HomeMy WebLinkAboutPROPOSAL 1P117) MECHANICAL
PROPOSAL BY
WBC MECHANICAL, INC.
1801 FALLS AVENUE
WATERLOO, IOWA 50701
(319) 233-6101 OR (800) 495-6461
FAX
SUBMITTED TO: CITY OF WATERLOO DATE: 8/13/08
ATTENTION: LOUIS CUTWRIGHT PHONE: 291-4319
ADDRESS : 715 MULBERRY ST. PROPOSAL# REH81308RAC
WATERLOO, IA 50703 LOCATION: WATERLOO
RECREATION & ARTS CENTER
EAST BOILER ROOM
SUBJECT OR JOB NAME: FLOOD BOILER & CIRCULATING
PUMPS REPLACEMENT
WE HEREBY SUBMIT SPECIFICATIONS AND ESTIMATES -
FURNISH ALL LABOR, MATERIAL, TRUCKS, TOOLS AND EQUIPMENT TO
Install :
OPTION #1 :
Two (2) Thermal Solutions EVA-1500 natural gas fired hot water
boilers, 88% efficiency rating, input of 1500 MBH each:
ASME construction - 160 psi
CSD-1 code accessories
Copper fin tube heat exchanger
ASME relief valve - 30 psi
Pressure and temperature gauge
Probe type low water cut-off with manual reset and test
switch
Operating control
High limit control with manual reset
Flow switch
Circulating pump
Steel skid base
Insulated metal jacket
1801 Falls Ave. • Waterloo, IA 50701 • (319) 233-6101 • Fax (319) 233-6102
NO. 2 of 7 PAGES
PROPOSAL# REH813C8RAC
Inspection openings
Inlet and exhaust connections
Sealed combustion chamber
Power type ceramic gas burner
Current: 120/60/1
Gas-electric ignition system •
Pilot magnetic valve, regulator and gas cock
Motor magnetic contactor
Honeywell RM7896 combustion control with display module
Pre and post purge
U.V. flame scanner
Prewired panel cabinet with control fuse, switch and
indicating light
Air pressure switch
Manual firing cock
Operating gas valve
Gas pressure regulator
Safety gas valve
Leakage test cocks
High gas pressure switch
Low gas pressure switch
Main gas shut-off cock
One (1) Tekmar 264 sequence and reset control panel with digital
display sensors and well .
One (1) Tjernlund VSAD variable speed induced draft system, sized
to provide adequate draft for both boilers through existing 10"
vent, complete as follows :
1 - VSAD 12-230 variable speed venter
1 - VFD-2H1A122C3 drive
1 - CPC-3 controller
1 - TD-2 pressure transducer
1 - RMK-12 roof mount kit
TOTAL $103,391.00
OPTION #2 :
Two (2) Raypak H3-1631 natural gas fired hot water boilers each
with a capacity of 1630 MBH input (1336. 6 MBH output) and each
complete with:
CSD-1 code accessories
Cast iron headers
Copper finned tube heat exchanger
ASME design (160 psi)
NO. 3 of 7 PAGES
PROPOSAL# REH81308RAC
ASME relief valve (60 psi)
Combination pressure and temperature gauge
Flow switch
Operating aquastat
High limit with manual reset
Top smoke outlet with draft inducer
Insulated metal jacket
Electronic ignition system
100% safety controls
On/off switch
Two-stage firing sequence
115/24V transformer
Operating gas valve
Gas pressure regulator
Safety gas valve
Leakage test cocks
Main gas shut-off cock
Circulating pump (mounted and wired)
One (1) Tekmar #264 boiler sequence and reset panel with digital
display sensors and well .
TOTAL COST $75,541 . 00
The following is inclusive in either option:
a) Recertify existing backflow preventer. NOTE: Backflow
preventers are now required to be installed and
recertified annually. The purpose is to prevent system
water backup into the municipal water system. Add a
air gap to the existing backflow preventer and a water
meter.
b) Remove existing boiler.
c) Use existing concrete housekeeping pad to place the new
Thermal Solutions boilers .
d) Re-size and pipe gas vent piping above the roof line.
e) Re-use existing expansion tank.
If Option #2 is chosen, the existing pad will need to be
increased in size for setting the Raypak boilers .
Boiler lead time is 8-10 weeks after acceptance of proposal .
NO. 4 of 7 PAGES
PROPOSAL# REH81308RAC
Replacement of both hot water base-mounted circulation pumps are
included for either option of this proposal .
Because of the late timeliness in which' the boilers will arrive
to be installed, the customer agrees to pay overtime charges, if
needed, to complete the installation of heat in the building.
Please initial
NO. 5 of 7 PAGES
PROPOSAL# REH81308RAC
* BID DOES NOT INCLUDE INSPECTION FEES . IF APPLICABLE, FEES
WILL BE ADDED.
* THIS PROPOSAL DOES NOT INCLUDE ANY REPAIRS FOR CONCEALED
DEFECTS THAT WERE NOT DETECTED AND ADDRESSED PRIOR TO
BEGINNING THE PROJECT. ANY EXTRA WORK WILL BE PERFORMED
ONLY AFTER AN ADDITIONAL COST IS AGREED TO BY THE OWNER
AND THE CONTRACTOR.
* NO ASBESTOS REMOVAL OR RE-INSULATING ARE INCLUDED.
* THE CONTRACTOR SHALL MAKE AN OPERATING TEST OF THE SYSTEM
AND RELATING EQUIPMENT.
