COMMERCIAL FIRE INSPECTION - 400 E TOWER PARK DR- FOR BILLING INQUIRY: (319)291-4323
08/31/26
Description Total Price
REINSPECTION 1 $100.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
12176 08/31/2026 10/05/2026 2027-00000099 $100.00
Less Prepayment $0.00
Total Due --> $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
4,* Waterloo Fire Rescue
t W Inspection Report 425 E.3rd Street
•""* Lowes-400 E tower park DR,BLDG 400 E Tower Park Dr,Waterloo IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
08/31/2026 Annual Inspection(1Yr) J REINSPECTION) + , 1 J(1�,p.'' 17421-R2
Lead Inspector Shift Station vv Unit
BRAD BALDWIN NIA N/A N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
00 03 013
Passed codes Resolved violations Failed codes
NEXT STEPS
Please direct questions about your Inspection to:
Reinspection Date
BRAD BALDWIN
brad.baldwin@waterloo-ia.org,3192914319
09/30/2026
GENERAL NOTES
BRAD BALDWIN-08/31/2026 @ 15:48
$100 re-inspection fee for failure to complete corrections on scheduled 8/31/26 inspection.Complete corrections to avoid fees at following inspections.
BRAD BALDWIN-08/03/2026 @ 08:24
•$610 annual inspection fee
BRAD BALDWIN-08103/2026 @ 08:24
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-08103/2026 @ 08:24
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-08/03/2026 @ 08:24
Withholding re-inspection fee on 7/31/26 due to progress made.Complete corrections to avoid fees at following inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completededpost stinspection
Scott June Date: BRAD BALDWIN 08131/2026
CHECKLISTS
GENERATED ON 8/31/2G, 3:49 PM
1 OF 6
Reinspection
Status Code Description
Fall 1010.1.3-Door opening force Forces to unlatch and open
doors. Location:Lawn&garden-Gate 495
The force for pushing or pulling open Interior swinging Comments:Lett exit door shall be repaired or replaced to allow door
egress doors,other than fire doors,shall not exceed 5 to open with less than 15lbs of force.Door failed to open easily today.
pounds(22 N).These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position.For other swinging doors,
as well as sliding and folding doors,the door latch shall
release when subjected to a 15-pound(67 N)force.The door
shall be set in motion when subjected to a 30-pound(133 N)
force.The door shall swing to a full-open position when
subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following:1.Where door
hardware operates by push or pull,the operational force to
unlatch the door shall not exceed 15 pounds(66.7 N).2.Where
door hardware operates by rotation,the operational force to
unlatch the door shall not exceed 28 inch-pounds(315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force
for pushing or pulling open the door shall not exceed 5
pounds(22 N).2.For other swinging doors,sliding doors or
folding doors,and doors required to be fire rated,the door
shall require not more than a 30-pound(133 N)force to be set
in motion and shall move to a full-open position when
subjected to not more than a 15-pound(67 N)force.
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:All of building
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Provide documentation of testing all emergency egress
lighting in the building including repairs made to maintain working
properly,documentation shall include address,signature and date of
responsible person.
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:All of building
in Section 1013.6.3.The system shall be capable of powering Comments:Provide documentation of testing all exit signs in the
the required load for a duration of not less than 90 minutes. building including repairs made to maintain working properly,
documentation shall include address,signature and date of
responsible person.
Fail 5.2.1-Annual sprinkler system inspection
Sprinklers shall be inspected at least annually by licensed Location:Sprinkler system
contractor Comments:Provide annual inspection and contractors report
including all deficiencies corrected to be uploaded to Compliance
Engine.Currently 48 days past due for inspection.
Additional comments:Deficiencies still remains on Compliance
Engine
®m
Fail 5.2.1.1.5-Missing escutcheons
Escutcheons and coverplates for recessed,flush,and Location:Break room
concealed sprinklers shall be replaced if found missing Comments:Replace missing escutcheon near exit door.
during the inspection.
Additional comments:No progress on 8131126
OF e
GENERATED ON 8/31/3e, 3:49 PP!
Fall 507.5.2 - Inspection, testing and maintenance.
