COMMERCIAL INSPECTION- 1459 ANSBOROUGH AVE-5-27-21 FOR BILLING INQUIRY: (319)291-4323
C Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
15106 06/15/2021 07/30/2021 2021-00000303 $80.00
Less Prepayment $0.00
Total Due— $80.00
City of Waterloo
W IRE RESCUE
\\S
__.�_.__ ,•� otINSPECT/ON REPORT- p,�
( NEWSTAR.1459 ANSBOROUGH AVE,BLDG 1459 ANSBOROUGH AVE,WATERLOO IA 50701 �
\DETAILS
Inspection ate:05/27/2021 I Inspection Type:Annual Inspection(1Yr) I Inspection Number:4569 I Shift: N/A I Station: N/A I
Unit: N/A I Lead Inspector:JE F SIEBEL I Other Inspectors: N/A
STATUS CODE DESCRIPTION
FAIL 102.4-Application of building The design and construction of new structures shall comply with the International
code Building Code,and any alterations,additions,changes in use or changes in
structures required by this code,which are within the scope of the International
Building Code,shall be made in accordance therewith.
Inspector:JEFF SIEBEL-Comments:obtain plumbing permit and inspections for water
heater installed in equipment room.
FAIL 305.1 -Clearance from Clearance between ignition sources,such as luminaires,heaters,flame-producing
ignition sources devices and combustible materials,shall be maintained in an approved manner.
Inspector:JEFF SIEBEL-Comments:remove obstructions to furnace. Maintain a
minimum of 36"clearance.
FAIL 5303.5.3-Securing Compressed gas containers,cylinders and tanks shall be secured to prevent falling
compressed gas containers, caused by contact,vibration or seismic activity.Securing of compressed gas
cylinders and containers,cylinders and tanks shall be by one of the following methods: 1.Securing
containers,cylinders and tanks to a fixed object with one or more restraints.2.
Securing containers,cylinders and tanks on a cart or other mobile device designed
for the movement of compressed gas containers,cylinders or tanks.3. Nesting of
compressed gas containers,cylinders and tanks at container filling or servicing
facilities or in sellers'warehouses not accessible to the public. Nesting shall be
allowed provided the nested containers,cylinders or tanks, if dislodged,do not
obstruct the required means of egress.4.Securing of compressed gas containers,
cylinders and tanks to or within a rack,framework,cabinet or similar assembly
designed for such use. Exception:Compressed gas containers,cylinders and tanks in
the process of examination,filling,transport or servicing.
Inspector:JEFF SIEBEL-Comments:secure compressed gas cylinders with chain in
equipment room.
FAIL 604.2.5-Exit signs Emergency power shall be provided for exit signs as required in Section 1013.6.3.The
system shall be capable of powering the required load for a duration of not less than
90 minutes.
Inspector:JEFF SIEBEL-Comments:A.repair egress/exit light above main door. B.
repair exit light above back door or remove and properly contain wiring in box with
cover. Exit not required by occupancy load.
Printed on 06/01/2021 @ 09:38
Page 1 of 4
STATUS CODE DESCRIPTION
FAIL 605.3-Working space and A working space of not less than 30 inches(762 mm)in width,36 inches(914 mm)in
clearance depth and 78 inches(1981 mm)in height shall be provided in front of electrical
service equipment.Where the electrical service equipment is wider than 30 inches
(762 mm),the working space shall be not less than the width of the equipment.
Storage of materials shall not be located within the designated working space.
Exceptions: 1.Where other dimensions are required or allowed by NFPA 70.2.Access
openings into attics or under-floor areas which provide a minimum clear opening of
22 inches(559 mm)by 30 inches(762 mm).
Inspector:JEFF SIEBEL-Comments:remove obstructions to electrical panel in
equipment room. maintain a minimum of 36"clearance.
FAIL 703.1 -Maintenance The required fire-resistance rating of fire-resistance-rated construction,including,
but not limited to,walls,firestops,shaft enclosures,partitions,smoke barriers,
floors,fire-resistive coatings and sprayed fire-resistant materials applied to
structural members and fire-resistant joint systems,shall be maintained.Such
elements shall be visually inspected by the owner annually and properly repaired,
restored or replaced where damaged,altered,breached or penetrated. Records of
inspections and repairs shall be maintained.Where concealed,such elements shall
not be required to be visually inspected by the owner unless the concealed space is
accessible by the removal or movement of a panel,access door, ceiling tile or similar
movable entry to the space.Openings made therein for the passage of pipes,
electrical conduit,wires,ducts,air transfer openings and holes made for any reason
shall be protected with approved methods capable of resisting the passage of smoke
and fire.Openings through fire-resistance-rated assemblies shall be protected by
self-or automatic-closing doors of approved construction meeting the fire protection
requirements for the assembly.
Inspector:JEFF SIEBEL-Comments:replace missing attic access door.
FAIL 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1. In new
and existing Group A, B,E,F,H,I,M, R-1, R-2, R-4 and S occupancies. Exception:In
Group R-2 occupancies,portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A: 10-B:C.2.Within 30 feet(9144 mm)
of commercial cooking equipment.3. In areas where flammable or combustible
liquids are stored, used or dispensed.4.On each floor of structures under
construction,except Group R-3 occupancies, in accordance with Section 3315.1.5.
Where required by the sections indicated in Table 906.1.6.Special-hazard areas,
including but not limited to laboratories,computer rooms and generator rooms,
where required by the fire code official.
Inspector:JEFF SIEBEL-Comments:provide a 21-10BC fire extinguisher outside in an
approved enclosure by gas pumps or on outside of building. Mount 4"to 5'above
the ground in an accessible location.
Printed on 06/01/2021 @ 09:38
Page 2 of 4
STATUS CODE DESCRIPTION
FAIL 906.2-General requirements Portable fire extinguishers shall be selected, installed and maintained in accordance
with this section and NFPA 10. Exceptions: 1.The distance of travel to reach an
extinguisher shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required and maintenance shall
be allowed to be once every 3 years for dry-chemical or halogenated agent portable
fire extinguishers that are supervised by a listed and approved electronic monitoring
device,provided that all of the following conditions are met:2.1. Electronic
monitoring shall confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2. Loss of power or circuit continuity to the electronic
monitoring device shall initiate a trouble signal.2.3.The extinguishers shall be
installed inside of a building or cabinet in a noncorrosive environment.2.4. Electronic
monitoring devices and supervisory circuits shall be tested every 3 years when
extinguisher maintenance is performed.2.5.A written log of required hydrostatic
test dates for extinguishers shall be maintained by the owner to verify that
hydrostatic tests are conducted at the frequency required by NFPA 10.3. In Group 1-3,
portable fire extinguishers shall be permitted to be located at staff locations.
Inspector:JEFF SIEBEL-Comments:provide annual service for fire extinguisher on
inside of building and mount 4"to 5'above the floor in an accessible location.
GENERAL NOTES
JEFF SIEBEL-06/01/2021 @ 09:38 finual inspection$80
J.
l,.
REINSPECTION DATE
06/16/2021
CONTACT SIGNATURE
Mamoon Akhther (�
Signed on:06/01/2021 @ 09:36 ' c%
1C ''
INSPECTOR SIGNATURE
JEFF SIEBEL
Signed on:06/01/2021 @ 09:36
Printed on 06/01/2021 @ 09:38
Page 3 of 4