COMMERCIAL FIRE INSPECTION- 1730 W RIDGEWAY AVE- FOR BILLING INQUIRY: (319)291-4323
09/16/26
Description Total Price
REINSPECTION 1 $100.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23829 09/17/2026 10/22/2026 2027-00000127 $100.00
Less Prepayment $0.00
Total Due—> $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report 425 E.3rd Street
Greenhouse Kitchen-1730 W Ridgeway AVE,BLDG 1730 W Ridgeway Ave-STE
500,Waterloo IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type n� Inspection Number
0911612026 Annual Inspection(1Yr) i REINSPECTION) 53S j, 7865-R2
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
0 0 6
Passed codes Failed codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 10/1612026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-09/16/2026 @ 13:58
$100 re-inspection fee due to lack of progress or completion of corrections on 9/16/26.Complete corrections to avoid fees at following inspections.
BRAD BALDWIN-08/18/2026 @ 12:01
•680 annual inspection fee
BRAD BALDWIN-08118/2026 @ 12:01
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(45)-Cell:319-230-1224
BRAD BALDWIN-08118/2026 @ 12:01
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m..".Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-0811812026 @ 12:01
Manager on-site stated the restaurant does not create grease,therefor no grease containment is needed.Creating grease in the future will require
purchasing and using a listed grease container with self-closing lid.
BRAD BALDWIN-0811812026 @ 12:01
Withholding re-inspection fee on 8/18/26 due to progress,complete corrections to avoid fees at following inspections.
SIGNATURES
Contact signature Inspector signature
No signature
inspection
Report completed post
Riley Luppen Date: BRAD BALDWIN 09116/2026
GENERATED ON 9/16/20, 2:03 PM t OF 0
CHECKLISTS
GENERATED ON 9/16/2G, 2:03 PM 2 OF 4
Reinspection
Status Code nescripfion
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Above door to bathroom hallway
Illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress lights on exit sign that failed to
illuminate during test.
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Dining area
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress lights(2)on exit sign that failed
to illuminate during test.
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Men's bathroom
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress lights on exit sign that failed to
illuminate during test.Was not able to access woinen's bathroom
during 7114126 inspection,lights shall be tested and repaired if not
functioning properly
Additional comments:Women's restroom egress-OK.Men's
bathroom egress light still tailed on 9116126.
Fail 1203.2.15-Means of egress illumination.
Emergency power shall be provided for means of egress Location:Bathroom hallway
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress lights on exit sign that failed to
illuminate during test.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not he a substitute Location:Menu TVs
for permanent wiring and shall be listed and labeled in Comments:Extension cord shall be removed from plugged to TVs.
accordance with UL 817.Extension cords and flexible Would approve the use of a properly mounted power strip with
cordsshall not be affixed to structures,extended through manual reset for low wattage electronics only.
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 906.2-General requirements.
Portable fire extinguishers shall be selected,installed and Location:Extinguishers
maintained in accordance with this section and NFPA 10. Comments:Provide annual service to all extinguishers,currently
Exceptions:1.The distance of travel to reach an extinguisher past due for service since Oct 2025.
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3,1n Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.