INSPECTION REPORT
fi
BLDG 314 RANDOLPH ST,314 RANDOLPH ST,WATERLOO IA 50701 C
DETAILS
Inspection Date:01/20/2022 1 Inspection Type: Rental Inspection j Inspection Number:7149 I S 'fit: /A I Station: N/A 1
Unit: N/A j Lead Inspector:BARRY STRATTON ( Other Inspectors: N/A l Fee:$50.00
STATUS CODE DESCRIPTION
FAIL 1104.16- Fire escape Fire escape stairways shall comply with Sections 1104.16.1 through 1104.16.7.
stairways
Inspector:BARRY STRATTON-Comments:
FAIL 2015 IFC-Fire alarm testing Is the fire alarm system powered,operational and displaying normal operation(no
and maintenance troubles,supervisory,or alarms)?
Inspector:BARRY STRATTON-Comments:Several violations with sprinkler system
that need corrected.
FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector:BARRY STRATTON-Comments:Extension cords still in use.
FAIL 901.6-Inspection,testing and Fire detection,alarm,and extinguishing systems,mechanical smoke exhaust
maintenance systems,and smoke and heat vents shall be maintained in an operative condition at
all times,and shall be replaced or repaired where defective. Nonrequired fire
protection systems and equipment shall be inspected,tested and maintained or
removed.
Inspector: BARRY STRATTON-Comments:Alarm 37 days past due and sprinkler has
several deficiencies that need corrected.
FAIL 901.6.1 -Standards Fire protection systems shall be inspected,tested and maintained in accordance with
the referenced standards listed in Table.
Inspector: BARRY STRATTON-Comments:
FAIL 901.6.2-Records Records of all system inspections,tests and maintenance required by the referenced
standards shall be maintained.
Printed on 01/20 2022 c;1317
Page 1 of 3
STATUS CODE DESCRIPTION
Inspector:BARRY STRATTON-Comments:
FAIL R2-Unsafe Equipment Was the presence of unsafe equipment noted during the inspection?Equipment may
include boilers,heating equipment,elevator,moving stairways,electrical wiring,and
flammable liquid containers.(IPMC 108.1.2)
Inspector: BARRY STRATTON-Comments:Fire escape on rear of building still not
corrected and still not certified.
FAIL R5-Exterior Structure Is the exterior of the structure maintained in good repair,structurally sound and
sanitary state?(IPMC 304)
Inspector:BARRY STRATTON-Comments:Fire escape.
FAIL R6-Interior Structure Has the interior of the structure and equipment inside been maintained in good
repair,structurally sound,and in a sanitary condition?(IPMC 305)
Inspector: BARRY STRATTON-Comments:Sprinkler in closet in bedroom is still
missing an escutcheon.Sprinkler and alarm need maintenance.
GENERAL NOTES
BARRY STRATTON-01/20/2022 @ 13:15 702.1 General.A safe,continuous and unobstructed path of travel shall be provided
from any point in a building or structure to the public way. Means of egress shall
comply with the International Fire Code.Appliances still not removed from 3rd Floor.2
refrigerators and 1 stove.
BARRY STRATTON-01/20/2022 @ 13:16 9-7-4 9-7-5:Updated owner and management information still not received.
BARRY STRATTON-01/20/2022 @ 13:17 106.4 Violation penalties.Any person who shall violate a provision of this code,or fail
to comply therewith,or with any of the requirements thereof,shall be prosecuted
within the limits provided by state or local laws. Each day that a violation continues
after due notice has been served shall be deemed a separate offense.
REINSPECTION DATE
02/18/2022
Printed on 31,20/2022;a 1317
Page 2 of 3
CONTACT SIGNATURE
Prairie Rapids Apartments LLC Z, r
Signed on:01/20/2022 @ 13:17
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on:01/20/2022 @ 13:17