WATERLOO FIRE RESCUE a
INSPECTION REPORT :
1736 FOREST AVE,WATERLOO IA S0702
OfTAILS
Inspection Date: 12/10/2021 1 Inspection Type: Rental Inspection j Inspection Number:6958 I Shi : N/A I Station: N/A I
Unit: N/A 1 Lead Inspector:BARRY STRATTON 1 Other Inspectors: N/A I Fee:$50.00 Z,Y
STATUS CODE DESCRIPTION
FAIL 1010.1.9-Door operations Except as specifically permitted by this section,egress doors shall be readily
openable from the egress side without the use of a key or special knowledge or
effort.
inspector:BARRY STRATTON-Comments:All interior doors are not capable of closing
and latching.
FAIL 1031.7-Emergency escape Required emergency escape and rescue openings shall be maintained in accordance
and rescue openings with the code in effect at the time of construction,and the following:Required
emergency escape and rescue openings shall be operational from the inside of the
room without the use of keys or tools. Bars,grilles,grates or similar devices are
allowed to be placed over emergency escape and rescue openings provided the
minimum net clear opening size complies with the code that was in effect at the time
of construction and such devices shall be releasable or removable from the inside
without the use of a key,tool or force greater than that which is required for normal
operation of the emergency escape and rescue opening.
Inspector:BARRY STRATTON-Comments:Bedroom in basement does not have an
egress window.House is only a 2 bedroom house and bedroom in basement is non-
conforming and needs removed.
FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector:BARRY STRATTON-Comments:Grounding strap loose on water pipe. Bath
outlet is not working. Bedroom outlet has hot/neutral reversed.Outlets need
replaced that have tension strength issues. Kitchen lights all need to be in working
condition.
FAIL 907.2.11 -Single-and Listed single-and multiple-station smoke alarms complying with UL 217 shall be
multiple-station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector:BARRY STRATTON-Comments:Smoke detectors needed in each bedroom,
also outside of the bedrooms and in basement.
Panted on 12/10/2021 le 12.08
Page 1 of 6
STATUS CODE DESCRIPTION
FAIL R4- Exterior Property Areas Is the exterior property area maintained in a clean,safe,and sanitary condition?This
includes grading and drainage,sidewalks and driveways,weeds,and pest
infestations.(iPMC 302)
Inspector: BARRY STRATTON-Comments:Broken windows needs repaired.
FAIL R5- Exterior Structure Is the exterior of the structure maintained in good repair,structurally sound and
sanitary state?(IPMC 304)
Inspector:BARRY STRATTON-Comments:Screen door needs replaced. Door does
not fit reasonably in its opening.
FAIL R6-interior Structure Has the interior of the structure and equipment inside been maintained in good
repair,structurally sound,and in a sanitary condition?(IPMC 305)
Inspector: BARRY STRATTON-Comments:Peeling paint,doors do not close and latch,
tub surround&tub need replaced, kitchen floor needs replaced,kitchen cabinets
missing doors,carpet is torn in areas and needs replaced.Need transition strips on
carpet in required floor transitions. Mice in unit needs exterminated. Basement has
leak coming from ceiling dropping sticky substance.
FAIL R6.A.- Interior Structure- Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1)
Unsafe Conditions
Inspector: BARRY STRATTON-Comments:Potential for mold to form in bathroom
from bath fan not working to manufactures specifications.
FAIL R6.B.-Residential Heating Are dwellings provided with heating facilities capable of maintaining a room
temperature of 68F?(IPMC 602.2)
Inspector:BARRY STRATTON-Comments:Need registers to be secured on all walls
and ducts to be connected to manufactures specifications. Register covers not on
terminations from walls.
FAIL R6.C.-Mechanical Eqiupment Are mechanical appliances properly installed and maintained in good working
condition?(iPMC 603.1)
Inspector: BARRY STRATTON-Comments:Refrigerator not cooling and another
refrigerator in house is nasty and needs cleaned.
