COMMERCIAL FIRE INSPECTION- 1542 FLAMMANG DR- FOR BILLING INQUIRY: (319)291-4323
08/12/2026
Description Total Price
INSPECTION 2,000 HH $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
4709 08/20/2026 09/25/2026 2027-00000085 $100.00
Less Prepayment $0.00
Total Due—> $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
?,,„„,`* Waterloo Fire Rescue
Inspection Report 425 E.3rd Street
Staples-1542 Flammang DR,BLDG 1542 Flammang Dr,Waterloo IA 50702
INSPECTION DETAILS
Inspection Date Inspection Type f� Inspection Number
0811212026 Annual Inspection(1Yr) Inn
J 10 1043
Lead Inspector Shift Station Unit
BRAD BALDWIN N/A N/A NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
038 k� 22 ® 25
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
09/14/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-0811212026 @ 15:18
c •$3.10 annual inspection fee
BRAD BALDWIN-08/12/2026 @ 15:18
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#0)-Cell:319-230-1224
BRAD BALDWIN-08/1212026 @ 15:19
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-08/12/2026 @ 15:28
Annual fire alarm and sprinkler system inspections due by 9117/26.Reports of inspections required to be uploaded to Compliance Engine including
deficiencies repaired.
BRAD BALDWIN-08/1212026 @ 15:31
Fire extinguishers due annually serviced by September 2026.
BRAD BALDWIN-08113/2026 @ 07:02
Corrected on site during 8112126 inspection:Removed laminator equipment from extension cord and cord was removed from walkway.Laminator shall
plug to a permanent outlet,adding a new outlet requires a licensed electrical contractor to obtain permit and inspection.
SIGNATURES
Contact signature Inspector signature
No signature
Report completededpost ostinspection
GENERATED ON 8/13/28, 7:42 AM 1 OF 11
General Manager(Brooke)2026 Date: BRAD BALDWIN 0811312026
CHECKLISTS
Means of Egress
stain. code Description
Fail 1032,2-Reliability.
Required exit accesses,exits and exit discharges shall be Location:Exit hallway near manager's officeibreakroom
continuously maintained free from obstructions or Comments:Remove all items and storage in hallway,all portions of a
impediments to full instant use in the case of fire or other required exit path shall remain unobstructed at all times.No storage
emergency where the building area served by the means of shall be kept in hallway.
egress is occupied.An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
\r-spm,
GENERATED ON 8/13/28, 7:42 AN 2 OF 11
Additional Codes
Stasis code Description
Fail 1013.1-Where required.
Exits and exit access doors shall be marked by an approved Location:NW corner-Sales floor
exit sign readily visible from any direction of egress travel. Comments:Rotate exit sign to direct path of egress from view of
The path of egress travel to exits and within exits shall be western most aisle.
marked by readily visible exit signs to clearly indicate the
direction of egress travel in cases where the exit or the path
of egress travel is not immediately visible to the occupants.
Intervening means of egress doors within exits shall be
marked by exit signs.Exit sign placement shall be such that
any point in an exit access corridor or exit passageway is
within 100 feet(30 480 mm)or the listed viewing distance of
the sign,whichever is less,from the nearest visible exit sign.
Exceptions:1.Exit signs are not required in rooms or areas
that require only one exit or exit access.2.Main exterior exit
doors or gates that are obviously and clearly identifiable as
exits need not have exit signs where approved by the fire
code official.3.Exit signs are not required in occupancies in
Group U and individual sleeping units or dwelling units in
Group R-1,R-2 or R-3.4.Exit signs are not required in
dayrooms,sleeping rooms or dormitories in occupancies in
Group 1-3.5.In occupancies in Groups A-4 and A-5,exit signs
are not required on the seating side of vomitories or openings
into seating areas where exit signs are provided in the
concourse that are readily apparent from the vomitories.
Egress lighting is provided to identify each vomitory or
opening within the seating area in an emergency.
Fail 1013.1-Where required.
Exits and exit access doors shall be marked by an approved Location:SE corner-Above desk chairs
exit sign readily visible from any direction of egress travel. Comments:Rotate exit sign to point egress path of travel towards
The path of egress travel to exits and within exits shall be rear exit.
marked by readily visible exit signs to clearly indicate the
direction of egress travel in cases where the exit or the path
of egress travel is not immediately visible to the occupants.
