.00 City of Waterloo WATERLOO FIRE RESCUE 44 Ent.% INSPECTION REPORT r KWIK TRIP#732,324 FLETCHER AVE,BLDG 324 FLETCHER AVE,WATERLOO IA 50701 DETAILS Inspection Date:05/04/2021 l Inspection Type:Annual Inspection(1Yr) Inspection Number:4522 Shift: N/A Station: N/A Unit: N/A j Lead Inspector:JEFF SIEBEL i Other Inspectors: N/A i Fee:$80.00 STATUS CODE DESCRIPTION FAIL 107.2-Testing and operation Equipment requiring periodic testing or operation to ensure maintenance shall be tested or operated as specified in this code. Inspector:JEFF SIEBEL-Comments:provide preventive maintenance safety check for CNG plant. FAIL 604.2.12-Means of egress Emergency power shall be provided for means of egress illumination in accordance illumination with Sections 1008.3 and 1104.5.1. Inspector:JEFF SIEBEL-Comments:repair egress lights by soup station. FAIL 604.2.5-Exit signs Emergency power shall be provided for exit signs as required in Section 1013.6.3.The system shall be capable of powering the required load for a duration of not less than 90 minutes. Inspector:JEFF SIEBEL-Comments:repair exit/egress sign hanging by wires in carwash. FAIL 605.3-Working space and A working space of not less than 30 inches(762 mm)in width,36 inches(914 mm)in clearance depth and 78 inches(1981 mm)in height shall be provided in front of electrical service equipment.Where the electrical service equipment is wider than 30 inches (762 mm),the working space shall be not less than the width of the equipment. Storage of materials shall not be located within the designated working space. Exceptions: 1.Where other dimensions are required or allowed by NFPA 70.2.Access openings into attics or under-floor areas which provide a minimum clear opening of 22 inches(559 mm)by 30 inches(762 mm). Inspector:JEFF SIEBEL-Comments:remove obstructions to electrical pane. Install permanent signage stating"No Storage Maintain 36"Clearance" FAIL 605.7-Appliances Electrical appliances and fixtures shall be tested and listed in published reports of inspected electrical equipment by an approved agency and installed and maintained in accordance with all instructions included as part of such listing. Inspector:JEFF SIEBEL-Comments: repair leaking diesel fuel hoses. Printed on 05/05/2021 @ 11:07 Page 1 of 2 GENERAL NOTES JEFF SIEBEL-05/05/2021 @ 09:41 annual inspection$80 REINSPECTION DATE 05/25/2021 CONTACT SIGNATURE Karina Signed on:05/05/2021 @ 10:59 G ,� rk_✓ INSPECTOR SIGNATURE JEFF SIEBEL Signed on:05/05/2021 @ 10:59 QUESTIONS ABOUT YOUR INSPECTION? JEFF SIEBEL Jeff.Siebel@Waterloo-ia.org 3192301224 Printed on 05/05/2021 @ 11:07 Page 2 of 2