GENERAL NOTES
Printed on 12/10/2021 e, 12.03
Page 2 of 6
BARRY STRATTON-12/10/2021 @ 12:02 106.4 Violation penalties.Any person who shall violate a provision of this code,or fail
to comply therewith,or with any of the requirements thereof,shall be prosecuted
within the limits provided by state or local laws. Each day that a violation continues
after due notice has been served shall be deemed a separate offense.Property is still
not registered and corrections have not been done.
BARRY STRATTON-12/10/2021 @ 12:03 9-7-4: LANDLORD LICENSE REQUIREMENT 9-7-5: RENTAL REGISTRATION PERMIT:Listed
address is not registered as a rental unit. Register all rentals units. Property is still not
registered.
BARRY STRATTON-12/1 0/2021 @ 12:03 Accurate And Complete Information:All information provided on the registration form
must be accurate and complete. No person shall provide inaccurate information for
the registration of a rental unit. Failure to provide the information required for such
registration shall be grounds for denial or nonrenewal.The landlord or the designated
responsible local agent shall sign the registration form,certifying to the accuracy and
completeness of the information provided.When the owner is not a natural person,
the owner information shall be that of the president,general manager or other chief
executive of the organization.When more than one person has an ownership interest,
the required information shall be provided on the registration form for each owner.
Currently manager is not licensed as a property manager.
BARRY STRATTON-12/10/2021 @ 12:03 302.5 Rodent harborage.Structures and exterior property shall be kept free from
rodent harborage and infestation.Where rodents are found,they shall be promptly
exterminated by approved processes that will not be injurious to human health.After
pest elimination,proper precautions shall be taken to eliminate rodent harborage and
prevent re-infestation.(Mice)
BARRY STRATTON-12/10/2021 @ 12:03 304.12 Handrails and guards. Every handrail and guard shall be firmly fastened and
capable of supporting normally imposed loads and shall be maintained in good
condition. Need handrails on basement stairs.
BARRY STRATTON-12/10/2021 @ 12:04 304.13 Window,skylight and door frames. Every window,skylight,door and frame shall
be kept in sound condition,good repair and weather tight.
BARRY STRATTON-12/10/2021 @ 12:04 304.15 Doors. Exterior doors, door assemblies,operator systems if provided,and
hardware shall be maintained in good condition. Locks at all entrances to dwelling
units and sleeping units shall tightly secure the door. Locks on means of egress doors
shall be in accordance with Section 702.3.
BARRY STRATTON-12/10/2021 @ 12:04 305.3 Interior surfaces. Interior surfaces,including windows and doors,shall be
maintained in good,clean and sanitary condition.Peeling,chipping,flaking or abraded
paint shall be repaired,removed or covered.Cracked or loose plaster,decayed wood
and other defective surface conditions shall be corrected.
Printed on 12/10/2021 12:08
Page 3 of 6
GENERAL NOTES
BARRY STRATTON-12/10/2021 @ 12:04 305.4 Stairs and walking surfaces.Every stair,ramp,landing,balcony,porch,deck or
other walking surface shall be maintained in sound condition and good repair.
BARRY STRATTON-12/10/2021 @ 12:05 305.6 Interior doors.Every interior door shall fit reasonably well within its frame and
shall be capable of being opened and closed by being properly and securely attached
to jambs headers or tracks as intended by the manufacturer of the attachment
hardware.
BARRY STRATTON-12/10/2021 @ 12:05 309,1 Infestation.Structures shall be kept free from insect and rodent infestation.
Structures in which insects or rodents are found shall be promptly exterminated by
approved processes that will not be injurious to human health.After pest elimination,
proper precautions shall be taken to prevent reinfestation.
BARRY STRATTON-12/10/2021 @ 12:05 403.2 Bathrooms and toilet rooms. Every bathroom and toilet room shall comply with
the ventilation requirements for habitable spaces as required by Section 403.1,except
that a window shall not be required in such spaces equipped with a mechanical
ventilation system.Air exhausted by a mechanical ventilation system from a bathroom
or toilet room shall discharge to the outdoors and shall not be recirculated.
