TO: City of Waterloo DATE: August 31, 2005
Attn: Louis Cutwright, Building Official
Building Department PROJECT: Phase 2 Facility Improvements
715 Mulberry Street Five Sullivan Brothers Convention Center
Waterloo. IA 50703
We at Johnson Controls are pleased to quote you a net firm price of$360,925 to provide the following items and
revisions for Phase 2 of the Five Sullivan Brothers Convention Center Facility Improvements.
Project Summary Projected Cost Annual Energy Savings Payback
AHU Re-Control $111,998 $20,200 Anticipated/Stipulated 5.5 Years
AHU Repairs $ 93,010 $14,300 Anticipated/Stipulated 6.5 Years
AHU Motor VFD's $ 89,182 $16,400 Anticipated/Stipulated 5.4 Years
Penthouse Chiller Integration $ 7,300 $ 2,275 Anticipated/Stipulated 3.2 Years
Lighting System Controls $ 33,538 $10,500 Anticipated/Stipulated 3.2 Years
Zone Heating Devices $ 11,058 $ 575 Anticipated/Stipulated 19.2 Years
Primary Heating System Valves $ 14,839 $ 4,790 Anticipated/Stipulated 3.1 Years
Total Project $360,925 $69,040 Anticipated/Stipulated 5.2 Years
The specific scope of work is as defined in the attached 5 page Facility Improvement Measures documentation
dated June 20, 2005.
This proposal includes engineering/drawings, material, installation, software programming, project management,
commissioning and a one year warranty.
The associated benefits include:
1. Reduction in energy consumption.
2. Improved comfort levels.
3. Extension of equipment life.
4. Reduction in maintenance costs.
5. Reduction in emergency repairs.
6. Improved risk management.
JOHNSON PROPOSAL Johnson Controls,
Systems and Services Division
CONTR LS e Pa
g Cedar Rapids,IA 52402
Tel.319/395-7070
FAX: 319/393-3247
TO: City of Waterloo DATE: August 31, 2005
Attn: Louis Cutwright, Building Official
Building Department PROJECT: Phase 2 Facility Improvements
715 Mulberry Street Five Sullivan Brothers Convention Center
Waterloo. IA 50703
Exclusions of the project include:
1. No holiday or overtime hours.
2. The pricing above does not include repair or replacement of any system or components other than that specifically
listed.
3. If the donated chiller for the kitchen air handling unit is non or partially functional, we will make notice to the owner.
4. During the air and water balancing, if any existing system component is non or partially functional, we will make
notice to the owner.
5. The City of Waterloo will provide Ethernet drops and IP addresses as required.
Payment Terms:
1. Upon acceptance of this proposal, an invoice in the amount of 35 percent of the contract price will be issued for job
mobilization.
2. For each category listed in this proposal; when engineering is complete, the material is snipped and the installation
has begun you will receive an invoice for 45 percent of the contract price.
3. For each category listed in this proposal; when installation is substantially complete you will receive an invoice for
15 percent of the contract price.
4. For each category listed in this proposal; when the project is finished and functioning you will receive a final invoice
for 5 percent of the contract price.
(IMPORTANT: This proposal incorporates by reference the terms and conditions on the third page of this proposal hereof.)
This proposal is hereby accepted and This proposal is valid for the next
Johnson Controls is authorized to
proceed with the work; subject, however, 30 Days
to credit approval by Johnson Controls, Inc,
Milwaukee, Wisconsin.
THE CITY OF WATERLOO JOHNSON CONTROLS, INC.
P aser- ompany Name .
