COMMERCIAL FIRE INSPECTION-351 FLETCHER AVE-09/15/26 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
23344 09/17/2026 10/22/2026 2027-00000135 $80.00
Less Prepayment $0.00
Total Due—+ $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report 425 E.3rd Street
"`"• Massage Studio-351 Fletcher AVE, BLDG 351 Fletcher Ave,Waterloo IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
0911512026 Annual Inspection(1Yr) ✓ 3848
Lead Inspector Shift Station Unit
BRAD BALDWIN NIA N/A NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
0 30 0 17 @ 38
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
10/1612026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-09/17/2026 @ 12:35
•$80 annual inspection fee
BRAD BALDWIN-09/17/2026 @ 12:36
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#0)-Cell:319-230-1224
BRAD BALDWIN-09117/2026 @ 12:36
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Suchen-2026 Date: BRAD BALDWIN 09/17/2026
CHECKLISTS
GENERATED ON 9/17/28, 12:40 PM 1 OF 11
Means of Egress
Status Code Desonoon
Fail 1032.2-Reliability.
Required exit accesses,exits and exit discharges shall be Location:Basement-West exit
continuously maintained free from obstructions or Comments:Remove board from base of exit door,maintain
impediments to full instant use in the case of fire or other unobstructed egress path through exit at all times.
emergency where the building area served by the means of
egress is occupied.An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
, EIT ,,r�,
rI
iti
4
/ A., -
_, _
_ ,
f.4 E `.:cY r
GENERATED ON 9/17/26, 12:48 PM 2 OF 11
Fail 1032.2-Reliability.
Required exit accesses,exits and exit discharges shall be Location:Basement•North exit
continuously maintained free from obstructions or Comments:Required exit doors shall be maintained free from
impediments to full instant use in the case of fire or other obstructed at all times.Current occupancy does not require this
emergency where the building area served by the means of second exit,options are as follows:(1)Remove cable lock from door
egress is occupied.An exit or exit passageway shall not be and maintain exit free of obstructions(2)Remove exit sign above
used for any purpose that interferes with a means of egress. basement door leading to this exit including capping electrical wires
of exit sign and containing in box with cover,other exit sign in
basement to remain.Cable lock remaining on door will require
approved permanent signage installed on exterior of door indicating
"THIS DOOR BLOCKED"
iI 0101 11112 I ill I II
GENERATED ON 9/17/26, 12:40 PM s of i.
Additional Codes
Status Code Description
Fail 102.3-Change of use or occupancy.
A change of occupancy shall not be made unless the use or Location:Basement
occupancy is made to comply with the requirements of this Comments:Remove bed from building immediately,sleeping not an
code and the International Existing Building Code. approved use in commercial space.
Exception:Where approved by the fire code official,a change
of occupancy shall be permitted without complying with the
requirements of this code and the International Existing
Building Code,provided that the new or proposed use or
occupancy is less hazardous,based on life and fire risk,than
the existing use or occupancy.
Oti
Fail 102.4-Application of building code.
The design and construction of new structures shall comply Location:Air Conditioner
with the International Building Code,and any alterations, Comments:Contractor(Bergen Plumbing,Heating&Cooling)shall
additions,changes in use or changes in structures required obtain inspection of AIC installed.Record of Bergen obtaining permit
by this code,which are within the scope of the International but failed to obtain inspection.
Building Code,shall be made in accordance therewith.
GENERATED ON 9/17/26, 12:46 PM 4 OF 11
Fail 1032.6-Finishes,furnishings and decorations.
Means of egress doors shall be maintained in such a manner Location:Basement
as to be distinguishable from the adjacent construction and Comments:Remove curtain from exit door,required exit doors may
finishes such that the doors are easily recognizable as doors. not be disguised.
Furnishings,decorations or other objects shall not be placed
so as to obstruct exits,access thereto,egress therefrom,or
visibility thereof.Hangings and draperies shall not be placed
over exit doors or otherwise be located to conceal or obstruct
an exit.Mirrors shall not be placed on exit doors.Mirrors
shall not be placed in or adjacent to any exit in such a manner
as to confuse the direction of egress.
............ ...
.I
am «ALI
101 .
l
wi
Fail 308.1.7.1-Aisles and exits.
Candles shall be prohibited in areas where occupants stand, Location:Large massage room
or in an aisle or exit. Comments:Candle shall be re-located away from wall and away from
walk path to avoid potential of tip-over.
t
i
5 OF 11
GENERATED ON G/17/20, 12:40 PM
Fail 310.1-General.
The smoking or carrying of a lighted pipe,cigar,cigarette or Location:North end stairs to basement
any other type of smoking paraphernalia or material is Comments:Smoking is strictly prohibited inside the building.Staff
prohibited in the areas indicated in Sections 310.2 through on-site during 9115126 inspection admitted to smoking in stairwell on
310.8. continuous basis.Also noted,walls show obvious sign of smoking
and jar of used cigarettes found.
