INSPECTION REPORT
b013
1738 FLOWER ST,WATERLOO IA S0701At.. \ 12 ; `
DETAILS
Inspection Date:02/01/2022 I Inspection Type: Rental Inspection I Inspection Number:7183 I Shift: IA Station: N/A I
Unit: N/A I Lead Inspector:BARRY STRATTON I Other Inspectors: N/A I Fee:$50.00
STATUS CODE DESCRIPTION
FAIL 1010.1.9-Door operations Except as specifically permitted by this section,egress doors shall be readily
openable from the egress side without the use of a key or special knowledge or
effort.
Inspector: BARRY STRATTON-Comments:Several doors missing hardware.
Corrections still not done.
FAIL 1018.1 -General Aisles and aisle accessways serving as a portion of the exit access in the means of
egress system shall comply with the requirements of this section.Aisles or aisle
accessways shall be provided from all occupied portions of the exit access that
contain seats,tables,furnishings,displays and similar fixtures or equipment.The
minimum width or required capacity of aisles shall be unobstructed.Exception:
Encroachments complying with Section 1005.7.
Inspector:BARRY STRATTON-Comments:Egress/exit lights not working. Lights and
signage still not working
FAIL 1031.2-Reliability Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector:BARRY STRATTON-Comments:
FAIL 1031.7-Emergency escape Required emergency escape and rescue openings shall be maintained in accordance
and rescue openings with the code in effect at the time of construction,and the following:Required
emergency escape and rescue openings shall be operational from the inside of the
room without the use of keys or tools. Bars,grilles,grates or similar devices are
allowed to be placed over emergency escape and rescue openings provided the
minimum net clear opening size complies with the code that was in effect at the time
of construction and such devices shall be releasable or removable from the inside
without the use of a key,tool or force greater than that which is required for normal
operation of the emergency escape and rescue opening.
Inspector:BARRY STRATTON-Comments:Broken windows need replaced.Broken
windows in exit discharge doors frames on rear of building.
Printed an 02/01/2022 ce 13:37
Page 1 of 5
STATUS CODE DESCRIPTION
FAIL 505.1 -Address identification New and existing buildings shall be provided with approved address identification.
The address identification shall be legible and placed in a position that is visible from
the street or road fronting the property.Address identification characters shall
contrast with their background.Address numbers shall be Arabic numbers or
alphabetical letters. Numbers shall not be spelled out.Each character shall be not
less than 4 inches(102 mm)high with a minimum stroke width of 1/2(12.7 mm).
Where required by the fire code official,address identification shall be provided in
additional approved locations to facilitate emergency response.Where access is by
means of a private road and the building cannot be viewed from the public way,a
monument,pole or other sign or means shall be used to identify the structure.
Address identification shall be maintained.
Inspector: BARRY STRATTON-Comments:Unit numbers need to be listed on
apartment door
FAIL 605.1 -Abatement of Identified electrical hazards shall be abated.Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector:BARRY STRATTON-Comments:Electric panel cover in unit#3 needs
secured.Outlets missing covers.Lights missing globes. Multi plug adapters need
removed. Exhaust fan above stove has exposed wires.Outlets not working. Extension
cords to lights running under door to common hallway.Also extension cords wired
into baseboard heaters
FAIL 901.6-Inspection,testing and Fire detection,alarm,and extinguishing systems,mechanical smoke exhaust
maintenance systems,and smoke and heat vents shall be maintained in an operative condition at
all times,and shall be replaced or repaired where defective. Nonrequired fire
protection systems and equipment shall be inspected,tested and maintained or
removed.
Inspector:BARRY STRATTON-Comments:Alarm testing and maintenance still not
done.
FAIL 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations:1.In new
and existing Group A, B,E,F, H, I, M, R-1,R-2,R-4 and S occupancies. Exception: In
Group R-2 occupancies,portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A:10-B:C.2.Within 30 feet(9144 mm)
of commercial cooking equipment.3. In areas where flammable or combustible
liquids are stored, used or dispensed.4.On each floor of structures under
construction,except Group R-3 occupancies, in accordance with Section 3315.1.5.