Signature Date L.. ignature Date
Name: /eon LJe,1p.e Y Name: Jim McDowell
Title: n1et yo 2 PRa Ie r- Title: Service Sales Solutions
TERMS AND CONDITIONS
By accepting this proposal,Purchaser agrees to be bound by the following terms and conditions:
1. SCOPE OF WORK. This proposal is based upon the use of straight time labor only. Plastering,patching and painting are excluded. "In-line"duct and piping
devices, including, but not limited to, valves, dampers, humidifiers,wells, taps, flow meters, orifices, etc., if required hereunder to be furnished by Johnson
Controls, Inc. (hereinafter referred to as JCI), shall be distributed and installed by others under JCI's supervision but at no additional cost to JCI. Purchaser
agrees to provide JCI with required field utilities(electricity,toilets,drinking water, project hoist,elevator service,etc.)without charge. JCI agrees to keep the
job site clean of debris arising out of its own operations. Purchaser shall not back charge JCI for any costs or expenses without JCI's written consent.
Unless specifically noted in the statement of the scope of work or services undertaken by JCI under this agreement, JCI's obligations under this agreement
expressly exclude any work or service of any nature associated or connected with the identification, abatement, clean up, control, removal, or disposal of
environment Hazards or dangerous substances,to include but not be limited to asbestos or PCSs,discovered in or on the premises. Any language or provision
of the agreement elsewhere contained which may authorize or empower the Purchaser to change,modify,or alter the scope of work or services to be performed
by JCI shall not operate to compel JCI to perform any work relating to Hazards without JCI's express written consent.
2. INVOICING & PAYMENTS. JCI may invoice Purchaser monthly for all materials delivered to the job site or to an off-site storage facility and for all work
performed on-site and off-site. Ten percent(10%)of the contract price is for engineering,drafting and other mobilization costs incurred prior to installation, This
10%shall be included in JCI's initial invoice. Purchaser agrees to pay JCI the amount invoiced upon receipt of the invoice. Waivers of lien will be furnished
upon request,as the work progresses,to the extent payments are received. If JCI's invoice is not paid within 30 days of its issuance,it is delinquent.
3. MATERIALS. If the materials or equipment included in this proposal become temporarily or permanently unavailable for reasons beyond the control and without
the fault of JCI,then in he case of such temporary unavailability,the time for performance of the work shall be extended to the extent thereof,and in the case of
permanent unavailability,JCI shall(a)be excused from furnishing said materials or equipment,and(b)be reimbursed for the difference between the cost of the
materials or equipment permanently unavailable and the cost of a reasonably available substitute therefor.
4. WARRANTY. JCI warrants that the equipment manufactured by it shall be free from defects in material and workmanship arising from normal usage for a
period of one(1)year from delivery of said equipment, or if installed by JCI, for a period of one(1)year from installation. JCI warrants that for equipment
furnished and/or installed but not manufactured by JCI,JCI will extend the same warranty terms and conditions which JCI receives from the manufacturer of said
equipment. For equipment installed by JCI, if Purchaser provides written notice to JCI of any such defect within thirty (30) days after the appearance or
discovery of such defect,JCI shall,at its option,repair or replace the defective equipment. For equipment not installed by JCI,if Purchaser returns the defective
equipment to JCI within thirty(30)days after appearance or discovery of such defect,JCI shall,at its option,repair or replace the defective equipment and return
said equipment to Purchaser. All transportation charges incurred in connection with the warranty for equipment not installed by JCI shall be borne by Purchaser.
These warranties do not extend to any equipment which has been repaired by others, abused, altered or misused, or which has not been properly and
reasonably maintained. THESE WARRANTIES ARE IN LIEU OF ALL OTHER WARRANTIES,EXPRESS OR IMPLIED,INCLUDING,BUT NOT LIMITED TO,
THOSE OF MERCHANTABILITY AND FITNESS FOR A SPECIFIC PURPOSE.
5. LIABILITY. JCI shall not be liable for any special,indirect or consequential damages arising in any manner from the equipment or material furnished or the
work performed pursuant to this agreement.
