COMMERCIAL FIRE INSPECTION -200 E ARLINGTON ST-08/20/26 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
REINSPECTION 1 $100.00
CUSTOMER# BILLING DATE DUE DATE _ INVOICE# CHARGES
22864 08/31/2026 10/05/2026 2027-00000103 $100.00
Less Prepayment $0.00
Total Due— $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
�y'`"•"� Inspection Report
425 E.3rd Street
•-�y>� Roosevelt Senior Housing-200 E Arlington ST,BLDG 200 E Arlington St,Waterloo
IA 50703
INSPECTION DETAILS /1 J�(A(�01z/1'L
Inspection Date Inspection Type `�— '- Inspection Number
08/20/2026 Residential Common Areas Inspection (REINSPECTION) ICO,CC) 17440-R2
Lead Inspector Shift Station Unit
JEREMIAH VANDYKE NIA NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
0 0 0 3
Passed codes Failed codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
JEREMIAH VANDYKE
jeremiah.vandyke@waterloo-ia.org 09/19/2026
GENERAL NOTES
JEREMIAH VANDYKE-07/2012026 @ 09:24
Talked to Gene on the phone.Working on getting contractors and Bids in order to repair deficiencies.
JEREMIAH VANDYKE-07/2012026 @ 09:24
Fire extinguishers serviced Proshield 2026 Feb.
JEREMIAH VANDYKE-07/20/2026 @ 09:24
No clothes dryers in building.
JEREMIAH VANDYKE-07/20/2026 @ 09:24
PERMIT INFO:•Any construction,electrical,plumbing,life safety,and HVAC requires proper permit and inspections.•All electrical work and repair must
be completed by a licensed electrical contractor with permits and inspections.
JEREMIAH VANDYKE-07/20/2026 @ 09:24
Re-inspection dates are automatically generated 30 days out from the initial inspection.Normal operating hours for inspections&re-inspections are
Monday-Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on a weekend,the re-inspection will typically be performed
the following Monday or Tuesday.If all corrections are made before the 30 days,you can call to set up an earlier re-inspection.**"**Re inspection fees
may be assessed for subsequent re-inspections.Re-inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-07/20/2026 @ 09:24
Lt.Van Dyke-jeremiah.vandyke@waterloo-ia.org-Work:319-291-4460-Cell:319-883-1615
JEREMIAH VANDYKE-07/2012026 @ 09:24
Inspection Fee=$100.00(To be mailed out by City via snail mail.)
JEREMIAH VANDYKE-08/20/2026 @ 13:45
Re inspect fee to be mailed out by city:$100.00
SIGNATURES
GENERATED ON 8/20/26, 1:47 PM 1 OF 4
Contact signature Inspector signature
No signature LCY
Report completed post inspection
Gene Evens-District Manager Date: JEREMIAH VANDYKE 0812012026
CHECKLISTS
GENERATED ON 8/20/26, 1:47 PM 2 OF 4
Reinspection
Status Code Description
Fail 2015 IFC - Fire alarm testing and maintenance
OIs the fire alarm system powered, operational and displaying Location: Fire alarm needs serviced. Compliance engine shows an
normal operation (no troubles, supervisory, or alarms)? deficiency.
Comments: Deficiency Found: Answer: Fire Alarm is not being
monitored. Contact fire alarm contractor as soon as possible.
Fail 901.6 - Inspection, testing and maintenance.
CDFire detection and alarm systems, emergency alarm systems, Location: 5 Deficiencies on compliance engine for sprinkler system.
gas detection systems, fire-extinguishing systems, Contact sprinkler contractor to fix issues and update compliance
mechanical smoke exhaust systems and smoke and heat engine.
vents protection and life safety systems shall be maintained Comments: Deficiencies Reviewed (Check All: ) Deficiency Found:
in an operative condition at all times, and shall be replaced or Answer: Flow switch body cover is broken. Deficiency Found:
repaired where defective. Nonrequired fire protection and life Answer: 2" piping on city side of the backflow is corroded and
safety systems and equipment shall be inspected, tested and leaking. Deficiency Found: Answer: 2nd floor laundry room sprinkler
maintained or removed in accordance with Section 901.8 . head needs extended down further. Deficiency Found: Answer:
Several painted sprinkler heads need replaced. Deficiency Found:
Answer: Sprinkler heads more than 20 years old need sample tested
and/or replaced.
Fail 906.1 - Where required.
Portable fire extinguishers shall be installed in all of the Location: Elevator room.
following locations: l.ln new and existing Group A, B, E, F, H, Comments: Fire extinguisher needs serviced in elevator room. Send
I, M, R-1, R-2, R-4 and S occupancies. Exceptions: 1.ln Group picture.
R-2 occupancies, portable fire extinguishers shall be required
only in locations specified in Items 2 through 6 where each
dwelling unit is provided with a portable fire extinguisher
having a minimum rating of 1-A:10-B:C. 2.In Group E
occupancies, portable fire extinguishers shall be required
only in locations specified in Items 2 through 6 where each
classroom is provided with a portable fire extinguisher having
a minimum rating of 2-A:20-B:C. 3. In storage areas of Group
S occupancies where forklift, powered industrial truck or
powered cart operators are the primary occupants, fixed
extinguishers, as specified in NFPA 10, shall not be required
where in accordance with all of the following: 3.1. Use of
vehicle-mounted extinguishers shall be approved by the fire
code official. 3.2. Each vehicle shall be equipped with a 10-
pound, 40A:80B:C extinguisher affixed to the vehicle using a
mounting bracket approved by the extinguisher manufacturer
or the fire code official for vehicular use. 3.3. Not less than
two spare extinguishers of equal or greater rating shall be
available on-site to replace a discharged extinguisher. 3.4.
Vehicle operators shall be trained in the proper operation, use
and inspection of extinguishers. 3.5. Inspections of vehicle-
mounted extinguishers shall be performed daily. 2.Within 30
feet (9144 mm) distance of travel from commercial cooking
equipment and from domestic cooking equipment in Group I-
1; 1-2, Condition 1; and R-2 college dormitory occupancies.
3.In areas where flammable or combustible liquids are stored,
used or dispensed. 4.0n each floor of structures under
construction, except Group R-3 occupancies, in accordance
with Section 3316.1. 5.Where required by the sections
indicated in Table 906.1. 6.Special-hazard areas, including but
not limited to laboratories, computer rooms and generator
rooms, where required by the fire code official. Exception:
Portable fire extinguishers are not required at normally
unmanned Group U occupancy buildings or structures where
a portable fire extinguisher suitable to the hazard of the
location is provided on the vehicle of visiting personnel.