COMMERCIAL INSPECTION -202 E 1ST-4-26-21 FOR BILLING INQUIRY: (319)291-4323
I_Description I Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
20693 05/26/2021 06/30/2021 2021-00000276 $80.00
Less Prepayment $0.00
Total Due—> $80.00
City of Waterloo
ac,) �i ATERLOO IRE RESCUE � :::0
INSPECTION REPORT
FRATERNAL ORDER OF EAGLES ARIE#764,202 E 1ST ST,BLDG 202 E 1ST ST,WATERLOO IA
4kzio.,
50703
DETAILS
Inspection Date:04/26/2021 j Inspection Type:Annual Inspection(1Yr) I Inspection Number:4548 I Shift: N/A I Station: N/A j
Unit: N/A I Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A I Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1031.2-Reliability Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
-- Inspector:JEFF SIEBEL-Comments:remove obstructions to front(desk)and rear exit
, doors.(movable wall)
'.- i ,: -\
FAIL 605.10.4-Prohibited areas Portable,electric space heaters shall not be operated within 3 feet(914 mm)of any
combustible materials. Portable,electric space heaters shall be operated only in
locations for which they are listed.
Inspector:JEFF SIEBEL-Comments: remove electric heater from Emoalonmthaey
FAIL 605.3-Working space and A working space of not less than 30 inches(762 mm)in width,36 inches(914.mm)in
clearance depth and 78 inches(1981 mm)in height shall be provided in front of electrical
service equipment.Where the electrical service equipment is wider than 30 inches
(762 mm),the working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1.Where other dimensions are required or allowed by NFPA 70.2.Access
�a" openings into attics or under-floor areas which provide a minimum clear opening of
2''''>------ -ruWf If ':` -- '� - 22 inches(559 mm)by 30 inches(762 mm).
s
Inspector:JEFF SIEBEL-Comments:remove obstructions to electrical panels and
disconnects. Maintain a 36"path to and around electrical panels.
Printed on 04/27/2021 @ 09:14
Page 1 of 3
STATUSDESCRIPTION
CODE
FAIL 605.4.3-Installation Relocatable power tap cords shall not extend through walls,ceilings,floors,under
doors or floor coverings,or be subject to environmental or physical damage.
Inspector:JEFF SIEBEL-Comments:remove ATM cord from door way.
� � r
FAIL 609.3.3-Cleaning Hoods,grease-removal devices,fans,ducts and other appurtenances shall be
cleaned at intervals as required by Sections 609.3.3.1 through 609.3.3.3.
Inspector:JEFF SIEBEL-Comments:provide current semi-annual kitchen hood
exhaust system cleaning inspection report with all discrepancies corrected.
Contractor must upload online to the Compliance Engine.
FAIL 609.3.3.3-Records Records for inspections shall state the individual and company performing the
inspection,a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the cleaning
and when the cleaning took place.Such records shall be completed after each
inspection or cleaning and maintained.
Inspector:JEFF SIEBEL-Comments:provide current semi-annual kitchen hood
exhaust system cleaning and fire suppression inspection report with all
discrepancies corrected.Contractor must upload online to the Compliance Engine.
FAIL 904.12.6.2-Extinguishing Automatic fire-extinguishing systems shall be serviced atl least every six months and
system service after activation of the system.Inspection shall be by qualified individuals,and a
certificate of inspection shall be forwarded to the fire code official upon completion.
Inspector:JEFF SIEBEL-Comments:provide current semi-annual kitchen hood fire
suppression system inspection report with all discrepancies corrected.Contractor
must upload online to the Compliance Engine.
GENERAL NOTES
JEFF SIEBEL-04/27/2021 @ 08:47 annual inspection$80
Printed on 04/27/2021 @ 09:14
Page 2 of 3
REINSPECTION DATE
05/17/2021
CONTACT SIGNATURE
Kevin Kressley (. _I
Signed on:04/27/2021 @ 09:08
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:04/27/2021 @ 09:08