6. TAXES. The price of this proposal does not include duties,sales,use,excise,or other similar taxes,unless required by federal,state or local law. Purchaser
shall pay, in addition to the stated price, all taxes not legally required to be paid by JCI or, alternatively, shall provide JCI with acceptable tax exemption
certificates. JCI shall provide Purchaser with any tax payment certificate upon request and after completion and acceptance of the work.
7. DELAYS. JCI shall not be liable for any delay in the performance of the work resulting from or attributed to acts or circumstances beyond JCI's control,
including,but not limited to,acts of God,fire,riots,labor disputes,conditions of the premises,acts or omissions of the Purchaser,Owner or other Contractors or
delays caused by suppliers or subcontractors of JCI,etc.
8. COMPLIANCE WITH LAWS. JCI shall comply with all applicable federal, state and local laws and regulations and shall obtain all temporary licenses and
permits required for the prosecution of the work. Licenses and permits of a permanent nature shall be procured and paid for by the Purchaser.
9. DISPUTES. All disputes involving more than$15,000 shall be resolved by arbitration in accordance with the rules of the American Arbitration Association. The
prevailing party shall recover all legal costs and attomey's fees incurred as a result. Nothing here shall limit any rights under construction lien laws.
10. INSURANCE. Insurance coverage in excess of JCI's standard limits will be furnished when requested and required. No credit will be given or premium paid by
JCI for insurance afforded by others.
11, INDEMNITY. The Parties hereto agree to indemnify each other from any and all liabilities,claims,expenses, losses or damages, including attorneys'fees,
which may arise in connection with the execution of the work herein specified and which are caused,in whole or in part,by the negligent act or omission of the
Indemnifying Party.
12. OCCUPATIONAL SAFETY AND HEALTH. The Parties hereto agree to notify each other immediately upon becoming aware of an inspection under,or any
alleged violation of,the Occupational Safety and Health Act relating in any way to the project or project site.
13. ENTIRE AGREEMENT. This proposal,upon acceptance,shall constitute the entire agreement between the parties and supersedes any prior representations
or understandings.
14. CHANGES. No change or modification of any of the terms and conditions stated herein shall be binding upon JCI unless accepted by JCI in writing.
L HNSO V
N r � � � r "" �,,, J -� -;ram � �
,...-. Gonv�ntlo�Carshr V`✓NTR 7 L t
Five Sullivan Brothers Convention Center
Phase 2 Facility Improvements I ` ,
June 20, 2005
Facility Improvement Measures
Overview
Johnson Controls, Inc., in association with Justin Doyle of Gilmore & Doyle, has developed this
plan to address facility improvement measures at the Five Sullivan Brothers Convention Center.
In preparing this strategy, our facility development staff made multiple site visits interviewing
personnel as well as inspecting and collecting information on the controls and mechanical
equipment throughout the facility. The convention center has seen a decline in preventative
maintenance due to fiscal constraints. This has caused the utility cost to increase faster then
anticipated. The following performance improvement measures are recommended to begin
restoring the 30-year old Five Sullivan Brothers Convention Center back to original design
operation with several energy savings measures incorporated in the project.
The recommendations listed below will build upon the foundation for standardization throughout
the City of Waterloo and allow for a consistent team approach from sales, service, project
management, engineering, software development, commissioning, training and installation
standards utilizing Johnson Controls knowledge and resources. This project will further enhance
progress towards the City of Waterloo's vision for centralized facility management, energy
reporting, monitoring,trending and control to utilize information for more effective and efficient
management of buildings and resources to lower overall operating costs.
Air Handling Units (Penthouse, Kitchen And Boiler Room)
Project Summary Projected Cost Annual Energy Savings Payback
AHU Re-Control $111,998 $20,200 Anticipated/Stipulated 5.5 Years
AHU Repairs $ 93,010 $14,300 Anticipated/Stipulated 6.5 Years
Motor VFD's $ 89,182 $16,400 Anticipated/Stipulated 5.4 Years
Penthouse AHU Equipment
Primary Building System Air Handlers
Air Handler 1 - Hot Deck Multi Zone Unit with a 40 hp Supply and 20 hp Return Fan.
