COMMERCIAL FIRE INSPECTION- 1505 LOGAN AVE-09/09/26 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 50,000 $225.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24575 09/17/2026 10/22/2026 2027-00000125 $235.00
Less Prepayment $0.00
Total Due—> $235.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
425 E.3rd Street
George Washington Carver Academy-1505 Logan AVE,BLDG 1505 Logan Ave,
Waterloo IA 50703
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
09/09/2026 Biennial Inspection(2yrs) c,241/45 1,J 15433
Lead Inspector Shift Station Unit
JEREMIAH VANDYKE N/A NIA NIA
Other Inspectors
BRAD BALDWIN
SUMMARY OF INSPECTION
G56 012 ® 7
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
JEREMIAH VANDYKE
10/09/2026
jeremiah.vandyke@waterloo-ia.org
GENERAL NOTES
JEREMIAH VANDYKE-09/0912026 @ 10:54
Fire drill 9/1/2026.
JEREMIAH VANDYKE-09/09/2026 @ 10:55
Fire extinguishers July 2026 Proshield.
JEREMIAH VANDYKE-09/09/2026 @ 11:04
All life safety systems are currently compliant per Compliance Engine.
JEREMIAH VANDYKE-0910912026 @ 11:09
Clothes dryers cleaned 3/1/2026 by Harris.
JEREMIAH VANDYKE-09/09/2026 @ 11:22
Re-inspection dates are automatically generated 30 days out from the initial inspection.Normal operating hours for inspections&re-inspections are
Monday-Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on a weekend,the re-inspection will typically be performed
the following Monday or Tuesday.If all corrections are made before the 30 days,you can call to set up an earlier re-inspection.""'Re inspection fees
may be assessed for subsequent re-inspections.Re-inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-09/0912026 @ 11:22
Lt.J.D.Van Dyke-jeremiah.vandyke@waterloo-ia.org-Work:319-291-4460-Cell:319-883-1615
JEREMIAH VANDYKE-09/0912026 @ 11:22
Inspection Fee=$235.00(To be mailed out by City via snail mail.)
SIGNATURES
Contact signature Inspector signature
GENERATED ON 9/9/26, 11:23 AM 1 OF 5
No signature
Report completed post inspection
\/
Zach Kelly-Maintenance Director Date:
CHECKLISTS
Means of Egress JEREMIAH VANDYKE 0 910 912 0 2 6
Code Description
Fail 1010.1.3-Door opening force Forces to unlatch and open
doors. Location:Room 140 exit door hard to open.
The force for pushing or pulling open interior swinging Comments:Room 140 exit door hard to open.
egress doors,other than fire doors,shall not exceed 5
pounds(22 N).These forces do not apply to the force
required to retract latch bolts or disengage other devices that
hold the door in a closed position.For other swinging doors,
as well as sliding and folding doors,the door latch shall
release when subjected to a 15-pound(67 N)force.The door
shall be set in motion when subjected to a 30-pound(133 N)
force.The door shall swing to a full-open position when
subjected to a 15-pound(67 N)force.The forces to unlatch
doors shall comply with the following:1.Where door
hardware operates by push or pull,the operational force to
unlatch the door shall not exceed 15 pounds(66.7 N).2.Where
door hardware operates by rotation,the operational force to
unlatch the door shall not exceed 28 inch-pounds(315 N-cm).
The force to open doors shall comply with the following:
1.For interior swinging egress doors that are manually
operated,other than doors required to be fire rated,the force
for pushing or pulling open the door shall not exceed 5
pounds(22 N).2.For other swinging doors,sliding doors or
folding doors,and doors required to be fire rated,the door
shall require not more than a 30-pound(133 N)force to be set
in motion and shall move to a full-open position when
subjected to not more than a 15-pound(67 N)force.
Fail 1032.2-Reliability.
Required exit accesses,exits and exit discharges shall be Location:Ramp leading to stage needs chairs cleared.
continuously maintained free from obstructions or Comments:Ramp leading to stage needs chairs cleared.
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied.An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Emergency Equipment
Status Coils Description
Fail 1203.4.3-Records.
ORecords of the inspection,testing and maintenance of Location:Need records of all egress and exit light testing records.
emergency and standby power systems shall include the date Send records to my email
of service,name of the servicing technician,a summary of Comments:Need records of all egress and exit light testing records.
conditions noted and a detailed description of any conditions Send records to my email
requiring correction and what corrective action was taken.
Such records shall be maintained.
GENERATED ON 9/9/26, 11:23 AN 2 OF 5
General Housekeeping
Status Code Description
Fail 315.3.3-Equipment rooms.
OCombustible material shall not be stored in boiler rooms, Location:Room 151
mechanical rooms,electrical equipment rooms or in fire Comments:Need all storage cleared from room due to size of
command centers as specified in Section 508.1.5. electrical panel.
Electrical Safety
Code Description
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Room 167.
equipment shall be provided in accordance with Section Comments:Storage blocking electrical panel.
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less,and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
Fail 603.5-Relocatable power taps and current taps.Multiplug
adapters. Location:Room 161 has fridge plugged into powerstrip.
Multiplug adapters,such as cube adapters,unfused plug Comments:Room 161 has fridge plugged into powerstrip.
strips or any other device not complying with NFPA 70 shall
be prohibited.The construction and use of current taps and
relocatable taps shall be in accordance with NFPA 70 and this
code.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Room 109 has extension cord in use.
for permanent wiring and shall be listed and labeled in Comments:Room 109 has extension cord in use.
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Stage area red extension cord into power strip.
for permanent wiring and shall be listed and labeled in Comments:Stage area red extension cord into power strip.
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.9.4-Prohibited areas.
Portable,electric space heaters shall not be operated within 3 Location:Room 107 Extension cord plugged into space heater.
feet(914 mm)of any combustible materials.Portable,electric Comments:Room 107 Extension cord plugged into space heater.
space heaters shall be operated only in locations for which
they are listed.
GENERATED ON 9/9/26, 11:23 AM 3 OF 5
Fire Resistant Construction Maintenance
Status Code Description
Fail 705.2.4 - Door operation.
Swinging fire doors shall close from the full-open position Location: Double doors 8th grade hallway near room 205 not closing.
and latch automatically. Sticking on floor. Send video.
Comments: Double doors 8th grade hallway near room 205 not
closing. Sticking on floor. Send video.
Fail 705.2.6 -Testing.
OHorizontal and vertical sliding and rolling fire doors shall be Location: Kitchen roll down fire doors need inspection.
inspected and tested annually to confirm proper operation
Comments: Kitchen roll down fire doors need inspection.
and full closure. Records of inspections and testing shall be
maintained.
Additional Codes
S t,dus ::ode Description
Fail 807.3 - Acceptance criteria and reports.
Where required to exhibit improved fire performance, Location: Current Stage curtain reports needed.
curtains, draperies, fabric hangings and other similar Comments: Last stage report on our ESO file was completed 2020 by
combustible decorative materials suspended from walls or harris cleaning.
ceilings shall be tested by an approved agency and meet the
flame propagation performance criteria of Test Method 1 or
Test Method 2, as appropriate, of NFPA 701 or exhibit a
maximum rate of heat release of 100 kW when tested in
accordance with NFPA 289, using the 20 kW ignition source.
Reports of test results shall be prepared in accordance with
the test method used and furnished to the fire code official
upon request.
GENERATED ON 9/9/26, 11:23 AM 4 OF 5