Intervening means of egress doors within exits shall be
marked by exit signs.Exit sign placement shall be such that
any point in an exit access corridor or exit passageway is
within 100 feet(30 480 mm)or the listed viewing distance of
the sign,whichever is less,from the nearest visible exit sign.
Exceptions:1.Exit signs are not required in rooms or areas
that require only one exit or exit access.2.Main exterior exit
doors or gates that are obviously and clearly identifiable as
exits need not have exit signs where approved by the fire
code official.3.Exit signs are not required in occupancies in
Group U and individual sleeping units or dwelling units in
Group R-1,R-2 or R-3.4.Exit signs are not required in
dayrooms,sleeping rooms or dormitories in occupancies in
Group 1-3.5.In occupancies in Groups A-4 and A-5,exit signs
are not required on the seating side of vomitories or openings
into seating areas where exit signs are provided in the
concourse that are readily apparent from the vomitories.
Egress lighting is provided to identify each vomitory or
opening within the seating area in an emergency.
Fail 603.1.1-Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment, Location:Break room
wiring,devices and appliances shall be tested;and listed by Comments:Remove microwave and air fryer plugged to power strip,
an approved agency and labeled;and installed,used and appliances including heat producing elements or motors shall plug
maintained in accordance with NFPA 70 and all instructions directly to a permanent outlet.Also,power strips shall be properly
included as part of such listing. mounted to avoid hanging by wires.
GENERATED ON 8/13/28, 7:42 AM 3 OF 11
Fail 901.4.7.2-Marking on access doors.
Access doors for automatic sprinkler system riser rooms and Location:Rear of building-Exterior door near sprinkler riser
fire pump rooms shall be labeled with an approved sign,The Comments:Permanent approved signage shall be installed on
lettering shall be in contrasting color to the background. exterior side of door indicating"SPRINKLER RISER"or like wording.
Letters shall have a minimum height of 2 inches(51 mm)with Laminated paper will not be accepted.
a minimum stroke of 318 inch(10 mm).
Emergency Equipment
Code Description
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Backup emergency lighting
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Provide documentation of testing all egress lighting
including repairs completed of any deficiencies to maintain working
properly.Document shall state address,date and signature of
responsible person.Email document to inspector at
brad.baldwin@waterloo-ia.org
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:All exit signage
in Section 1013.6,3,The system shall be capable of powering Comments:Provide documentation of testing all exit signs including
the required load for a duration of not less than 90 minutes. repairs completed of any deficiencies to maintain working properly.
Document shall state address,date and signature of responsible
person.Email document to inspector at brad.baldwin@waterloo-
ia.org
Fire Sprinkler System
Status Code Description
Fail 5.2.1.1.5-Missing escutcheons
Ox Escutcheons and coverplates for recessed,flush,and Location:Back storage near drinking fountains
concealed sprinklers shall be replaced if found missing Comments:Sprinkler escutcheon shall be installed tight to ceiling.
during the inspection.
GENERATED ON 8/13/26, 7:42 AM 4 OF 11
Fire Service Features
``alto, Code Description
Fail 505.1-Address identification.
New and existing buildings shall be provided with approved Comments:Current address numbers very difficult to see from the
address identification.The address identification shall be street.Relocate address numbers compliant to code requirements or
legible and placed in a position that is visible from the street alter current numbers to make more visible.
or road fronting the property.Address identification
characters shall contrast with their background.Address
numbers shall be Arabic numbers or alphabetical letters.
Numbers shall not be spelled out.Each character shall be not
less than 4 inches(102 mm)high with a minimum stroke
width of 112 inch(12.7 mm).Where required by the fire code
official,address identification shall be provided in additional
approved locations to facilitate emergency response.Where
access is by means of a private road and the building cannot
be viewed from the public way,a monument,pole or other
sign or means shall be used to identify the structure.Address
identification shall be maintained.
Fail 507.5.5-Clear space around hydrants.
A 3-foot(914 min)clear space shall be maintained around the Location:Rear of building
circumference of fire hydrants,except as otherwise required Comments:Clear vegetation obstructing hydrants.
or approved.
Fail 509.2-Equipment access.
