COMMERCIAL INSPECTION-2841 CROSSROADS BLVD. -4-12-21 FOR BILLING INQUIRY: (319)291-4323
Description Total Price J
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
22674 05/26/2021 06/30/2021 2021-00000282 $80.00
Less Prepayment $0.00
Total Due —> $80.00
City of Waterloo
WATERLOO FIRE RESCUE r 44p.„RLo0
INSPECTION REPORT
AT&T&SPRINT MOBILE,2841 CROSSROADS BLVD,BLDG 2841 CROSSROADS BLVD, )//
WATERLOO/A 50702
DETAILS
Inspection Date:04/12/2021 Inspection Type:Annual Inspection(1Yr) I Inspection Number:5770 I Shift: N/A Station: N/A
Unit: N/A I Lead Inspector:JEFF SIEBEL ; Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 505.1 -Address identification New and existing buildings shall be provided with approved address identification.
The address identification shall be legible and placed in a position that is visible from
the street or road fronting the property.Address identification characters shall
contrast with their background.Address numbers shall be Arabic numbers or
alphabetical letters. Numbers shall not be spelled out. Each character shall be not
less than 4 inches(102 mm)high with a minimum stroke width of 1/2(12.7 mm).
Where required by the fire code official,address identification shall be provided in
additional approved locations to facilitate emergency response.Where access is by
means of a private road and the building cannot be viewed from the public way,a
monument,pole or other sign or means shall be used to identify the structure.
Address identification shall be maintained.
Inspector:JEFF SIEBEL-Comments:replace faded and peeling number on building.
FAIL 604.2.5-Exit signs Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments: Repair egress//exit lights:A. Front door B. Back of
Retail area.C. Rear exit.
Printed on 04/26/2021 41 09:40
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector:JEFF SIEBEL-Comments:properly mount electrical boxes by desk.
i
tit/
`y
FAIL 906.2-General requirements Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10. Exceptions:1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall
be allowed to be once every 3 years for dry-chemical or halogenated agent portable
fire extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1. Electronic
monitoring shall confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2. Loss of power or circuit continuity to the electronic
monitoring device shall initiate a trouble signal.2.3.The extinguishers shall be
installed inside of a building or cabinet in a noncorrosive environment.2.4. Electronic
monitoring devices and supervisory circuits shall be tested every 3 years when
extinguisher maintenance is performed.2.5.A written log of required hydrostatic
test dates for extinguishers shall be maintained by the owner to verify that
hydrostatic tests are conducted at the frequency required by NFPA 10.3.In Group 1-3,
portable fire extinguishers shall be permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments: provide annual service and properly mount fire
extinguisher 4"to 5 feet above floor in an accessible area.
GENERAL NOTES
JEFF SIEBEL-04/26/2021 @ 09:39 annual inspection$80
Printed on 04/26/2021 @ 09:40
Page 2 of 3
GENERAL NOTES
JEFF SIEBEL-04/26/2021 @ 09:40 provide corrections to avoid re-inspection fees.Several attempts made to obtain
contact information since 4/12
REINSPECTION DATE
05/13/2021
CONTACT SIGNATURE
Jake Williams (C/i
Signed on:04/26/2021 @ 09:37 h y
)21
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:04/26/2021 @ 09:37
fr
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 04/26/2021 @ 09:40