COMMERCIAL FIRE INSPECTION - 1509 FLAMMANG DR-08/26/26 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 1 $40.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24069 08/31/2026 10/05/2026 2027-00000106 $50.00
Less Prepayment $0.00
Total Due —4 $50.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
1.0114. Inspection Report 425 E.3rd Street
Smoke O's Vapor•1509 Flammang DR,BLDG 1509 Flammang Dr,Waterloo IA 50702
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
08/26/2026 Annual Inspection(1Yr) , go tQci r 10525
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA N/A NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
0 31 0 11 ® 33
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 09/25/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-0812712026 @ 07:44
$50 annual inspection fee
BRAD BALDWIN-08127/2026 @ 07:44
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#0)-Cell:319-230-1224
BRAD BALDWIN-0812712026 @ 07:44
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature 1
Report completed post inspection
Maggie Lies staff 2026 Date: BRAD BALDWIN 08127/2026
CHECKLISTS
GENERATED ON 8/27/28, 7:48 AM 1 OF 9
Means of Egress
States Code Description
Fail 1010.1.3-Door opening force Forces to unlatch and open
doors. Location:Back exit door
The force for pushing or pulling open interior swinging Comments:Repair or replace exit door that failed to open with less
egress doors,other than fire doors,shall not exceed 5 than 15Ibs of force.Replacing door requires commercial building
pounds(22 N).These forces do not apply to the force permit and inspection.
required to retract latch bolts or disengage other devices that
hold the door in a closed position.For other swinging doors,
as well as sliding and folding doors,the door latch shall
release when subjected to a 15-pound(67 N)force.The door
shall be set in motion when subjected to a 30-pound(133 N)
force.The door shall swing to a full-open position when
subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following:1.Where door
hardware operates by push or pull,the operational force to
unlatch the door shall not exceed 15 pounds(66.7 N).2.Where
door hardware operates by rotation,the operational force to
unlatch the door shall not exceed 28 inch-pounds(315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force
for pushing or pulling open the door shall not exceed 5
pounds(22 N).2.For other swinging doors,sliding doors or
folding doors,and doors required to be fire rated,the door
shall require not more than a 30-pound(133 N)force to be set
in motion and shall move to a full-open position when
subjected to not more than a 15-pound(67 N)force.
Fail 1032.2-Reliability.
Required exit accesses,exits and exit discharges shall be Location:Back exit
continuously maintained free from obstructions or Comments:Relocate storage(Boxes below extinguisher)obstructing
impediments to full instant use in the case of fire or other
clear path to exit.Clear path of egress to exit shall be maintained at
emergency where the building area served by the means of all times.
egress is occupied.An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
:
.� If
r�
�� 11110$', a .'
4
M
t:.,,,itr41GENERATED ON 8/27/28, 7:48 AM 2 OF 9
Additional Codes
Status Code Description
Fail 102.3-Change of use or occupancy.
A change of occupancy shall not be made unless the use or Location:Security Camera room
occupancy is made to comply with the requirements of this Comments:Remove cot from building immediately.Sleeping is
code and the International Existing Building Code. strictly prohibited in commercial space.
Exception:Where approved by the fire code official,a change
of occupancy shall be permitted without complying with the
requirements of this code and the International Existing
Building Code,provided that the new or proposed use or
occupancy is less hazardous,based on life and fire risk,than
the existing use or occupancy.
U.,
4
w<.
GENERATED ON 8/27/28, 7:48 AM 3 OF 9
Emergency Equipment
St,at,is Code Description
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Back exit
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace emergency egress lights that failed to
illuminate during test and one light bulb hanging by wires.
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Back exit
in Section 1013.6.3.The system shall be capable of powering
Comments:Repair or replace exit sign that failed to illuminate during
the required load for a duration of not less than 90 minutes. test
GENERATED ON 8/27/28, 7:48 AM 4 OF g
Electrical Safety
S,mus Code Description
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
Open junction boxes and open-wiring splices shall be Location:Near Hemp Papers
prohibited.Approved covers shall be provided for all switch
Comments:Provide missing outlet cover
and electrical outlet boxes.
11
1BF�''.
o
Ma''R
•
GENERATED ON 8/27/28, 7:48 AM 5 OF 9
Fail 603.4-Working space and ciearancesclearance.
A working space of not Working space around electrical Location:Back stock area
equipment shall be provided in accordance with Section Comments:Remove storage within 36 inches of panel.Maintain
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or proper clearances and clear path of access at all times.
less,and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
provided in front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
a
r,
;:f I . i Ai
e'
t , _
fi
,, 1::-4,. 411—..--..—
GENERATED ON 8/27/28, 7:48 AM 6 OF 9
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Behind cigar cabinet.
for permanent wiring and shall be listed and labeled in Comments:Remove all extension cords behind cabinets.Extension
accordance with UL 817.Extension cords and flexible cords shall not be used as permanent wiring.
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
,
l
a .
:\
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Front wall corner behind display counter
for permanent wiring and shall be listed and labeled in Comments:Extension cord extending above drop ceiling shall be
accordance with UL 817.Extension cords and flexible removed.Extension cords shall not be used as permanent wiring and
cordsshall not be affixed to structures,extended through flexible supply cords shall not pass through concealed spaces.
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 6/27/26, 7:46 AM 7 OF 9
Fire Resistant Construction Maintenance
5[a:.is Code Description
Fail 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:Security camera room
materials and systems used to protect joints and voids in the Comments:Replace missing ceiling tiles.
following locations shall be maintained.The materials and
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floorlceiling assemblies and roof or
rooflceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Portable Fire Extingusihers
Sig ua COO Description
Fail 906.2-General requirements.
Portable fire extinguishers shall be selected,installed and Location:Extinguishers(2)
maintained in accordance with this section and NFPA 10. Comments:Provide required annual service to extinguishers,no
Exceptions:1.The distance of travel to reach an extinguisher
current contractor's tag or date reference to last service date.If
shall not apply to the spectator seating portions of Group A-5 purchasing own extinguishers,tape receipt to bottom to use as
occupancies.2.Thirty-day inspections shall not be required annual service date.
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
GENERATED ON 8/27/28, 7:48 AM 8 OF 9