COMMERCIAL FIRE INSPECTION - 201 SUN-SET RD-09/08/26 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 50, 000 $225. 00
OCCUPANCY FEE $10. 00
CUSTOMER # BILLING DATE DUE DATE INVOICE # CHARGES
3599 09/17/2026 10/22/2026 2027-00000130 $235 .00
Less Prepayment $0.00
Total Due -- S235.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
� Inspection Report 425 E.3rd Street
0114;: i Kingsley Elementary School-201 Sunset RD,BLDG 201 Sunset Rd,Waterloo IA
50702
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
09/0812026 Biennial Inspection(2yrs) e' 4C6— 15076
Lead Inspector Shift Station Unit
JEREMIAH VANDYKE NIA NIA NIA
Other Inspectors
BRAD BALDWIN,BROCK WELIVER
SUMMARY OF INSPECTION
0 61 0 6 0 7
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
JEREMIAH VANDYKE
1010&2026
jeremiah.vandyke@waterloo-ia.org
GENERAL NOTES
JEREMIAH VANDYKE-0910812026 @ 16:14
Fire drill 9-1-2026
JEREMIAH VANDYKE-0910812026 @ 16:14
Fire extinguishers Proshield July 2026
JEREMIAH VANDYKE-0910812026 @ 16:24
All life safety systems in compliance engine are compliant.
JEREMIAH VANDYKE-0910812026 @ 16:34
Re-inspection dates are automatically generated 30 days out from the initial inspection.Normal operating hours for inspections&re-inspections are
Monday-Friday,8:00 a.m.-5:00 p.m.If the automatically generated re-inspection date lands on a weekend,the re-inspection will typically be performed
the following Monday or Tuesday.If all corrections are made before the 30 days,you can call to set up an earlier re-inspection....file inspection fees
may be assessed for subsequent re-inspections.Re-inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.-
JEREMIAH VANDYKE-0910812026 @ 16:34
Lt.J.D.Van Dyke-jeremiah.vandyke@waterloo-ia.org-Work:319-291-4460-Cell:319-883-1615
JEREMIAH VANDYKE-0910812026 @ 16:39
Inspection Fee=$235.00(To be mailed out by City via snail mail.)
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GENERATED ON a/8/26, 4:40 PR 1 OF 4
Zach Kelly-Maintenance Date: /In
CHECKLISTS
Means of Egress
Si,itus code Descriptio
Fail 1032.2-Reliability.
Required exit accesses,exits and exit discharges shall be Location:All Floors in hallways.
continuously maintained free from obstructions or Comments:Desk need to be removed from hallways.Discussed
impediments to full instant use in the case of fire or other getting archirtect involved to check measurements to see if small
emergency where the building area served by the means of desk could be allowed.
egress is occupied.An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Fail 1032.2-Reliability.
Required exit accesses,exits and exit discharges shall be Location:Near room 308 in hallway.
continuously maintained free from obstructions or Comments:Large desk needs to be removed from hallway.
impediments to full instant use in the case of fire or other
emergency where the building area served by the means of
egress is occupied.An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Emergency Equipment
code Description
Fail 1203.4.3-Records.
Records of the inspection,testing and maintenance of Location:Need records of all egress and exit light testing records.
emergency and standby power systems shall include the date Send records to my email.
of service,name of the servicing technician,a summary of Comments:Need records of all egress and exit light testing records.
conditions noted and a detailed description of any conditions Send records to my email.
requiring correction and what corrective action was taken.
Such records shall be maintained.
Electrical Safety
=iatu, Cock Description
Fail 603.2-Abatement of unsafe conditions and electrical
hazards. Location:Outside by door#2 near fire escape.
Identified electrical hazards shall be abated.Identified Comments:Need cover replaced over outlet.Send picture after
hazardous electrical conditions in permanent wiring shall be corrected.
brought to the attention of the responsible code official.
Electrical wiring,devices,appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
GENERATED ON 9/R/2G, 4:40 PM 2 OF 4
Fire Resistant Construction Maintenance
Status Code Description
Fail 705.2 - Inspection and maintenance.
V Opening protectives in fire-resistance-rated assemblies shall Location: Entire building for marked fire doors need smoke seals.
be inspected and maintained in accordance with NFPA 80. Comments: Marked fire doors need smoke seals installed.
Opening protectives in smoke barriers shall be inspected and
maintained in accordance with NFPA 80 and NFPA 105.
Openings in smoke partitions shall be inspected and
maintained in accordance with NFPA 105. Fire doors and
smoke and draft control doors shall not be blocked,
obstructed, or otherwise made inoperable. Fusible links shall
be replaced promptly whenever fused or damaged. Opening
protectives and smoke and draft control doors shall not be
modified.
Fail 705.2.4 - Door operation.
Swinging fire doors shall close from the full-open position Location: 2nd floor elevator door does not swing or latch. Need to
and latch automatically. adjust and send video.
Comments: 2nd floor elevator door does not swing or latch. Need to
adjust and send video.