WATERLOO FIRE RESCUE 00
INSPECTION REPORT l
VERVE KOMBUCHA,327 W 3RD ST,BLDG 327 W 3RD ST,WATERLOO IA 50702 44
DETAI S-. �.
Inspection Date:05/11/2021 i Inspection Type:Annual Inspection(1Yr) Inspection Number:4738 I Shift: N/A Station: N/A
Unit: N/A ; Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A I Fee:$80.00
STATUS CODE DESCRIPTION
FAIL 1010.1.3-Door opening force The force for pushing or pulling open interior swinging egress doors,other than fire
doors,shall not exceed 5 pounds(22 N).These forces do not apply to the force
required to retract latch bolts or disengage other devices that hold the door in a
closed position. For other swinging doors,as well as sliding and folding doors,the
door latch shall release when subjected to a 15-pound(67 N)force.The door shall be
set in motion when subjected to a 30-pound(133 N)force.The door shall swing to a
full-open position when subjected to a 15-pound(67 N)force.
Inspector:JEFF SIEBEL-Comments:repair walk through door to alley.Must open with
less than 15#force.
FAIL 6109.1 -General Storage of portable LP-gas containers of 1,000 pounds(454 kg)or less,whether filled,
partially filled or empty,at consumer sites or distribution points,and for resale by
dealers or resellers shall comply with Sections 6109.2 through 6109.1.5.1. Exceptions:
1. LP-gas containers that have not previously been in LP-gas service.2. LP-gas
containers at distribution plants.3. LP-gas containers at consumer sites or
distribution points,which are connected for use.
Inspector:JEFF SIEBEL-Comments:Remove all propane tanks from the building
including the 4 in the exit vestibule and in patio heaters in back storage area.See also
6109.4 and 6109.9
FAIL 904.12.6.2-Extinguishing Automatic fire-extinguishing systems shall be serviced at least every six months and
system service after activation of the system. Inspection shall be by qualified individuals,and a
certificate of inspection shall be forwarded to the fire code official upon completion.
Inspector:JEFF SIEBEL-Comments:provide current semi-annual kitchen hood fire
suppression inspection report with all discrepancies corrected.Contractor must
upload online to the compliance engine. 138 days overdue at this time.
GENERAL NOTES
JEFF SIEBEL-05/12/2021 @ 09:31 Annual Inspection$80
JEFF SIEBEL-05/12/2021 @ 09:31 Fire extinguishers due in June.
Printed on 05/12/2021 @ 09:35
Page 1 of 2
REINSPECTION DATE
06/01/2021
CONTACT SIGNATURE
Alex Hottle -' d Signed on:05/12/2021 @ 09:24t
°17 471 d
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:05/12/2021 @ 09:24
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 05/12/2021 @ 09:35