Fail 603.1-General.
Electrical equipment,wiring and systems required by this Location:Small massage room
code or the International Building Code shall be installed, Comments:Remove microwave
used and maintained in accordance with NFPA 70 and plugged rssh to power strip.Appliances
Sections 603.2 through 603.10.
including heating elements or motors shall plug directly to a
permanent outlet.
Fail 603.1-General.
Electrical equipment,wiring and systems required by this Location:Small massage room
code or the International Building Code shall be installed,
used and maintained in accordance with NFPA 70 and Comments:Heat pad shall be removed from plugged to power strip.
Sections 603.2 through actor 603.10. Appliances including heating elements or motors shall plug directly
to a permanent outlet.
,x
GENERATED ON 0/17/26, 12:40 PM
6 OF 11
Fail 807.3-Acceptance criteria and reports.
(";-'r Where required to exhibit improved fire performance, Location:Entire building
curtains,draperies,fabric hangings and other similar Comments:Provide documentation of all curtains and draperies
combustible decorative materials suspended from walls or throughout building have been tested and meet required Flame
ceilings shall be tested by an approved agency and meet the Spread criteria.Curtains and draperies that do not meet required
flame propagation performance criteria of Test Method 1 or criteria shall be removed.
Test Method 2,as appropriate,of NFPA 701 or exhibit a
maximum rate of heat release of 100 kW when tested in
accordance with NFPA 289,using the 20 kW ignition source.
Reports of test results shall be prepared in accordance with
the test method used and furnished to the fire code official
upon request.
4'
„
Fail 907.10-Smoke alarm maintenance.
Smoke alarms shall be tested and maintained in accordance Location:Large massage room
with the manufacturer's instructions.Smoke alarms shall be Comments:Replace smoke detector more than 10 years old
replaced when they fail to respond to operability tests,or
when they exceed 10 years from the date of manufacture,
unless an earlier replacement is specified in the
manufacturer's published instructions.
7 OF 11
GENERATE6 ON 5i/17/26, 12:40 PM
Electrical Safety
Stat.i_. Code Description
Fail 603.4-Working space and clearancesclearance.
A working space of not Working space around electrical Location:Basement-mechanical room
equipment shall be provided in accordance with Section Comments:Relocated laundry appliance obstructing clear path of
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or access to electric panel.Maintain clear,unobstructed path to utilities
less,and Section 110.33 of NFPA 70 for electrical equipment at all times.
rated over 1,000 volts.The minimum required working space
shall be not less than 30 inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm).
; iI lfbf •
, ....16 : to? Iii.
ili .. ,.:, A ,
., , _ _17 , j .
--.1...fiad".*. 'V... I-'I/ 1 fi'l',.
0 . •
' .
Fail 603.4.1-Labeling.
Doors into electrical control panel rooms shall be marked Location:Basement-Mechanical Room
with a plainly visible and legible sign stating"ELECTRICAL
Comments:Provide permanent signage on door indicating ROOM"or similar approved wording.The disconnecting
"ELECTRICAL PANEL INSDE"or other approved wording.Laminated
means for each service,feeder or branch circuit originating
on a switchboard or panelboard shall be legibly and durably paper will not be accepted.
marked to indicate its purpose unless such purpose is clearly
evident.Where buildings or structures are supplied by more
than one power source,markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
GENERATED ON 9/17/26, 12:40 PM
8 OF 11
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Couch near front desk
for permanent wiring and shall be listed and labeled in Comments:Remove mini fridge plugged to extension cord.Appliance
accordance with UL 817.Extension cords and flexible shall plug directly to outlet.
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Stairs from main exit
for permanent wiring and shall be listed and labeled in Comments:Remove extension cord.
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
4"
i
a
•
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Stairs from main exit
for permanent wiring and shall be listed and labeled in Comments:Remove power strip next to stairs plugged to extension
accordance with UL 817.Extension cords and flexible cord,power strip shall plug directly to a wall outlet.Currently power
cordsshall not be affixed to structures,extended through strip is also hanging by wires.
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 0/17/28, 12:40 PM 9 OF 11
Portable Fire Extingusihers
Stat.n; Cod, Description
Fail 906.2-General requirements.
Portable fire extinguishers shall be selected,Installed and Comments:Annually serviced 2A-10BC fire extinguisher shall be
maintained in accordance with this section and NFPA 10. properly located in upper and lower level of massage business.Last
Exceptions:1.The distance of travel to reach an extinguisher recorded service in April 2025.
shall not apply to the spectator seating portions of Group A-5
occupancies.2.Thirty-day inspections shall not be required
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.
GENERATED ON 9/17/26, 12:40 PM 10 OF 11