COMMERCIAL FIRE INSPECTION - 1518 FLAMMANG DR-08/24/26 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
10914 08/31/2026 10/05/2026 2027-00000089 $100.00
Less Prepayment $0.00
Total Due —+ $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
d + Inspection Report 425 E.3rd Street
Barnes&Noble-1518 Flammang DR,BLDG 1518 Flammang Dr,Waterloo IA 50702
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
V {
0812412026 Annual Inspection(1Yr) U A 45 00.° 1054
Lead Inspector Shift Station Unit
BRAD BALDWIN N/A N/A NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
041 012 @23
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
09125/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-08126/2026 @ 06:55
•$110 annual inspection fee
BRAD BALDWIN-08/25/2026 @ 07:48
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#0)-Cell:319-230-1224
BRAD BALDWIN-08/25/2026 @ 07:49
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-08125/2026 @ 07:49
Annual fire alarm inspection and report to be uploaded to Compliance Engine due on 10/24126
BRAD BALDWIN-08127/2026 @ 11:03
•Request of specific time on scheduled inspection date or change of inspection date shall be made by business representative prior to scheduled
inspection date.Failure to request time or change of date will result in failed inspection.
SIGNATURES
Contact signature Inspector signature
No signature
Report completededpost ostinspection
Michelle Cable 2026 Date: BRAD BALDWIN 08/27/2026
CHECKLISTS
GENERATED ON 8/27/26, 11:05 AM 1 OF 8
Means of Egress
Status Cod, Description
Fail 1032.2-Reliability.
C} Required exit accesses,exits and exit discharges shall be Location:Back storage-"Receiving Room"
continuously maintained free from obstructions or Comments:Remove all storage&obstructions to clear path of
impediments to full instant use in the case of fire or other egress to exit hallway.Clear path of egress shall be maintained at all
emergency where the building area served by the means of
times.
egress is occupied.An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
14.
•
} L `
GENERATED ON 8/2T/26, 11:05 AM 2 OF 8
Additional Codes
Status Code Description
Fail 1010.2.4-Locks and latches.
Locks and latches shall be permitted to prevent operation of Location:Main exit doors
doors where any of the following exist:1.Places of detention Comments:Provide permanent signage on west door of double
or restraint.2.In Group I-i,Condition 2 and Group 1-2 doors indicating THIS DOOR SHALL REMAIN UNLOCKED DURING
occupancies where the clinical needs of persons receiving BUSINESS HOURS"or other approved wording on the interior side of
care require containment or where persons receiving care the door,
pose a security threat,provided that all clinical staff can
readily unlock doors at all times,and all such locks are keyed
to keys carried by all clinical staff at all times or all clinical
staff have the codes or other means necessary to operate the
locks at all times.2.3.In buildings in occupancy Group A
having an occupant load of 300 or less,Groups B,F,M and S,
and in places of religious worship,the main door or doors are
permitted to be equipped with key-operated locking devices
from the egress side provided:2.1.3.1.The locking device is
readily distinguishable as locked.2.2.3.2.A readily visible
durable sign is posted on the egress side on or adjacent to
the door stating:"THIS DOOR TO REMAIN UNLOCKED WHEN
THIS SPACE IS OCCUPIED."The sign shall be in letters 1 inch
(25 mm)high on a contrasting background.2.3.3.3.The use
of the key-operated locking device is revocable by the fire
code official for due cause.3.4.Where egress doors are used
in pairs,approved automatic flush bolts shall be permitted to
be used,provided that the door leaf having the automatic
flush bolts does not have a doorknob or surface-mounted
hardware.4.5.Doors from individual dwelling or sleeping
units of Group R occupancies having an occupant load of 10
or less are permitted to be equipped with a night latch,dead
bolt or security chain,provided such devices are openable
from the inside without the use of a key or tool.5.6.Fire
doors after the minimum elevated temperature has disabled
the unlatching mechanism in accordance with listed fire door
test procedures.6.7.Doors serving roofs not intended to be
occupied shall be permitted to be locked,preventing entry to
the building from the roof.8.Other than egress courts,where
occupants must egress from an exterior space through the
building for means of egress,exit access doors shall be
permitted to be equipped with an approved locking device
where installed and operated in accordance with all of the
following:8.1.The maximum occupant load shall be posted
where required by Section 1004.9.Such sign shall be
permanently affixed inside the building and shall be posted in
a conspicuous space near all the exit access doorways.8.2.A
weatherproof telephone or two-way communication system
installed in accordance with Sections 1009.8.1 and 1009.8.2
shall be located adjacent to not less than one required exit
access door on the exterior side.8.3.The egress door locking
device is readily distinguishable as locked and shall be a key-
operated locking device.8.4.A clear window or glazed door
opening,not less than 5 square feet(0.46 m2)in area,shall
be provided at each exit access door to determine if there are
occupants using the outdoor area.8.5.A readily visible
durable sign shall be posted on the interior side on or
adjacent to each locked required exit access door serving the
exterior area stating:"THIS DOOR TO REMAIN UNLOCKED
WHEN THE OUTDOOR AREA IS OCCUPIED."The letters on
the sign shall be not less than 1 inch(25.4 mm)high on a
contrasting background.8.6.The occupant load of the
occupied exterior area shall not exceed 300 occupants in
accordance with Section 1004.9,Locking devices are
permitted on doors to balconies,decks or other exterior
spaces serving individual dwelling or sleeping units.
