COMMERCIAL FIRE INSPECTION - 3821 UNIVERSITY AVE- FOR BILLING INQUIRY: (319)291-4323
08/24/26
Description Total Price
REINSPECTION 1 $100.00
CUSTOMER# BILLING DATE DUE DATE _ INVOICE# CHARGES
24657 08/31/2026 10/05/2026 2027-00000104 $100.00
Less Prepayment $0.00
Total Due—* $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
4,,., Waterloo Fire Rescue
Inspection Report 425 E.3rd Street
R Smokes Plus-3821 University AVE,BLDG 3821 University Ave,Waterloo IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type ( Inspection Number
08/24/2026 Annual Inspection(lYr) REINSPECTION &5 -7- \co. 22882-R3
Lead Inspector Shift Station
Unit
BRAD BALDWIN N/A N/A N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
' 0 1 8
Passed codes Resolved violations Failed codes
NEXT STEPS
Please direct questions about your Inspection to:
Reinspection Date
BRAD BALDWIN
brad.baldwin@waterloo-ia.org,3192914319
09/21/2026
GENERAL NOTES
BRAD BALDWIN-08124/2026 @ 11:24
$100 re-inspection fee for failure to complete corrections on scheduled 8/24/26 inspection.Complete corrections to avoid fees at following inspections.
Discussed remaining corrections with on-site staff today during 8/24/26 inspection.
BRAD BALDWIN-07/27/2026 @ 08:12
•$80 annual inspection fee
BRAD BALDWIN-07/27/2026 @ 08:12
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#5)-Cell:319-230-1224
BRAD BALDWIN-07/27/2026 @ 08:12
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-07127/2026 @ 08:12
Please note:Initial inspection(#22882)scheduled re-inspection date of 7115/26 will not be reset to 7/22/26 due to additional violations added per walk
through with City Electrical Inspector.
BRAD BALDWIN-07/27/2026 @ 08:12
Withholding re-inspection fee due to some progress on 7/22/26 inspection.Complete corrections to avoid fees at following inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completededpost stinspection
GENERATED ON 8/24/26, 11:25 AM
1 OF 6
Nabii•2026 Date: BRAD BALDWIN 0812412026
CHECKLISTS
2OF 6
GENERATED ON 8/24/28, 11:25 AM
Reinspection
Status Code Description
Fail 102.4-Application of building code.
The design and construction of new structures shall comply Location:Cigar room
with the International Building Code,and any alterations,
Comments:Building and electrical permits shall be obtained for additions,changes in use or changes in structures required
by this code,which are within the scope of the International "Cigar Room"constructed without permits.
Building Code,shall be made in accordance therewith. Additional comments:No permit in system on 8124/26
•
=r 1
Fail 603.1-General.
Electrical equipment,wiring and systems required by this Location:Electrical
code or the International Building Code shall be installed,
used and maintained in accordance with NFPA 70 and Comments:All electrical MC cable and wiring shall be installed in
Sections 603.2 through actor 603.10. electrical code compliance,multiple issues noted by City Electrical
Inspector during 6/24/26 walk-thru.Display case lighting shall be
listed and used per its listing,provide documentation of case lighting
to inspector.Licensed electrical contractor shall make all necessary
repairs,obtain invoice to provide to inspector.
Additional comments:No repairs made as of 8/24/26
GENERATED ON 8/24/28, 11:25 AM
3 OF 6
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:Cigar cutters display case
Identified electrical hazards shall be abated.Identified Comments:Licensed electrical contractor shall make corrections to
hazardous electrical conditions in permanent wiring shall be wiring unprotected entering box.Obtain invoice from electrician to
brought to the attention of the responsible code official. show inspector
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that Additional comments:No progress made 8124126
constitute an electrical shock or fire hazard shall be abated
not be used.
N
•�1
Fail 603.2-Abatement of unsafe conditions and electrical
Location:Behind register counter
hazards.
Identified electrical hazards shall be abated.Identified Comments:Power strip cord shall be properly protected across
hazardous electrical conditions in permanent wiring shall be walkway to avoid damage to cord hazard.
brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment Additional comments:No progress,cord has become damaged and
that is modified or damaged and constitutes Conditions that shall be replaced
constitute an electrical shock or fire hazard shall be abated
not be used.
ler
Ea
aoFs
GENERATED ON 8/24/28, 11:25 AM
Fail 603.4.1-Labeling,
0 Doors into electrical control panel rooms shall be marked Location:Mechanical room
with a plainly visible and legible sign stating"ELECTRICAL Comments:Ap
proved permanent"Electric room"signage shall
ROOM"or similar approved wording.The disconnecting installed on door,laminated paper will not be accepted.
means for each service,feeder or branch circuit originating
on a switchboard or panelboard shall be legibly and durably Additional comments:no progress
marked to indicate its purpose unless such purpose is clearly
evident.Where buildings or structures are supplied by more
than one power source,markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
Fail 603.5.3-Installation.
ORelocatable power tap cords shall not extend through walls, Location:Mechanical room storage
ceilings,floors,under doors or floor coverings,or be subject Comments:Power strip hanging over green storage tote shall be
to environmental or physical damage. mounted to avoid supported pported by wires.
Fail 603.6-Extension cords.
OExtension cords and flexible cordsshall not be a substitute Location:Cigar room
for permanent wiring and shall be listed and labeled in Comments:Extension cord shall be removed.Also,cords shall not
accordance with UL 817.Extension cords and flexible pass through doorways to avoid hazard of damaging cord.
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings, Additional comments:No progress made
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
•
\ am.
I
Fail 603.6-Extension cords.
Ox Extension cords and flexible cordsshall not be a substitute Location:TV above register counter
for permanent wiring and shall be listed and labeled in Comments:Remove TV plugged to extension cord,would approve to
accordance with UL 817.Extension cords and flexible replace with properly mounted power strip with manual reset for low
cordsshall not be affixed to structures,extended through wattage usage only.
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or Additional comments:No progress made
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.