Ox Approved access shall be provided and maintained for all fire Location:Back storage area
protection system equipment to permit immediate safe Comments:Remove all storage within 3 feet of sprinkler riser
operation and maintenance of such equipment.Storage,trash equipment,maintain proper clearances at all times.Suggest marking
and other materials or objects shall not be placed or kept in floor where storage shall not be kept to avoid repeat violation.
such a manner that would prevent such equipment from
being readily accessible.
r
IFJ zh
,.` 0 Wee
i Fri , , ' - _
-,a
GENERATED ON 8/13/28, 7;42 AM 5 OF 11
Fail 509.2-Equipment access.
Approved access shall be provided and maintained for all fire Location:Near front exit
protection system equipment to permit immediate safe Comments:Relocate stand-up signage obstructing view of alarm pull
operation and maintenance of such equipment.Storage,trash station from all sides.
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
.w srt' bepd�
%th p •
„
•
IR -
fV
v
t a
3 f"
GENERATED ON 8/13/28, 7:42 AM 6 OF 11
Electrical Safety
Status Cone Description
Fall 603.2.2-Unapproved conditionsOpen electrical terminations.
0 Open junction boxes and open-wiring splices shall be Location:Middle storage room
prohibited.Approved covers shall be provided for all switch Comments:Provide knockout plug for opening in box.
and electrical outlet boxes.
, y
u
II 40
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
OOpen junction boxes and open-wiring splices shall be Location:Break room-near extinguisher
prohibited.Approved covers shall be provided for all switch Comments:Provide missing outlet cover
and electrical outlet boxes.
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
OOpen junction boxes and open-wiring splices shall be Location:Customer service
prohibited.Approved covers shall be provided for all switch Comments:Repair loose outlets cover inside cabinet.
and electrical outlet boxes.
i 1 '4'.
/ il
4-1 il I I .
v •
r
�, T
GENERATED ON 8/13/28, 7:42 AM 7 OF 11
Fail 603.4.1-Labeling.
Doors into electrical control panel rooms shall be marked Location:Cash room door
with a plainly visible and legible sign stating"ELECTRICAL Comments:Provide permanent approved signage on door indicating
ROOM"or similar approved wording.The disconnecting "ELECTRIC ROOM"or similar wording,laminated paper will not be
means for each service,feeder or branch circuit originating accepted.
on a switchboard or panelboard shall be legibly and durably
marked to indicate its purpose unless such purpose is clearly
evident.Where buildings or structures are supplied by more
than one power source,markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
Fail 603.4.1-Labeling.
Doors into electrical control panel rooms shall be marked Location:Middle storage room-near cash room
with a plainly visible and legible sign stating"ELECTRICAL Comments:Provide permanent approved signage on door indicating
ROOM"or similar approved wording.The disconnecting "ELECTRIC ROOM"or similar wording,laminated paper will not be
means for each service,feeder or branch circuit originating accepted.
on a switchboard or panelboard shall be legibly and durably
marked to indicate its purpose unless such purpose is clearly
evident.Where buildings or structures are supplied by more
than one power source,markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
Fail 603.5.3-Installation.
Relocatable power tap cords shall not extend through walls, Location:Managers office
ceilings,floors,under doors or floor coverings,or be subject Comments:Power strip below desk shall be properly mounted or
to environmental or physical damage.
supported to avoid hanging by wires.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Passport photos sign
for permanent wiring and shall be listed and labeled in Comments:Extension cord shall be removed,may be replaced with
accordance with UL 817.Extension cords and flexible properly supported power strip with manual reset for low wattage
cordsshall not be affixed to structures,extended through
electronics only.
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
a.
GENERATED ON 8/13/28, 7:42 AM 8 OF 11
Fire Resistant Construction Maintenance
Status Cod, Description
Fail 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:Back storage-Above drinking fountains
materials and systems used to protect joints and voids in the Comments:Replace missing ceiling tiles.
following locations shall be maintained.The materials and
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floorlceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Fail 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:Managers office
materials and systems used to protect joints and voids in the Comments:Replace missing ceiling tiles.
following locations shall be maintained.The materials and
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
GENERATED ON S/13/26, 7:42 Aft 9 OF 11
Portable Fire Extingusihers
code Description
Fail 906.6-Unobstructed and unobscured.
Portable fire extinguishers shall not be obstructed or Location:Back storage-near sprinkler riser
obscured from view.In rooms or areas in which visual Comments:Repair or replace extinguisher signage falling off wall.
obstruction cannot be completely avoided,means shall be
provided to indicate the locations of extinguishers.
\1
i ,
, �.
GENERATED ON 8/13/28, 7:42 AM 10 OF 11
.