BARRY STRATTON-12/10/2021 @ 12:05 504.1 General.Plumbing fixtures shall be properly installed and maintained in working
order,and shall be kept free from obstructions,leaks and defects and be capable of
performing the function for which such plumbing fixtures are designed. Plumbing
fixtures shall be maintained in a safe,sanitary and functional condition. Bathtub and
surround need replaced.
BARRY STRATTON-12/10/2021 @ 12:05 503.4 Floor surface. In other than dwelling units,every toilet room floor shall be
maintained to be a smooth,hard, nonabsorbent surface to permit such floor to be
easily kept in a clean and sanitary condition.
BARRY STRATTON-12/10/2021 @ 12:06 603.1 Mechanical appliances. Mechanical appliances,fireplaces,solid fuel-burning
appliances,cooking appliances and water heating appliances shall be properly
installed and maintained in a safe working condition,and shall be capable of
performing the intended function.
BARRY STRATTON-12/10/2021 @ 12:06 604.3 Electrical system hazards.Where it is found that the electrical system in a
structure constitutes a hazard to the occupants or the structure by reason of
inadequate service,improper fusing,insufficient receptacle and lighting outlets,
improper wiring or installation,deterioration or damage,or for similar reasons,the
code official shall require the defects to be corrected to eliminate the hazard.
BARRY STRATTON-12/10/2021 @ 12:06 607.1 General. Duct systems shall be maintained free of obstructions and shall be
capable of performing the required function.
Printed on 12/10/2021+c 12:Os,
Page 4 of 6
GENERAL NOTES
BARRY STRATTON-12/10/2021 @ 12:06 702.4 Emergency escape openings.Required emergency escape openings shall be
maintained in accordance with the code in effect at the time of construction,and the
following. Required emergency escape and rescue openings shall be operational from
the inside of the room without the use of keys or tools. Bars,grilles,grates or similar
devices are permitted to be placed over emergency escape and rescue openings
provided the minimum net clear opening size complies with the code that was in effect
at the time of construction and such devices shall be releasable or removable from the
inside without the use of a key,tool or force greater than that which is required for
normal operation of the escape and rescue opening.
BARRY STRATTON-12/10/2021 @ 12:06 9-7-6:DENIAL,SUSPENSION,REVOCATION OR NONRENEWAL:A.Grounds:The licensing
officer or building official may revoke,suspend,deny or decline to renew any landlord
license issued under section 9-7-4 of this chapter or any rental registration permit
issued under section 9-7-5 of this chapter for any of the following grounds: 1. False
statements on any application or other information or report required by this section
to be given by the applicant or licensee.2. Failure to pay any application, penalty,
reinspection or reinstatement fee required by this chapter or city council resolution. 3.
Failure to correct deficiencies noted in notices of violation within the time specified in
the notice.4. Failure to comply with the provisions of a mitigation or remediation plan
approved by the building official or designee. 5. Failure to comply with the provisions of
title VIII of the fair housing act of 1968(as amended).6.Allowing rental units to be
occupied after the tenant has violated the crime free lease addendum required by
section 9-7-8 of this chapter and failing to take reasonable and effective remedial
action when such violative conduct occurs.7. Failure to implement the crime free lease
addendum required by section 9-7-8 of this chapter on all new and renewal lease
agreements.8. Failure to provide proof of the insurance referred to in subsection 9-7-
5A of this chapter upon request of the city clerk.9. Designation of a rental unit or the
larger structure of which it is a part as an unsafe structure by the building official or his
designee.
BARRY STRATTON-12/10/2021 @ 12:07 Corrections from initial inspection have not been done. Property is not registered as a
rental unit.
REINSPECTION DATE
01/10/2022
CONTACT SIGNATURE
Abigail Matamoros
Signed on:12/10/2021 @ 12:07
Printed on 12/1 012021 1 12.03
Page 5 of 6
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on: 12/10/2021 @ 12:07
QUESTIONS ABOUT YOUR INSPECTION?
BARRY STRATTON
barry.stratton@waterloo-ia.org
(319)231-9147
Panted on 12r10;2021 1.12.OS
Page 6 of 6