INSPECTION REPORT
8;r 11 W 3RD St WATERLOO IA 50701 \ cukbA �;'
DETAILS 5
r3
inspection Date:03/04/2022 I Inspection Type: Rental Inspection I Inspection Number:7328 I Shift: N/A I Station: N/A
Unit: N/A Lead Inspector:BARRY STRATTON I Other Inspectors: N/A Fee:$50.00 9�14)� 1is °
STATUS CODE DESCRIPTION
FAIL 1031.2-Reliability Required exit accesses,exits and exit discharges shall be continuously maintained
free from obstructions or impediments to full instant use in the case of fire or other
emergency where the building area served by the means of egress is occupied.An
exit or exit passageway shall not be used for any purpose that interferes with a
means of egress.
Inspector:BARRY STRATTON-Comments:Front door replaced but door hardware not
installed to code.Only dead bolt installed in lock set and no door knob assembly in
door.
FAIL 605.1 -Abatement of Identified electrical hazards shall be abated. Identified hazardous electrical conditions
electrical hazards in permanent wiring shall be brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment that is modified or
damaged and constitutes an electrical shock or fire hazard shall not be used.
Inspector:BARRY STRATTON-Comments:Bath fan
FAIL 906.1 -Where required Portable fire extinguishers shall be installed in all of the following locations: 1.In new
and existing Group A,B,E, F, H, I, M,R-1,R-2, R-4 and S occupancies. Exception: In
Group R-2 occupancies, portable fire extinguishers shall be required only in locations
specified in Items 2 through 6 where each dwelling unit is provided with a portable
fire extinguisher having a minimum rating of 1-A:10-B:C.2.Within 30 feet(9144 mm)
of commercial cooking equipment.3. In areas where flammable or combustible
liquids are stored,used or dispensed.4.On each floor of structures under
construction,except Group R-3 occupancies,in accordance with Section 3315.1. 5.
Where required by the sections indicated in Table 906.1.6.Special-hazard areas,
including but not limited to laboratories,computer rooms and generator rooms,
where required by the fire code official.
Inspector:BARRY STRATTON-Comments:
FAIL 907.2.11 -Single-and Listed single-and multiple-station smoke alarms complying with UL 217 shall be
multiple-station smoke installed in accordance with Sections 907.2.11.1 through 907.2.11.6 and NFPA 72.
alarms
Inspector:BARRY STRATTON-Comments:
Printed on 03/04,2022 0 11:51
Page 1 of 3
. '
STATUS CODE ' DESCRIPTION `
FAIL 915.1 Genera} Cat-bon monoxide detection shall be installed in new buildings in accordance with
Sections 015.1.1 through 915.6. Carbon monoxide detection shall be installed in
existing buildings in accordance with Section 1103.9.
Inspector: 8ARRv STRATTOm Comments:
FAIL RS Exterior Structure Is the exterior of the srructure maintained in good repair'szructuraUy snund and
sanitary state?(|P/N[304)
Inspector: BARRYSTRATT0N Comments: Front door and front step at entrance the
rise is to tall.
FAIL RG Interior Structure Has the interior of the suuoure and equipment inside been maintained in good
repair'structurally sound' and in a sanitary condition!(|prNC 305)
Inspector: 8ARRY STRxTTOw Comments: Front door needs replaced. Door broken
and doora|so does not fit reasonably in jamb. Peeling paint in shower on ceiling.
Back bedroom has mold growth from water damage. Removed all damaged drywall
and replace. Interior doors missing.
FAIL R0.x. Interior Structure- Were any Unsafe conditions noted during the interior inspection?(IPMC 305.1.1)
Unsafe Conditions
Inspector: BARRYSTR/TTON Comments:Security
GENERAL NOTES '
8ARRY STRAlTON 03/04/2822 @ 1 1:47 Un|c# 1
BARRv STRATT0N 82/04/2822 @ 11:47 304.15 Doors. Exterior doors' door assemb|ies, operator systenns if provided, and
hardware shall be maintained in good condition. Locks at all entrances to dwelling
units and sleeping units shall tightly secure the door. Locks on means of egress doors
shall be in accordance with Section 702.3.
BARRYSTRATT0m 03/04/2022 @ 1 1:47 305.0 Interior doors. Every interior door shall fit reasonably well within its frame and
shall be capable of being opened and closed by being properly and securely attached
to jambs,
8ARRvSTRA7TON 03/04/2022 @o 11:47 305.3 Interior Surfaces, Interior surfaces,including windows and doors,shall be
maintained in good,cleat)and sanitary condition. Peeling,chipping'flaking o/'abraded
paint shall be repaired, removed or covered, Cracked or loose plaster,decayed wood
and other defective surface conditions shall he corrected.
p,/".°""noy,owzmz2'm``.s`
Paoazuro
s _
GENERAL NOTES
BARRY STRATTON-03/04/2022 @ 11:47 403.6 Mold Present In A Rental Unit.a.When mold is found to be visibly present in
small amounts, it can be cleaned in a safe and sanitary manner. b.When mold is found
in a rental unit and is determined to be a health risk,the building official may order
that a clean air report be obtained from a mold specialist approved by the building
official.
BARRY STRATTON-03/04/2022 @ 11:47 304.10 Stairways,decks,porches and balconies. Every exterior stairway,deck, porch
and balcony,and all appurtenances attached thereto,shall be maintained structurally
sound, in good repair,with proper anchorage and capable of supporting the imposed
loads.
BARRY STRATTON-03/04/2022 @ 11:50 702.3 Locked doors. Means of egress doors shall be readily openable from the side
from which egress is to be made without the need for keys, special knowledge or effort,
except where the door hardware conforms to that permitted by the International
Building Code. Required emergency escape and rescue openings shall be operational
from the inside of the room without the use of keys or tools.
REINSPECTION DATE
04/04/2022
CONTACT SIGNATURE
Adam Hunemuller -A6,.,_
Signed on:03/04/2022 @ 11:51
INSPECTOR SIGNATURE
BARRY STRATTON
Signed on:03/04/2022 @ 11:51