COMMERCIAL FIRE INSPECTION-425 E RIDGEWAY AVE- FOR BILLING INQUIRY: (319)291-4323
09/08/26
Description Total Price
INSPECTION 100,000 $600.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
3597 09/17/2026 10/22/2026 2027-00000143 $610.00
Less Prepayment $0.00
Total Due—> $610.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
•,•�s Inspection Report
425 E.3rd Street
,.a 3, West High School-425 E Ridgeway AVE,BLDG 425 E Ridgeway Ave,Waterloo IA
50702
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
09/08/2026 Biennial Inspection(2yrs) ' 7— 43(e/0 15445
Lead Inspector Shift Station
Unit
BRAD BALDWIN NIA NIA N/A
Other Inspectors
JEREMIAH VANDYKE,BROCK WELIVER
SUMMARY OF INSPECTION
0 61 U 15 ® 5
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to:
Reinspection Date
BRAD BALDWIN
brad.baldwin@waterloo-ia.org,3192914319
10/09/2026
GENERAL NOTES
BRAD BALDWIN-09108/2026 @ 14:41
•$610 annual inspection fee
BRAD BALDWIN-09/08/2026 @ 14:41
•Commercial Fire Inspector—brad.baldwin@waterloo-ia.org—Work:319-291-4319(#0)-Cell:319-230-1224
BRAD BALDWIN-0910812026 @ 14:41
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday—Friday,9:00 a.m.—4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-09/08/2026 @ 14:42
Kitchen hood suppression inspection and report to be uploaded to Compliance Engine with deficiencies corrected due 9/18/26
BRAD BALDWIN-09108/2026 @ 15:15
Clothes dryer vent cleanings completed on 3/18126 by Harris Cleaning.
BRAD BALDWIN-09/09/2026 @ 07:39
Christmas and like lighting noted in multiple spaces throughout building approved for temporary lighting(90 days).Lighting shall be removed after 90
days of usage has expired.
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Zach Kelly-Maintenance Director Date: BRAD BALDWIN 09/10/2026
GENERATED ON 9/10/26, 8:30 AM
1 OF 6
CHECKLISTS
Means of Egress
Status Code Description
Fail 1032.2-Reliability.
ORequired exit accesses,exits and exit discharges shall be Location:Rooms 0201 to 0203
continuously maintained free from obstructions or Comments:Remove obstruction(storage)not allowing door to fully
impediments to full instant use in the case of lire or other open.Also,remove filing cabinet in exit path,maintain clear path of
emergency where the building area served by the means of exit at all times.
egress is occupied.An exit or exit passageway shall not be
used for any purpose that interferes with a means of egress.
Additional Codes
Status Code Description
Fail 313.1-General.
OFueled equipment including,but not limited to,motorcycles, Location:Room 0200
mopeds,lawn-care equipment,portable generators and Comments:Remove gas powered mower from building.
portable cooking equipment,shall not be stored,operated or
repaired within a building.Exceptions:(Buildings or rooms
constructed for such use in accordance with the International
Building Code.2.Where allowed by Section 314.3.Storage of
equipment utilized for maintenance purposes is allowed in
approved locations where the aggregate fuel capacity of the
stored equipment does not exceed 10 gallons(38 L)and the
building is equipped throughout with an automatic sprinkler
system installed in accordance with Section 903.3.1.1.
Fail 603.1-General.
Electrical equipment,wiring and systems required by this Location:Room 4130
code or the International Building Code shall be installed, Comments:Remove microwave and fridge plugged to multi-plug
used and maintained in accordance with NFPA 70 and adapter.Appliances including heat producing elements and motors
Sections 603.2 through 603.10. shall plug directly to a permanent outlet.
Fail 807.1-General.