10.Locking devices are permitted on doors to balconies,
decks or other exterior spaces of 250 square feet(23.23
m2)or less,serving a private office space,
GENERATED ON 8/27/26, 11:05 AM 3 OF 8
Fail 1011.12,2-Roof access.
Where a stairway is provided to a roof,access to the roof Location:Roof access ladder
shall be provided through a penthouse complying with Comments:Remove storage from obstructing clear path of access to
Section 1511.2 of the International Building Code.Exception: roof ladder.
In buildings without an occupied roof,access to the roof shall
be permitted to be a roof hatch or trap door not less than 16
square feet(1.5 m2)in area and having a minimum dimension
of 2 feet(610 mm).
Fail 102.4-Application of building code.
The design and construction of new structures shall comply Location:8 Rooftop units-HVAC permit
with the International Building Code,and any alterations, Comments:Contractor(Lennox National Acct Services)shall obtain
additions,changes in use or changes in structures required inspection of work completed,permit obtained in March of 2024 to
by this code,which are within the scope of the International replace 8 rooftop units.
Building Code,shall be made in accordance therewith.
General Housekeeping
siaa;s Code Description
Fail 315.3.2-Means of egress.
Ox Combustible materials shall not be stored in exits or Location:Back hallway exit
enclosures for stairways and ramps.Combustible materials in Comments:Remove all combustible material(ex:cardboard)from
the means of egress during construction,demolition, exit hallway.Maintain combustible storage clear of exits at all times.
remodeling or alterations shall comply with Section 3312.3.
Fire Sprinkler System
Description
Fail 903.3.3-Obstructed locations.
Automatic sprinklers shall be installed with regard to Location:Coffee shop
obstructions that will delay activation or obstruct the water Comments:Remove dustldebris from sprinkler heads above back
distribution pattern and shall be in accordance with the wall sinks.
applicable automatic sprinkler system standard that is being
used.Automatic sprinklers shall be installed in or under
covered kiosks,displays,booths,concession stands or
equipment that exceeds 4 feet(1219 mm)in width.Not less
than a 3-foot(914 mm)clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers.Exception:Kitchen equipment under exhaust hoods
protected with a fire-extinguishing system in accordance with
Section 904.
Fire Service Features
S:e os C ode Description
Fail 509.1-Identification.
Fire protection equipment shall be identified in an approved Location:Managers office
manner.Rooms containing controls for air-conditioning Comments:Permanent approved signage shall be installed on door
systems,sprinkler risers and valves,or other fire detection, indicating"FIRE ALARM CONTROL PANEL"or"FACP".Signage shall
suppression or control elements fire protection systems shall include white lettering with red background,laminated paper will not
be identified for the use of the fire department.Approved be accepted.
signs required to identify fire protection system equipment
and equipment location shall be constructed of durable
materials,permanently installed and readily visible.
GENERATED ON 8/27/28, 11:05 AM 4 OF 8
Electrical Safety
Status Code Description
Fail 603.4.1-Labeling.
Doors into electrical control panel rooms shall be marked Location:Main electric panel room
with a plainly visible and legible sign stating"ELECTRICAL Comments:Provide permanent approved signage on door indicating
ROOM"or similar approved wording.The disconnecting "ELECTRICAL ROOM"or other approved wording,laminated paper
means for each service,feeder or branch circuit originating will not be accepted.
on a switchboard or panelboard shall be legibly and durably
marked to indicate its purpose unless such purpose is clearly
evident.Where buildings or structures are supplied by more
than one power source,markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
Fail 603.6-Extension cords.
OExtension cords and flexible cordsshall not be a substitute Location:Coffee shop
for permanent wiring and shall be listed and labeled in Comments:Remove extension cord plugged to sandwich fridge.
accordance with UL 817.Extension cords and flexible Extension cords shall not be used as permanent wiring.Relocate
cordsshall not be affixed to structures,extended through appliance to plug directly to permanent outlet,or obtain licensed
walls,ceilings or floors,or under doors or floor coverings, electrical contractor to add new outlet with permit and inspection.
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fire Resistant Construction Maintenance
Status Code Description
Fail 705.2.4-Door operation.
Ux Swinging fire doors shall close from the full-open position Location:Receiving area-Electric Room
and latch automatically. Comments:Repair or replace fire rated door that failed to self shut
and latch.Also,remove storage outside of door obstructing the
ability for door to fully-open,
GENERATED ON 8/27/28, 11:05 AM 5 OF 8
Portable Fire Extingusihers
Scair.s Code Description,
Fail 906.2-General requirements.
Portable fire extinguishers shall be selected,Installed and Location:Sprinkler riser room
maintained in accordance with this section and NFPA 10. Comments:Provide required annual service to extinguisher,last
Exceptions:1.The distance of travel to reach an extinguisher tagged for service in 2023.
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1,Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2,4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
GENERATED ON 8/27/28, 11:05 AM 6 OF 8
Fall 906.6-Unobstructed and unobscured.
0 Portable fire extinguishers shall not be obstructed or Location:Near Legos area
obscured from view.In rooms or areas in which visual Comments:Provide signage(see attached)in approved location
obstruction cannot be completely avoided,means shall be indicating extinguisher location or relocate extinguisher to an
provided to indicate the locations of extinguishers. approved unobstructed location.Contact inspector for approved
locations.
FIRE
1
IT
I
N
C
U
I
S
H
E
R
GENERATED ON 8/27/28, 11:05 AM 7 OF 8
'o Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $110.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 8/27/26, 11:85 AM 8 OF 8