INSPECTION REPORT
CHAPALAS,900 LA PORTE RD,BLDG 900 LA PORTE RD,WATERLOO IA 50702 440
DETAILS
Inspection Date:05/03/2021 Inspection Type:Annual Inspection(1Yr) I Inspection Number:4859 I Shift: N/A Station: N/A
Unit: N/A Lead Inspector:JEFF SIEBEL 1 Other Inspectors: N/A I Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 10.2.2-Fire extinguisher A placard shall be conspicuously placed near each extinguisher that states that the
placard fire protection system shall be activated prior to using the fire extinguisher
Inspector:JEFF SIEBEL-Comments:Install proper signage above the K guard fire
extinguisher.
FAIL 1031.2-Reliability Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector:JEFF SIEBEL-Comments:remove loose tables and chairs from back hall.
No storage allowed.
FAIL 5.2.1 -Annual sprinkler Sprinklers shall be inspected at least annually by licensed contractor
system inspection
Inspector:JEFF SIEBEL-Comments:provide current annual fire sprinkler inspection
report with all discrepancies corrected.Contractor must upload online to the
compliance engine.
FAIL 5303.5.3-Securing Compressed gas containers,cylinders and tanks shall be secured to prevent falling
compressed gas containers, caused by contact,vibration or seismic activity.Securing of compressed gas
cylinders and containers,cylinders and tanks shall be by one of the following methods: 1.Securing
containers,cylinders and tanks to a fixed object with one or more restraints.2.
Securing containers,cylinders and tanks on a cart or other mobile device designed
for the movement of compressed gas containers,cylinders or tanks.3. Nesting of
compressed gas containers,cylinders and tanks at container filling or servicing
facilities or in sellers'warehouses not accessible to the public.Nesting shall be
allowed provided the nested containers,cylinders or tanks,if dislodged,do not
obstruct the required means of egress.4.Securing of compressed gas containers,
cylinders and tanks to or within a rack,framework,cabinet or similar assembly
designed for such use. Exception:Compressed gas containers,cylinders and tanks in
the process of examination,filling,transport or servicing.
Inspector:JEFF SIEBEL-Comments:secure all compressed gas cylinders with chain.
Printed on 05/04/2021 @ 08:37
Page 1 of 3
STATE. 41E DESCRIPTION
FAIL 605.3-Working space and A working space of not less than 30 inches(762 mm)in width,36 inches(914 mm)in
clearance depth and 78 inches(1981 mm)in height shall be provided in front of electrical
service equipment.Where the electrical service equipment is wider than 30 inches
(762 mm),the working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1.Where other dimensions are required or allowed by NFPA 70.2.Access
openings into attics or under-floor areas which provide a minimum clear opening of
22 inches(559 mm)by 30 inches(762 mm).
F
;Ca tInspector:JEFF SIEBEL-Comments:remove obstructions to electricpanels REPEAT
p
�� OFFENSE.Install permanent red sign with white letters stating"No Storage Maintain
36"Clearance"
FAIL 609.3.3-Cleaning Hoods,grease-removal devices,fans,ducts and other appurtenances shall be
cleaned at intervals as required by Sections 609.3.3.1 through 609.3.3.3.
Inspector:JEFF SIEBEL-Comments: Provide current semi-annual kitchen hood
exhaust system cleaning report with all discrepancies corrected.Contractor must
upload online to the compliance
FAIL 609.3.3.3-Records Records for inspections shall state the individual and company performing the
inspection,a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the cleaning
and when the cleaning took place.Such records shall be completed after each
inspection or cleaning and maintained.
Inspector:JEFF SIEBEL-Comments:Provide current semi-annual kitchen hood
exhaust system cleaning and fire suppression inspection report with all
discrepancies corrected.Contractor must upload online to the compliance
FAIL 904.12.6.2-Extinguishing Automatic fire-extinguishing systems shall be serviced at least every six months and
system service after activation of the system. Inspection shall be by qualified individuals,and a
certificate of inspection shall be forwarded to the fire code official upon completion.
Inspector:JEFF SIEBEL-Comments:Provide current semi-annual kitchen hood
exhaust system fire suppression report with all discrepancies corrected.Contractor
must upload online to the compliance
GENERAL NOTES
JEFF SIEBEL-05/04/2021 @ 08:35 Annual inspection$80
Printed on 05/04/2021 @ 08:37
Page 2 of 3
REM, c..ATE
05/24/2021
CONTACT SIGNATURE
Freddy
Signed on:05/04/2021 @ 08:25 / � c 7
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:05/04/2021 @ 08:25