HomeMy WebLinkAboutFAREWAY-40 W SAN MARNAN DR OF WA fF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
S. ..e 09/17/2026 10/22/2026 2027-00000124 $100.00
ti
/I�• ,MI O
• •it 1 111 III 11• I •
> *--= T O
4s 7vilN
Customer#: 6854 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
FAREWAY 715 Mulberry St
40 W SAN MARNAN DR WATERLOO, IA 50703
WATERLOO, IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION-40 W. SAN MARNAN DR- FOR BILLING INQUIRY: (319)291-4323
09/11/26
Description Total Price
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
6854 09/17/2026 10/22/2026 2027-00000124 $100.00
Less Prepayment $0.00
Total Due -* $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report 425 E.3rd Street
Fareway Store S951-40 W San Marnan DR,BLDG 40 W San Manias Dr,Waterloo IA
50701
INSPECTION DETAILS
Inspection Date Inspection Type inspection Number
0911112026 Annual Inspection(1Yr) 4 T 16551
Lead Inspector Shift Station Unit
BRAD BALDWIN N/A NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
043 7 ® 25
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 1010212026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-0 9111/2 0 2 6 @ 14:27
•$100 annual inspection fee
BRAD BALDWIN-09111/2026 @ 14:28
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#0)-Cell:319-230-1224
BRAD BALDWIN-0911112026 @ 14:28
•Provide corrections to avoid progressive re-inspection fees beginning at$100.BeerlLiquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-0911112026 @ 14:28
•If all corrections are made before the scheduled re-inspection date,you can call to setup an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.Ir.1'.Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection tees start at$100,then$150,and S200 for all subsequent re-inspections.
BRAD BALDWIN-0911112026 @ 14:29
Annual fire sprinkler inspection due 1011126.Contractor's report shall be uploaded to Compliance Engine including deficiencies corrected.
BRAD BALDWIN-0911112026 @ 14:31
Extinguishers due annually serviced in June 2027
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
John Pentecost 2026 Date: BRAD BALDWIN 09/11/2026
GENERATED ON 0/11/20, 2:42 PH _of 3
CHECKLISTS
Emergency Equipment
Status Code Description
Fail 1203.2.15•Means of egress Illumination.
Emergency power shall be provided for means of egress Location:Tunnel
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress light above"system 13"that
failed to illuminate during test.
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Tunnel
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress light above"system 3"that
failed to illuminate during test.
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Entire building
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Provide documentation of testing all emergency egress
lighting in the building including repairs completed to maintain
working properly.Email document to inspector signed and dated.
Fail 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Entire building
in Section 1013.6.3.The system shall be capable of powering
Comments:Provide documentation of testing all exit signage in the
the required load for a duration of not less than 90 minutes. building including repairs completed to maintain working properly.
Email document to inspector signed and dated.
General Housekeeping
Sta•us Code Description
Fail 315.3.2-Means of egress.
Combustible materials shall not be stored in exits or Location:Main exit vestibule
enclosures for stairways and ramps.Combustible materials in
Comments:Remove stack of pallets from exit enclosure.
the means of egress during construction,demolition,
remodeling or alterations shall comply with Section 3312.3.
Fire Sprinkler System
Status Code Description
Fail 5.2.1.1.5•Missing escutcheons
Escutcheons and coverplates for recessed,flush,and Location:Above register 7
concealed sprinklers shall he replaced if found missing Comments:Replace missing sprinkler head escutcheon.
during the inspection.
Fire Service Features
Status Code Description
Fail 509.2-Equipment access.
Approved access shall be provided and maintained for all fire Location:Sprinkler riser
protection system equipment to permit immediate safe Comments:Remove storage within 36 inches of sprinkler equipment,
operation and maintenance of such equipment.Storage,trash equipment shall be maintained with ready access for fire fighters at
and other materials or objects shall not be placed or kept in all times.
such a manner that would prevent such equipment from
being readily accessible.
GENERATED ON 9/11/26, 2:42 PM 2 OF 3
•
to Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
N/A $100.00
Invoice Number Check Number Transaction Number
N/A NIA N/A
3 OF 3
GENERATED ON 9/11/2G, 2:42 PM