Air Handler 2 - Hot Deck Multi Zone Unit with a 40 hp Supply and 20 hp Return Fan.
Air Handler 3 - Hot Deck Multi Zone Unit with a 40 hp Supply and 20 hp Return Fan.
Air Handler 4 - Constant Volume Cooling only Unit with a 40 hp Supply and 20 hp Return
Fan.
Air Handler 5 - Constant Volume Cooling only Unit with a 75 hp Supply and 25 hp Return
Fan.
Confidential-Johnson Controls,Inc. 1
v*, JAHNSON
CONTRuLS
At this time the air handlers have DX9100 controls installed; this was to replace the Powers
System. In recent years the system has been overridden and many of the pneumatic dampers
and valves have been bypassed.
Penthouse AHU Equipment Continued:
Johnson Controls, Inc. Recommendations
Re-Control of the primary building system air handlers include:
• Replacement of the deteriorated hot water valves with new equipment on AHU 1, 2 & 3.
• Replacement of the aging supply and return motors with high efficiency equipment.
• Installation of Variable Speed Drives on the new supply and return fan motors.
• Replacement of all pneumatic transducers. The existing devices are failing due to oil and
water contamination.
• Replacement of all failed dampers and pneumatic actuators.
• Correct all operational software to ensure proper sequence of control.
Repairs to the primary building system air handlers include:
• Perform Vibration Analysis on all supply and return fans.
• Replacement of all required bearings, sheaves, pulleys and v-belts.
• Perform Laser Alignment to all repaired equipment.
• Air balance reporting of all supply and return fans.
• Water balance reporting of all heating and coiling coils.
Main Hall Relief Fan
Currently the Main Hall exhaust fan is not being used which is causing pressure relief problems
in the facility. This condition prevents the economizer operation from functioning correctly.
Johnson Controls,Inc. Recommendations
• Replacement of the aging motor with high efficiency equipment.
• Installation of a Variable Speed Drive on the new fan motor.
• Correct all operational software to ensure proper sequence of control.
• Perform Vibration Analysis on the fan.
• Air balance reporting of the fan.
Pneumatic Controls and Digital Control Interfacing
Currently the pneumatic air system is contaminated with oil and water. This condition
deteriorates the pneumatic devices causing premature failure. The existing air compressor also
runs excessively, which is indicative of leaks in the air lines.
Confidential-Johnson Controls,Inc. 2
' 4 4444: J HNSON
CONTR LS
Johnson Controls, Inc. Recommendations
• Installation of a new air compressor, dryer and pressure reducing station in the penthouse.
• Repair or replace pneumatic air lines in the penthouse as needed.
• Clean and purge pneumatic air lines in the penthouse to remove contaminates.
Kitchen AHU Equipment
Air Handler 6 serving the kitchen area is a Hot Deck Multi Zone Unit utilizing 100% outdoor air
with a 20 hp supply fan. This unit provides the heating, cooling and makeup air to kitchen and
exhaust hoods. The unit was not in operation during our visits. The mechanical cooling for this
unit is from a donated chiller that has not been commissioned.
Johnson Controls, Inc. Recommendations
Re-Control of the kitchen air handler includes:
• Installation of METASYS Direct Digital Controls to ensure proper sequence of operation.
• Incorporate control of the chiller to provide mechanical cooling.
• Replacement of the deteriorated hot water valve with new equipment.
• Replacement of the aging supply fan motor with high efficiency equipment.
• Installation of a Variable Speed Drive on the new supply fan motor.
Repairs to the kitchen air handler include:
• Performing Vibration Analysis on the supply fan.
• Replacement of all required bearings, sheaves, pulleys and v-belts.
• Perform Laser Alignment to all repaired equipment.
