COMMERCIAL INSPECTION-225-229 E 4TH ST- 6-7-21 I FOR BILLING INQUIRY: (319)291-4323
I
LDescription
1 Total Price j
INSPECTION 2,000 $70.00
OCCUPANCY FEE
$10.00
CUSTOMER# BILLING DATE I DUE DATE CHARGES
22984 06/15/2021 07/30/2021/2021INVOICE#
2021-00000300
$80.00
Less Prepayment $0.00
Total Due--3 $80.00
City of Waterloo
--a-a7c64/
WATERLOO FIRE RESCUE R(oo
_.-INSPECTION REPORT
LOCALS,225-229 E 4TH ST,BLDG 22 -229 E 4TH ST,WATERLOO IA 50703
Inspection Date:06/07/2021 l Inspection Type:Annual Inspection(1Yr) Inspection Number:4564 l Shift: N/A i Station: N/A
Unit: N/A l Lead Inspector:JEFF SIEBEL I Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 604.2.5-Exit signs Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:repair egress/exit lights:A. Kitchen B.West end of
bar.
FAIL 605.5-Extension cords Extension cords and flexible cords shall not be a substitute for permanent wiring.
Extension cords and flexible cords shall not be affixed to structures,extended
through walls,ceilings or floors,or under doors or floor coverings, nor shall such
cords be subject to environmental damage or physical impact. Extension cords shall
be used only with portable appliances.
Inspector:JEFF SIEBEL-Comments: remove extension cord from refrigerator in
kitchen.The refrigerator must plug directly into the wall outlet.
FAIL 605.7-Appliances Electrical appliances and fixtures shall be tested and listed in published reports of
inspected electrical equipment by an approved agency and installed and maintained
in accordance with all instructions included as part of such listing.
Inspector:JEFF SIEBEL-Comments:freezer in basement must plug directly into wall
outlet in basement. Remove extension cord.
FAIL 609.3.3-Cleaning Hoods,grease-removal devices,fans,ducts and other appurtenances shall be
cleaned at intervals as required by Sections 609.3.3.1 through 609.3.3.3.
Inspector:JEFF SIEBEL-Comments:Provide current semi-annual kitchen hood
exhaust system cleaning inspection report with all discrepancies corrected.
Contractor must upload online to the compliance engine.
Printed on 06/08/2021 @ 08:55
Page 1 of 3
STATUS CODE DESCRIPTION
FAIL 609.3.3.3-Records Records for inspections shall state the individual and company performing the
inspection,a description of the inspection and when the inspection took place.
Records for cleanings shall state the individual and company performing the cleaning
and when the cleaning took place.Such records shall be completed after each
inspection or cleaning and maintained.
Inspector:JEFF SIEBEL-Comments: Provide current semi-annual kitchen hood
exhaust system cleaning and fire suppression inspection reportswith all
discrepancies corrected.Contractor must upload online to the compliance engine.
FAIL 904.12.5.2-Class K portable Where hazard areas include deep fat fryers,listed Class K portable fire extinguishers
fire extinguishers for deep fat shall be provided as follows: 1. For up to four fryers having a maximum cooking
f medium capacity of 80 pounds(36.3 kg)each:one Class K portable fire extinguisher
of a minimum 1.5-gallon(6 L)capacity.2. For every additional group of four fryers
having a maximum cooking medium capacity of 80 pounds(36.3 kg)each:one
additional Class K portable fire extinguisher of a minimum 1.5-gallon(6 L)capacity
shall be provided.3. For individual fryers exceeding 6 square feet(0.55 mA2)in
surface area:Class K portable fire extinguishers shall be installed in accordance with
the extinguisher manufacturer's recommendations.
Inspector:JEFF SIEBEL-Comments:properly mount sign above k guard extinguisher
in kitchen.
FAIL 904.12.6.2-Extinguishing Automatic fire-extinguishing systems shall be serviced at least every six months and
system service after activation of the system. Inspection shall be by qualified individuals,and a
certificate of inspection shall be forwarded to the fire code official upon completion.
Inspector:JEFF SIEBEL-Comments:Provide current semi-annual kitchen hood
exhaust system fire suppression inspection report with all discrepancies corrected.
Contractor must upload online to the compliance engine.
FAIL 906.2-General requirements Portable fire extinguishers shall be selected,installed and maintained in accordance
with this section and NFPA 10. Exceptions:1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall
be allowed to be once every 3 years for dry-chemical or halogenated agent portable
fire extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1. Electronic
monitoring shall confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2. Loss of power or circuit continuity to the electronic
monitoring device shall initiate a trouble signal.2.3.The extinguishers shall be
installed inside of a building or cabinet in a noncorrosive environment.2.4. Electronic
monitoring devices and supervisory circuits shall be tested every 3 years when
extinguisher maintenance is performed.2.5.A written log of required hydrostatic
test dates for extinguishers shall be maintained by the owner to verify that
hydrostatic tests are conducted at the frequency required by NFPA 10.3. In Group 1-3,
portable fire extinguishers shall be permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:provide annual service for fire extinguishers.
Printed on 06/08/2021 @ 08:55
Page 2 of 3
STATUS CODE
DESCRIPTION
FAIL
906.7-Hangers and brackets Hand-held portable fire extinguishers,not housed in cabinets,shall
be
the hangers or brackets supplied. Hangers or brackets shall be securely anchored to
the mounting surface in accordance with the manufacturer's installation instructions.
Inspector:JEFF SIEBEL-Comments:properly mount fire extinguisher sitting by dj
booth 4"to 5'above the floor.
GENERAL NOTES
JEFF SIEBEL-06/08/2021 @ 08:49 Annual inspection.$80
REINSPECTION DATE
07/06/2021
CONTACT SIGNATURE
Yashpal Saini /�
Signed on:06/08/2021 @ 08:52 Y ,„„ci
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:06/08/2021 @ 08:52
QUESTIONS ABOUT YOUR INSPECTION?
JEFF SIEBEL
Jeff.Siebel@Waterloo-ia.org
3192301224
Printed on 06/08/2021 @ 08:55