* AT TIME SET BY CONTRACTOR AND AGREED TO BY THE OWNER, THE
CONTRACTOR SHALL ARRANGE TO PLACE THE PLANT IN OPERATION AND
TO MAKE NECESSARY ADJUSTMENT TO EQUIPMENT, TO PROVE
SATISFACTORY OPERATION PRIOR TO TURNING OVER TO THE OWNER.
* THE CONTRACTOR SHALL EXPLAIN THE OPERATION OF THE SYSTEM TO
THE OWNER OR THE OWNERS REPRESENTATIVE DURING THIS FINAL
TEST AND ADJUSTMENT PERIOD. THE FINAL TEST SHALL BE
PERFORMED AS SOON AS POSSIBLE AFTER THE WORK IS ENTIRELY
COMPLETED.
* ALL DEFECTS IN THE WORK OR WORKMANSHIP WHICH APPEAR DURING
THESE TESTS SHALL BE PROPERLY REMEDIED AND A TEST AGAIN
APPLIED AND CONTINUED TO A SATISFACTORY CONCLUSION.
* ALL ELECTRICITY OR FUEL NECESSARY FOR USE IN TESTING AND
ADJUSTING FOR THE OPERATION PERIOD WILL BE SUPPLIED BY THE
OWNER.
* RE-TUBING PROJECTS DO NOT INCLUDE CLEANING OF EXCESSIVE
LOOSE SCALE DEPOSITS . EXCESSIVE IS DEFINED AS MORE THAN ONE
2-1/2 GALLON PAIL.
• THE ABOVE ARE APPLIED IF APPLICABLE TO THE WORK PROPOSED.
PAGE NO. 6 of 7 PAGES
PROPOSAL# RH030305RAC
GUARANTEE:
THIS CONTRACTOR SHALL ASSUME RESPONSIBILITY FOR ANY DEFECTS WHICH
MAY DEVELOP IN ANY PART OF HIS WORK CAUSED BY FAULTY WORKMANSHIP
BY THE CONTRACTOR. REPLACEMENT OF PARTS AND EQUIPMENT THAT ARE
FAULTY WILL BE LIMITED TO THE WARRANTY PROVIDED BY THE EQUIPMENT
MANUFACTURER.
QUALITY ASSURANCE:
A) CONTRACTOR SHALL USE ONLY SKILLED WORKMEN WHO ARE
EXPERIENCED WITH MATERIALS AND METHODS ASSOCIATED WITH THE
TYPE OF WORK QUOTED.
B) ALL MATERIALS AND METHODS OF THIS PROJECT SHALL COMPLY WITH:
ASHRAE HANDBOOK
UNDERWRITERS
STATE OF IOWA CODES
CSD-1 CODE
ASME
NATIONAL BOARD
C) CONTRACTOR SHALL USE ALL MEANS NECESSARY TO PROTECT
MATERIALS BEFORE AND DURING INSTALLATION AND TO MAKE ALL
REPAIRS OR REPLACEMENTS IN THE EVENT OF DAMAGE.
PAGE NO. 7 of 7 PAGES
PROPOSAL# REH81308RAC
WE PROPOSE HEREBY TO FURNISH LABOR AND MATERIALS - COMPLETE IN
ACCORDANCE WITH ABOVE SPECIFICATIONS, FOR THE SUM OF CHOSEN
OPTION
PLUS TAX IF APPLICABLE
OPTION #1 ($103,391 . 00) OPTION #2 ($75,541 . 00)
Please initial the option of choice.
Please initial for over charges, if needed.
DOWN PAYMENT 10%
DELIVERY OF MATERIAL 40%
UPON COMPLETION 50%
BECAUSE OF THE VOLATILITY OF STEEL PRICES, IF ANY MATERIAL IS
SUBJECT TO A SURCHARGE BY THE SHIP DATE, THE SURCHARGE WILL BE
PASSED ON TO THE CUSTOMER AT COST.
TERMS : 10 DAYS NET
AUTHORIZED SIGNATURE A)4./4;
RICHARD HAR LEY
NOTE: THIS PROPOSAL MAY BE WITHDRAWN BY US IF NOT ACCEPTED
WITHIN 10 DAYS .
ALL MATERIAL IS GUARANTEED TO BE AS SPECIFIED. ALL WORK TO BE
COMPLETED IN A WORKMANLIKE MANNER ACCORDING TO STANDARD
PRACTICES . ANY ALTERATION OR DEVIATION FROM ABOVE SPECIFICATIONS
INVOLVING EXTRA COSTS WILL BE EXECUTED ONLY UPON WRITTEN ORDERS,
AND WILL BECOME AN EXTRA CHARGE OVER AND ABOVE THE ESTIMATE. ALL
AGREEMENTS CONTINGENT UPON STRIKES, ACCIDENTS OR DELAYS BEYOND
OUR CONTROL. OWNER TO CARRY FIRE, TORNADO AND OTHER NECESSARY
INSURANCE. OUR WORKERS ARE FULLY COVERED BY WORKMEN' S
COMPENSATION INSURANCE.
ACCEPTANCE OF PROPOSAL - THE ABOVE PRICES, SPECIFICATIONS AND
CONDITIONS ARE SATISFACTORY AND ARE HEREBY ACCEPTED. YOU ARE
AUTHORIZED TO DO THE WORK AS SPECIFIED. PAYMENT WILL BE MADE AS
OUTLINED ABOVE.
DATE OF ACCEPTANCE:
COMPANY:
BY:
PLEASE SIGN AND RETURN ONE COPY TO US IF THIS PROPOSAL IS
ACCEPTED.