COMMERCIAL INSPECTION-225 W 4TH ST-03-25-21 FOR BILLING INQUIRY: (319)291-4323
LDescription I Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
22280 05/26/2021 06/30/2021 2021-00000266 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
�p'C6R(QO
WATERLOO FIRE RESCUE `.
INSPECTION REPORT
BASAL PIZZA,225 W 4TH ST,BLDG 225 W 4TH ST,WATERLOO/A 50702
DETAILS
Inspection Date:03/25/2021 Inspection Type:Annual Inspection(1Yr) Inspection Number:4673 I Shift: N/A ! Station: N/A l
Unit: N/A l Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A ; Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 605.3-Working space and A working space of not less than 30 inches(762 mm)in width,36 inches(914 mm)in
clearance depth and 78 inches(1981 mm)in height shall be provided in front of electrical
service equipment.Where the electrical service equipment is wider than 30 inches
(762 mm),the working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1.Where other dimensions are required or allowed by NFPA 70.2.Access
openings into attics or under-floor areas which provide a minimum clear opening of
22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments:remove obstructions to electrical panel .Maintain
a minimum of 36"to electrical panel at all times.
FAIL 609.3.3.1 -Inspection Hoods,grease-removal devices,fans,ducts and other appurtenances shall be
inspected at intervals specified in Table or as approved by the fire code official.
Inspections shall be completed by qualified individuals.
Inspector:JEFF SIEBEL-Comments:Table 609.3.3.1 states that cooking operations
utilizing solid fuel-burning cooking appliances shall be inspected Monthly by a
qualified individual.Provide documentation of hood cleaning. Last was July 2020,
overdue.
GENERAL NOTES
JEFF SIEBEL-03/29/2021 @ 10:01 annual inspection$80
JEFF SIEBEL-03/29/2021 @ 10:02 Annual fire sprinkler 6/8/2020 due June
JEFF SIEBEL-03/29/2021 @ 10:02 Annual fire alarm 5/19/2020 due May
JEFF SIEBEL-03/29/2021 @ 10:02 fire extinguishers due in June.
Printed on 03/29/2021 @ 10:06
Page 1 of 2
REINSPECTION DATE
04/16/2021
CONTACT SIGNATURE
Tony Eischeid
Signed on:03/29/2021 @ 10:03
N PG
I a-(1'-'
..................................
INSPECTOR SIGNATURE
JEFF SIEBEL '
Signed on:03/29/2021 @ 10:03
QUESTIONS ABOUT YOUR INSPECTION'
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 03/29/2021 @ 10:06