COMMERCIAL INSPECTION-205 FRANKLIN ST-3-24-21 FOR BILLING INQUIRY: (319)291-4323
LDescription J Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
20699 05/26/2021 06/30/2021 2021-00000267 $80.00
Less Prepayment $0.00
Total Due---> $80.00
City of Waterloo
WATERLOO FIRE RESCUE V 44pTER1Q4
INSPECTION REPORT "
CVS PHARMACY,205 FRANKLIN ST,BLDG 205 FRANKLIN ST,WATERLOO IA 50703 4410
DETAILS
Inspection Date:03/24/2021 Inspection Type:Annual Inspection(1Yr) Inspection Number:4393 I Shift: N/A { Station: N/A
Unit:326-Fire Prevention Officer Lead Inspector:BROCK WELIVER i Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 1010.1.3-Door opening force The force for pushing or pulling open interior swinging egress doors,other than fire
doors,shall not exceed 5 pounds(22 N).These forces do not apply to the force
required to retract latch bolts or disengage other devices that hold the door in a
closed position. For other swinging doors,as well as sliding and folding doors,the
door latch shall release when subjected to a 15-pound(67 N)force.The door shall be
set in motion when subjected to a 30-pound(133 N)force.The door shall swing to a
full-open position when subjected to a 15-pound(67 N)force.
Inspector:JEFF SIEBEL-Comments:allow fire inspector opportunity to test exit doors.
FAIL 509.2-Equipment access Approved access shall be provided and maintained for all fire protection equipment
to permit immediate safe operation and maintenance of such equipment.Storage,
trash and other materials or objects shall not be placed or kept in such a manner
that would prevent such equipment from being readily accessible.
Inspector:JEFF SIEBEL-Comments:
*Isar 1
FAIL 604.2.5-Exit signs Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments: Repair exit/egress lights:A.above outside door in
front vestibule. B.above door from stock room to outside C.From Restroom hall to
store.
Printed on 03/29/2021 @ 09:25
Page 1 of 2
STATUS CODE DESCRIPTION
FAIL Chapter 14-Inspection, Fire alarm system tested at least annually by licensed contractor
testing,and maintenance
Inspector:JEFF SIEBEL-Comments:Annual inspection by JF Ahern dated 7/4/20 shows
deficiencies(faulty SD and sensitivity testing).Contractor must upload corrections
online to the compliance engine.
GENERAL NOTES
JEFF SIEBEL-03/29/2021 @ 08:54 annual inspection$80
JEFF SIEBEL-03/29/2021 @ 09:25 annual fire sprinkler Ahearn 8/3/20
REINSPECTION DATE
04/14/2021
CONTACT SIGNATURE
Michael Paige
Signed on:03/29/2021 @ 08:51 KC7 -/
Ls+ nr-
INSPECTOR SIGNATURE
BROCK WELIVER
Signed on:03/29/2021 @ 08:51
QUESTIONS ABOUT YOUR INSPECTION?
BROCK WELIVER
brock.weliver@waterloo-ia.org
3192914460
Printed on 03/29/2021 @ 09:25