The following requirements shall apply to all occupancies: Location:Stage curtains
(Furnishings or decorative materials of an explosive or Comments:Provide documentation of fire retardant treatment applied
highly flammable character shall not be used.2.Fire-retardant to curtains.Last recorded treatment in 2020.Email document to
coatings in existing buildings shall be maintained so as to inspector.
retain the effectiveness of the treatment under service
conditions encountered in actual use.3.Furnishings or other
objects shall not be placed to obstruct exits,access thereto,
egress therefrom or visibility thereof.4.The permissible
amount of noncombustible decorative materials shall not be
limited.
Emergency Equipment
Status Code Description
Fail 1203.2.6-Exit signs.
OEmergency power shall be provided for exit signs as required Location:Athletic meeting room
in Section 1013.6.3.The system shall be capable of powering Comments:Repair or replace exit sign currently hanging by wires.
the required load for a duration of not less than 90 minutes.
Fail 1203.4.3-Records.
Records of the inspection,testing and maintenance of Location:Entire building
emergency and standby power systems shall include the date Comments:Provide documentation of testing all exit signs and
of service,name of the servicing technician,a summary of emergency egress lighting including repairs completed if needed.
conditions noted and a detailed description of any conditions Email to inspector.
requiring correction and what corrective action was taken.
Such records shall be maintained.
OF 6
GENERATED vu s/le/Os, 6:30 Ni
Documentation
Status Code Description
Fail 403.4.1 - First emergency evacuation drill.
OThe first emergency evacuation drill of each school year shall Location: Fire drill
be conducted within 10 days of the beginning of classes. Comments: Provide documentation of date of first Fire Drill, email to
inspector.
Fire Service Features
Status Code Description
Fail 506.2 - Key box maintenance.
O The operator of the building shall immediately notify the fire Location: Room #342B
code official and provide the new key where a lock is changed Comments: Contact Waterloo Fire Department at 319-291-4460 to
or rekeyed. The key to such lock shall be secured in the key provide copy of key in Knox Box.
box.
Electrical Safety
Status Code Description
Fail 603.2 -Abatement of unsafe conditions and electrical
0 hazards. Location: Basement - Wrestling Room
Identified electrical hazards shall be abated. Identified Comments: Outlet and conduit not anchored to wall shall be repaired.
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official.
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
Fail 603.5.2 -Application and usePower supply.
ORelocatable power taps and current taps shall be directly Location: Christine Erie's desk
connected to a permanently installed receptacle. Exceptions: Comments: Remove power strips daisychained (plugged
p (p gged from one to
1. Where approved for use in a Group A occupancy or in a another). Each power strip shall plug directly to a permanent outlet.
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
Fail 603.5.2 -Application and usePower supply.
0 Relocatable power taps and current taps shall be directly Location: Joanie Spencer's desk
connected to a permanently installed receptacle. Exceptions:
Comments: Remove power strips daisy chained (plugged from one to
1. Where approved for use in a Group A occupancy or in a another). Each power strip shall plug directly to a permanent outlet.
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
GENERATED ON 9/10/26, 8:30 AM 3 OF 6
Fire Resistant Construction Maintenance
5 d;u_, Sc k Description
Fail 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:Athletic foyer
materials and systems used to protect joints and voids in the Comments:Replace missing ceiling tile.
following locations shall be maintained.The materials and
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floor/ceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Fail 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:Room#205
materials and systems used to protect joints and voids in the Comments:Replace missing ceiling tile
following locations shall be maintained.The materials and
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floor/ceiling assemblies and roof or
rooflceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
GENERATED ON 9/18/26, 8:30 AM 4 OF 6
Fad 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:Room#300
materials and systems used to protect joints and voids in the Comments:Replace missing ceiling tile
following locations shall be maintained.The materials and
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floorlceiling assemblies and roof or
rooflceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.S.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Fail 705.2.4-Door operation.
xl Swinging fire doors shall close from the full-open position Location:Tunnel-door by hallway stairs
and latch automatically. Comments:Repair or replace fire rated door that fails to self shut and
latch.Also,remove device holding door open.