• Air balance reporting of the unit.
• Water balance reporting of the heating and coiling coils.
Boiler Room AHU Equipment
The AHU serving the boiler room provides makeup air for the boilers utilizing 100% outdoor air
and a heating coil to temper the air. The unit was not in operation during our visits.
Johnson Controls, Inc. Recommendations
Re-Control of the boiler room air handler includes:
• Installation of METASYS Direct Digital Controls to ensure proper sequence of operation.
• Replacement of the deteriorated hot water valve with new equipment.
Repairs to the boiler room air handler include:
• Performing Vibration Analysis on the supply fan.
• Replacement of all required bearings, sheaves, pulleys and v-belts.
• Perform Laser Alignment to all repaired equipment.
• Air balance reporting of the unit.
• Water balance reporting of the heating coil.
Confidential-Johnson Controls,Inc. 3
s ,041111
7
JOHNSON
CvnwntionGrnbrz "�'`' t VNTi \
uiS
Facility Commissioning
• Johnson Controls, Inc will provide facility commissioning and programming of the
digital controls for complete integration of Phase One and Phase 2.
Penthouse Chiller Integration
Projected Cost Annual Energy Savings Payback
$7,300 $2,275 Anticipated/Stipulated 3.2 Years
Currently the 260 ton chiller is operated by manually turning the chilled water pumps on and off
with interlocking of the chiller on/off command and the use of an outdoor air remote bulb
controller to lockout the chiller on low temperature conditions.
Johnson Controls, Inc. Recommendations
• Installation of a METASYS Chiller Integrator to ensure proper sequence of operation.
• Provide system control of the chiller and associated chilled water pumps.
• Water balance reporting of the chiller pumps
Lighting System Controls
Projected Cost Annual Energy Savings Payback
$33,538 $10,500 Anticipated/Stipulated 3.2 Years
Currently the Sullivan Center Main Hall lighting control is done manually with breakers and 2
staff members. This original design has exceeded its life expectancy. There are approximately 84
breakers controlling the Main Hall lighting system. Outdoor lighting is being performed
manually on the main entrance level.
Johnson Controls,Inc. Recommendations
Installation of a Triatek lighting panel system with (84) low voltage lighting relays to control the
Main Hall fixtures. This lighting system is METASYS compatible; network controlled and can
be operated by the METASYS System for energy savings and long term reliability. The outdoor
lighting control will have up to (8) zoned areas and will be installed as part of this project.
Zone Heating Devices
Projected Cost Annual Energy Savings Payback
$11,058 $575 Anticipated/Stipulated 19.2 Years
Currently there are eleven additional units of heating equipment that are pneumatically
controlled and not interfaced to the METASYS System. Similar devices in the facility are failing
due to oil and water contamination in the Pneumatic System.
Confidential-Johnson Controls,Inc. 4
.el.i '- 4
�s ,
(t., ,,,,, ,,
,. - - ,,---,--,.-,,,7 7 ' - - Lc-„, ; ..,„
',- .; 4.. A .- ,:pse,,..i^,-," „-- ,--,„.„ „.„Ata,scsi - ,,,„ , J2FINSON
Johnson Controls, Inc. Recommendations
Replacement of the pneumatic devices with direct digital control on (5)terminal units and (6)
convectors on the first and second floors. Connection to the METASYS System will allow
complete control and energy management of all the zone units.
Primary Heating System Valves
Projected Cost Annual Energy Savings Payback
$14,839 $4,790 Anticipated/Stipulated 3.1 Years
Currently there are (4) 3-way valves for control of heating loop temperatures that are not
functioning. These valves are required to reset the hot water temperature need to heat the
following systems:
• Main Air Handlers
• Booster Coils
• Fan Coils, Heaters & Univents
• Makeup Air Handler
Johnson Controls, Inc. Recommendations
• Replacement of the deteriorated and nonfunctioning 3-way valve with new equipment.