Where required by the sections indicated in Table 906.1.6.Special-hazard areas,
including but not limited to laboratories,computer rooms and generator rooms,
where required by the fire code official.
Inspector:BARRY STRATTON-Comments:
Printed on 02/01/2022 :3:37
Page 2 of 5
6
STATUS CODE DESCRIPTION
FAIL 907.2.11 -Single-and Listed single-and multiple-station smoke alarms complying with UL 217 shall be
multiple-station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector:BARRY STRATTON-Comments:Need smoke detectors installed in each
bedroom and outside of the bedrooms.
FAIL R2-Unsafe Equipment Was the presence of unsafe equipment noted during the inspection?Equipment may
include boilers,heating equipment,elevator,moving stairways,electrical wiring,and
flammable liquid containers.(IPMC 108.1.2)
Inspector: BARRY STRATTON-Comments:Water leaking into electric pane. Need
licensed professional to check panel and breakers for water damage.604.3.1
Abatement of electrical hazards associated with water exposure.The provisions of
this section shall govern the repair and replacement of electrical systems and
equipment that have been exposed to water
FAIL R4-Exterior Property Areas Is the exterior property area maintained in a clean,safe,and sanitary condition?This
includes grading and drainage,sidewalks and driveways,weeds,and pest
infestations.(IPMC 302)
Inspector:BARRY STRATTON-Comments:Concrete block not repaired
FAIL R5- Exterior Structure Is the exterior of the structure maintained in good repair,structurally sound and
sanitary state?(IPMC 304)
Inspector:BARRY STRATTON-Comments:Debris all over property
FAIL R6-Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair,structurally sound,and in a sanitary condition?(IPMC 305)
Inspector:BARRY STRATTON-Comments:Black mold,fire safety items not addressed,
exit/egress lights not addressed,broken windows,common area floors,&alarm
FAIL R6A.-Interior Structure- Were any unsafe conditions noted during the interior inspection?(IPMC 305.1.1)
Unsafe Conditions
Inspector: BARRY STRATTON-Comments:Ceiling in kitchen has water leak.
Mechanical closet in bedroom has large water leak. Black mold on walls. Damaged
drywall needs removed and replaced. Living room windows leaking water.Doors
missing hardware.
FAIL R6.B.-Residential Heating Are dwellings provided with heating facilities capable of maintaining a room
temperature of 68F?(IPMC 602.2)
Inspector:BARRY STRATTON-Comments:Furnace needs maintenance
Printed an 02/01/2022 13:37
Page 3 of 5
STATUS CODE DESCRIPTION
FAIL R6.C.-Mechanical Eqiupment Are mechanical appliances properly installed and maintained in good working
condition?(IPMC 603.1)
Inspector:BARRY STRATTON-Comments:Supply lines to water heater not installed to
code.Stove has broken handle and burners not working.
GENERAL NOTES
BARRY STRATTON-02/01/2022 @ 13:35 Unit#3 and common areas
BARRY STRATTON-02/01/2022 @ 13:35 604.3 Electrical system hazards.Where it is found that the electrical system in a
structure constitutes a hazard to the occupants or the structure by reason of
inadequate service,improper fusing, insufficient receptacle and lighting outlets,
improper wiring or installation,deterioration or damage,or for similar reasons,the
code official shall require the defects to be corrected to eliminate the hazard.604.3.1
Abatement of electrical hazards associated with water exposure.The provisions of this
section shall govern the repair and replacement of electrical systems and equipment
that have been exposed to water
BARRY STRATTON-02/01/2022 @ 13:36 9-7-6:DENIAL,SUSPENSION,REVOCATION OR NONRENEWAL:A.Grounds:The licensing
officer or building official may revoke,suspend,deny or decline to renew any landlord
license issued under section 9-7-4 of this chapter or any rental registration permit
issued under section 9-7-5 of this chapter for any of the following grounds:3. Failure to
correct deficiencies noted in notices of violation within the time specified in the notice.
Court Order still not complied with.(Contempt)
REINSPECTION DATE
03/01/2022
CONTACT SIGNATURE
Dominic Tangen F
Signed on:02/01/2022 @ 13:36
BARRY STRATTON
Signed on:02/01/2022 @ 13:36
Printed an 02/01i2022(13:37