HomeMy WebLinkAbout1850 LOGAN AVE (2) INVOICE DATE DUE DATE INVOICE# TOTAL DUE
41411., 41..� 05/26/2021 06/30/2021 2021-00000277 $80.00
4terloo �o
Customer#: 13992 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
WALGREENS DRUG STORE 715 Mulberry St
1850 LOGAN AV WATERLOO, IA 50703
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 1850 LOGAN AVE-4-16-21 FOR BILLING INQUIRY: (319)291-4323
L Description ( Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
13992 05/26/2021 06/30/2021 2021-00000277 $80.00
Less Prepayment $0.00
Total Due-* $80.00
City of Waterloo
(,..":„(
�pTER(pO
ATERLOO FIRE RESCUE
INSPECTION REPORT
WALGREENS,1850 LOGAN AVE,BLDG 1850 LOGAN AVE,WATERLOO IA 50703 4740
DETAILS
Inspection Date:04/16/2021 Inspection Type:Annual Inspection(1Yr) I Inspection Number:4372 I Shift: N/A Station: N/A
Unit: N/A I Lead Inspector:JEFF SIEBEL ! Other Inspectors: N/A I Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1031.2-Reliability Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector:JEFF SIEBEL-Comments:remove storage from outside of back exit.Could
not open. Install permanent red sign with white letters stating"Fire Exit Door Do Not
Block"
FAIL 604.2.12-Means of egress Emergency power shall be provided for means of egress illumination in accordance
illumination with Sections 1008.3 and 1104.5.1.
Inspector:JEFF SIEBEL-Comments: Repair egress light in immunization room.
FAIL 604.4.2-Records Records of the inspection,testing and maintenance of emergency and standby
power systems shall include the date of service, name of the servicing technician,a
summary of conditions noted and a detailed description of any conditions requiring
correction and what corrective action was taken.Such records shall be maintained.
Inspector:JEFF SIEBEL-Comments:Provide documentation of testing of emergency
lights with all corrections completed with signature and date.
FAIL 605.5-Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring.
Extension cords and flexible cords shall not be affixed to structures,extended
through walls,ceilings or floors,or under doors or floor coverings, nor shall such
cords be subject to environmental damage or physical impact. Extension cords shall
be used only with portable appliances.
Inspector:JEFF SIEBEL-Comments:remove extension cord with box from behind
check out. Install permanent power with permits and inspections.
GENERAL NOTES
JEFF SIEBEL-04/19/2021 @ 09:08 Annual inspection$80.
Printed on 04/19/2021 @ 09:08
Page 1 of 2
REINSPECTION DATE
05/07/2021
CONTACT SIGNATURE
Mike-Assistant Manager � �j -7
Signed on:04/19/2021 @ 09:06
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:04/19/2021 @ 09:06
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 04/19/2021 @ 09:08
Page 2 of 2