COMMERCIAL INSPECTION-307 W 5TH-4-28-21 FOR BILLING INQUIRY: (319)291-4323
LDescription Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
20688 05/26/2021 06/30/2021 2021-00000260 $80.00
Less Prepayment $0.00
Total Due $80.00
City of Waterloo
A !
WATERLOO
FIRERESCUE �
INSPECTION REPORT i
BRIQUE HOUSE,301-307 W STH ST,BLDG 301-307 W STH ST, WATERLOO IA S0702 9
DETAILS
Inspection Date:04/28/2021 I Inspection Type:Annual Inspection(1Yr) I Inspection Number:4588 1 Shift: N/A Station: N/A
Unit: N/A 1 Lead Inspector:JEFF SIEBEL 1 Other Inspectors: N/A ; Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 605.7-Appliances Electrical appliances and fixtures shall be tested and listed in published reports of
inspected electrical equipment by an approved agency and installed and maintained
in accordance with all instructions included as part of such listing.
Inspector:JEFF SIEBEL-Comments:remove extension cord from cooler in kitchen.
Repeat violations.Install permanent outlet with proper permits and inspections to
avoid re-inspection fees.
FAIL 609.2-Where required A Type I hood shall be installed at or above all commercial cooking appliances and
domestic cooking appliances used for commercial purposes that produce grease
vapors. Exception:A Type I hood shall not be required for an electric cooking
appliance where an approved testing agency provides documentation that the
appliance effluent contains 5 mg/m^3 or less of grease when tested at an exhaust
flow rate of 500 cfm(0.236 m^3/s)in accordance with UL 710B.
Inspector:JEFF SIEBEL-Comments:4 burner stove must be installed under kitchen
exhaust hood and covered by fire suppression system.
FAIL 609.3.3-Cleaning Hoods,grease-removal devices,fans,ducts and other appurtenances shall be
cleaned at intervals as required by Sections 609.3.3.1 through 609.3.3.3.
Inspector:JEFF SIEBEL-Comments:Provide current semi-annual kitchen hood
exhaust system inspection with all discrepancies corrected.Contractor must upload
online to the compliance engine.
FAIL 609.3.3.2-Grease If during the inspection it is found that hoods,grease-removal devices,fans,ducts or
accumulation other appurtenances have an accumulation of grease,such components shall be
cleaned in accordance with ANSI/IKECA C 10.
Inspector:JEFF SIEBEL-Comments:Clean all excessive grease off floor,walls,
appliances,and basement walls and floors. Repeat offense.
Printed on 04/29/2021 @ 11:23
Page 1 of 3
STATUS CODE DESCRIPTION
FAI 609.3.3.3-Records Records for inspections shall state the individual and company performing the
inspection,a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the cleaning
and when the cleaning took place.Such records shall be completed after each
inspection or cleaning and maintained.
Inspector:JEFF SIEBEL-Comments: Provide current semi-annual kitchen hood
exhaust system cleaning and fire suppression system reports with all discrepancies
corrected.Contractor must upload online to the compliance engine.
FAI 904.12.6.2-Extinguishing Automatic fire-extinguishing systems shall be serviced at least every six months and
system service after activation of the system. Inspection shall be by qualified individuals,and a
certificate of inspection shall be forwarded to the fire code official upon completion.
Inspector:JEFF SIEBEL-Comments:Provide current semi-annual kitchen hood
exhaust system fire suppression system inspection reports with all discrepancies
corrected.Contractor must upload online to the compliance engine.
FAIL 906.2-General requirements Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10. Exceptions: 1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall
be allowed to be once every 3 years for dry-chemical or halogenated agent portable
fire extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1. Electronic
monitoring shall confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2. Loss of power or circuit continuity to the electronic
monitoring device shall initiate a trouble signal.2.3.The extinguishers shall be
installed inside of a building or cabinet in a noncorrosive environment.2.4. Electronic
monitoring devices and supervisory circuits shall be tested every 3 years when
extinguisher maintenance is performed.2.5.A written log of required hydrostatic
test dates for extinguishers shall be maintained by the owner to verify that
hydrostatic tests are conducted at the frequency required by NFPA 10.3.In Group 1-3,
portable fire extinguishers shall be permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:provide annual service for fire extinguishers.
GENERAL NOTES
JEFF SIEBEL-04/29/2021 @ 11:21 annual inspection $80
JEFF SIEBEL-04/29/2021 @ 11:21 building is under construction.
JEFF SIEBEL-04/29/2021 @ 11:22 Provide permanent corrections to repeat offenses to avoid progressive re-inspection
fees starting at$100.
Printed on 04/29/2021 @ 11:23
Page 2 of 3
REINSPECTION DATE
05/19/2021
CONTACT SIGNATURE
Anthony King
Signed on:04/29/2021 @ 11:19
C
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:04/29/2021 @ 11:20