HomeMy WebLinkAbout217 E 1ST ST (2) (;t ► 0 \
LTTLIt1P?R? FIRE RESCUE
cow
217 E 1ST ST, WATERLOO IA S07 03 9‘Ci
DETAILS .(1.4)
Inspection Date:02/10/2022 I Inspection Type: Rental Inspection Inspection Number:7227 Shift: N/A Station: N/A I
Unit: N/A I Lead Inspector:BARRY STRATTON [ Other Inspectors: N/A j Fee:$50.00
STATUS CODE DESCRIPTION
FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector: BARRY STRATTON-Comments:Electric system is not grounded.SEU Cable
on house needs replaced.Service entrance box is detached from house.Outlets in
unit have bad grounds. Need approved covers on all outlets and switches.Contact
licensed professional to make electrical corrections.Electric service on exterior of
house still not corrected.
FAIL 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1.In new
and existing Group A,B,E,F, H, I, M, R-1,R-2, R-4 and S occupancies. Exception: In
Group R-2 occupancies,portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A:10-B:C.2.Within 30 feet(9144 mm)
of commercial cooking equipment.3. In areas where flammable or combustible
liquids are stored, used or dispensed.4.On each floor of structures under
construction,except Group R-3 occupancies, in accordance with Section 3315.1.5.
Where required by the sections indicated in Table 906.1.6.Special-hazard areas,
including but not limited to laboratories,computer rooms and generator rooms,
where required by the fire code official.
Inspector:BARRY STRATTON-Comments:
FAIL 907.2.11 -Single-and Listed single-and multiple-station smoke alarms complying with UL 217 shall be
multiple-station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
11041
alarms
Inspector: BARRY STRATTON-Comments:Smoke detectors need installed to code
FAIL 915.1 -General Carbon monoxide detection shall be installed in new buildings in accordance with
Sections 915.1.1 through 915.6.Carbon monoxide detection shall be installed in
existing buildings in accordance with Section 1103.9.
Inspector:BARRY STRATTON-Comments:
Prsnteo on O2 1 OJ2O22 1:14:0
Page 1 of 2
STATUS CODE DESCRIPTION
FAIL R5- Exterior Structure Is the exterior of the structure maintained in good repair,structurally sound and
sanitary state?(IPMC 304)
Inspector:BARRY STRATTON-Comments:Electrical service box on house needs
replaced.SEU cable needs replaced.
FAIL R6-Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair,structurally sound,and in a sanitary condition?(IPMC 305)
Inspector: BARRY STRATTON-Comments:Ceiling in living room damaged from water
leak. Peeling paint needs corrected.
GENERAL NOTES
BARRY STRATTON-02/10/2022 @ 14:01 9-7-4 9-7-5:2022 Rental registration is needed for all rental units.
BARRY STRATTON-02/10/2022 @ 14:01 IPMC 106.4:Failure to make required corrections citation(s)shall be issued$500.00
plus Costs$95.00=$595.00
REINSPECTION DATE
03/10/2022
CONTACT SIGNATURE
Marilu Sanchez JI tL
Signed on:02/10/2022 @ 14:01 /
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on:02/10/2022 @ 14:01
QUESTIONS ABOUT YOUR INSPECTION?
BARRY STRATTON
barry.stratton@waterloo-ia.org
(319)231-9147
Printed on O2.'0,2,22 Cs',4'_02
Page 2 of 2