City of Waterloo
WATERLOO FIRE RESCUE ER(00
INSPECTION REPORT
YESWAY,117E SAN MARNAN DR,BLDG 117E SAN MARNAN DR,WATERLOO IA 50702 4410
DETAILS
Inspection Date:05/28/2021 1 Inspection Type:Annual Inspection(1Yr) I Inspection Number:4752 I Shift: N/A Station: N/A 1
Unit: N/A I Lead Inspector:JEFF SIEBEL ; Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 604.2.12-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments:repair egress light above main front door.
FAIL 605.3-Working space and A working space of not less than 30 inches(762 mm)in width,36 inches(914 mm)in
clearance depth and 78 inches(1981 mm)in height shall be provided in front of electrical
service equipment.Where the electrical service equipment is wider than 30 inches
(762 mm),the working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1.Where other dimensions are required or allowed by NFPA 70.2.Access
openings into attics or under-floor areas which provide a minimum clear opening of
22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments: Remove obstructions to the electrical panel in
back hallway.Maintain a minimum of 36"clearance.
FAIL 605.4.2-Power supply Relocatable power taps shall be directly connected to a permanently installed
receptacle.
Inspector:JEFF SIEBEL-Comments:power taps must plug directly into permanent
wall outlet.Can not be plugged into anther power tap.Install permanent outlet with
proper permits and inspections.
Printed on 05/03/2021 @ 10:04
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 906.2-General requirements Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10. Exceptions: 1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall
be allowed to be once every 3 years for dry-chemical or halogenated agent portable
fire extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1. Electronic
monitoring shall confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2. Loss of power or circuit continuity to the electronic
monitoring device shall initiate a trouble signal.2.3.The extinguishers shall be
installed inside of a building or cabinet in a noncorrosive environment.2.4. Electronic
monitoring devices and supervisory circuits shall be tested every 3 years when
extinguisher maintenance is performed.2.5.A written log of required hydrostatic
test dates for extinguishers shall be maintained by the owner to verify that
hydrostatic tests are conducted at the frequency required by NFPA 10.3.In Group 1-3,
portable fire extinguishers shall be permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:provide annual service for fire extinguishers.
GENERAL NOTES
JEFF SIEBEL-05/03/2021 @ 10:04 annual inspection $80
REINSPECTION DATE
06/18/2021
CONTACT SIGNATURE
Stephanie Adolph ,�J Cc._.r( 7
Signed on:05/03/2021 @ 10:03
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:05/03/2021 @ 10:03