0 Fire hydrant systems shall be subject to periodic tests as Location: Private fire hydrants
required by the fire code official. Fire hydrant systems shall Comments: Provide annual inspection and contractors report
be maintained in an operative condition at all times and shall including all deficiencies corrected to be uploaded to Compliance
be repaired where defective. Additions, repairs, alterations Engine. Currently 48 days past due for inspection.
and servicing shall comply with approved standards. Records
of tests and required maintenance shall be maintained. Additional comments: Deficiency still remains on Compliance Engine
.-..emu-
•LYOttYt�+w. ws
-MI
Fail 509.1 - Identification.
0 Fire protection equipment shall be identified in an approved Location: Aisle 53, bay 19 - near ladders
manner. Rooms containing controls for air-conditioning Comments: "HOSE CONNECTION" signage hidden up in ceiling
systems, sprinkler risers and valves, or other fire detection, trusses. Signage shall be in place indicating location of sprinkler
suppression or control elements fire protection systems shall hose connection at all times.
be identified for the use of the fire department. Approved
signs required to identify fire protection system equipment
and equipment location shall be constructed of durable
materials, permanently installed and readily visible.
Fail 509.1 - Identification.
Fire protection equipment shall be identified in an approved Location: Aisle 39, bay 17 - near tile tools
manner. Rooms containing controls for air-conditioning Comments: "HOSE CONNECTION" signage hidden up in ceiling
systems, sprinkler risers and valves, or other fire detection, trusses. Signage shall be in place indicating location of sprinkler
suppression or control elements fire protection systems shall hose connection at all times.
be identified for the use of the fire department. Approved
signs required to identify fire protection system equipment
and equipment location shall be constructed of durable
materials, permanently installed and readily visible.
Fail 509.1 - Identification.
OX Fire protection equipment shall be identified in an approved Location: Aisle 45, bay 20 - near vanitys
manner. Rooms containing controls for air-conditioning Comments: "HOSE CONNECTION" signage hidden u pin ceiling
systems, sprinkler risers and valves, or other fire detection, trusses. Signage shall be in place indicating location of sprinkler
suppression or control elements fire protection systems shall hose connection at all times.
be identified for the use of the fire department. Approved
signs required to identify fire protection system equipment
and equipment location shall be constructed of durable
materials, permanently installed and readily visible.
Fail 603.1 - General.
0 Electrical equipment, wiring and systems required by this Location: Break room
code or the International Building Code shall be installed, Comments: Remove toaster plugged to power strip. Appliances with
used and maintained in accordance with NFPA 70 and motors or heat producing elements shall plug directly to a permanent
Sections 603.2 through 603.10. outlet
Additional comments: New outlet installed requires licensed
electrical contractor to obtain permit and inspection.
GENERATED ON 8/31/20, 3:49 PM 3 OF 6
Fail 6107.3-Clearance to combustibles.
Weeds,grass,brush,trash and other combustible materials Location:South exterior of building
shall be kept not less than 10 feet(3048 mm)from LP-gas Comments:Remove all combustible material(pallets)within 10ft of
tanks or containers, propane cabinet.
i
1
�iii.r 1
r• i
UMW
f��� A
--
;,
• N
Fail 903.3.3-Obstructed locations.
Automatic sprinklers shall be installed with regard to Location:Seasonal area
obstructions that will delay activation or obstruct the water Comments:Gazebo shall be removed due to obstruction of sprinkler
distribution pattern and shall be in accordance with the head coverage or sprinkler head added below ceiling.
applicable automatic sprinkler system standard that is being
used.Automatic sprinklers shall be installed in or under
covered kiosks,displays,booths,concession stands or
equipment that exceeds 4 feet(1219 mm)in width.Not less
than a 3-foot(914 mm)clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers.Exception:Kitchen equipment under exhaust hoods
protected with a fire-extinguishing system in accordance with
Section 904.
' .
116-3
q8‘.* ii al ri
3 r
t' h1
-1 �. l r 1
Oil - _
4 OF 6
GENERATED ON 8/31/26, 2:46 PM
Fail Chapter 14-Inspection,testing,and maintenance
Fire alarm system tested at least annually by licensed Location:Fire alarm
contractor Comments:Provide annual inspection and contractors report
including all deficiencies corrected to be uploaded to Compliance
Engine.Currently due for inspection on 7115126,"battery trouble"
alarm noted during 6129126 inspection.
Additional comments:No report in Compliance Engine as of 8/31126
t
SO
•
GENERATED ON 8/31/26, 3:49 PM
5 OF 6