HomeMy WebLinkAboutscan-17RL
RL
RS
RS
CONDENSING UNIT
�-- EX ROOF ►+
RAILS
NOTES:
1. INSULATE REFRIGERANT SUCTION & GAS LINES
W/3/4" ARMAFLEX PIPE INSULATION. USE RIGID
ARMAFLEX AT ALL PIPE HANGER LOCATIONS.
2. REFRIGERANT LINES SHALL BE SIZED BY THE
EQUIPMENT MANUFACTURER.
3. ON SMALL SIZED DX SYSTEM, EQUIPMENT. SHOWN
ON LIQUID LINE MAY BE FURNISHED WITH UNIT.
MECHANICAL CONTRACTOR TO VERIFY.
---EX ROOF OPENING
- FILTER DRYER (TYR)
--LIQUID LINE SIGHT GLASS &
MOIST. INDICATOR (TYP.)
---SOLENOID VALVE WIRED
BY MECHANICAL (TYP.)
-OIL TRAP CONSIST.
OF STREET ELBOW
(TYP.)
DUAL -CIRCUIT -CONDENSING UNIT HIGH DETAIL
3- No Scale - -
-THERMAL EXPANSION VALVE
W/REMOTE SENSING BULB
- -- AIR FLOW
CONDENSATE DRAIN PAN
- CD -I
---CONDENSATE DRAIN LINE
TO FLOOR DRAIN
EX MAIN SWITCHGEAR
2500A, 480V/277V, 30, 4VV
-^ 90A-3P
0/3 Anus 3 nE T
� 20A-3P �1 r
�3 Anu o r.v iv
25A-3P 25/3 ACCU-3A
25A-3P
�ACC
25/37
EX
2500A-3P
ELECTRICAL RISER DIAGRAM
5 %o Scam
NOTE:
REFER TO SPECIFICATIONS FOR 360
DEGREE INSERT INFORMATION.
SPECIFIED
INSULATION
•
CORNERS
ARE CLIPPED
PIPE HANGER
(SEE SPECS)
PIPE SADDLE WITH FLARED
- EDGES NOTCHED TO FIT PIPE
HANGER, TO SPAN 180°
�J
FLARED _/ SPECIFIED
EDGES LENGTH = 12" INSULATION
ALL INSULATION
360 DEGREE SHALL PASS UNBROKEN --
INSERT (SEE SPEC) - THROUGH HANGER
2 INSULATED PIPE HANGER DETAIL
No Scale
GENERAL NOTES:
A. MAINTAIN ALL SERVICE CLEAti=NCE_ REQUIRED BY THE UTILITY.
B. UTILITY CONTACT: MID AMEF-rAN
C. INSTALL ALL CONDUCTORS = MA'.--ACTURER'S RECOMMENDATIONS,
CONDUCTOR AND
CONDUIT SIZING CHART
CONDUCTORS(T-,IN-_
CONDUIT
PARALLEL
PHASE NEUTR-_
:;ROUND
EMT
RMC
RUNS
20/3
;3) #12 AWG -
=:? AWG
1/2"
3/4"
1
25/3
(3)#10 AWG
_3 AWG
1/2"
3/4"
1
90/3
(3) #3 AWG
AWG
1-1/4"
1-1/4"
1
AHU-3 MODULES
O1.
AIR MIXING SECTION
O2.
ACCESS SECTION
30.
ELECTRIC HEAT SECTION
O4.
COOLING COIL SECTION
O5.
ACCESS SECTION
O6.
SUPPLY FAN SECTION
BEAD OF 3M FIRI
BARRIER CP 25N/S CAULI
RIER
'STRIP
2" MAX. GLASS FIBER
PIPE INSULATION
"•TE,
F-t ADDITIONAL FIRE PROOFING
"ETHODS AND MATERIALS CONTACT
A -M FIRE PROTECTION DISTRIBUTOR.
EL
1 OR 2 HR. FIRE RATED
WALLBOARD A
1 HOUR INSULATED PIPE/DUCT AND 2 HOUR INSULATED PIPE DETAIL
No Scale - - - - -- - - - -
EX--'x20'EA
Y
EX 12"x36" OA
0
RS/RL
-AHU-3 5 SIZED BY
6 -MANUR
O ���
O O H
O5 O
E' :ONCRETE PADS '-NEW CONCRETE PAD
4 AHU-3 MODULES
-
.14'=1 - -
AIR HANDLING UNIT SCHEDULE
T
SUPPLY FAN
._ _
_ELECTRIC HEAT -_- _ -__..
-
COOLING COIL -
ELECTRICAL
DIMENSIONS
'�
WEIGHT AIRFLOW TSP (IN. ESP (IN. MOTOR
MOTOR
EAT/LAT
OUTPUT FACE VELOCITY FACE AREA
APD (IN.! TOTAL CAPACITY
SENSIBLE CAPACITY
EADBIWlITADB/wB
FACEVELOCITY
FACE AR� FIN SPACING
FIN
HEAT HEAT
FAN
FAN
VOLTAGE/
UNIT _ MANUFACTURER MODEL
(W"xL"xH')
(LBS) (CFM) - _ H2O) H2O) BHP
HP
(°F)
(kW) (FPM) _(SQ. FT.)
H2O)
STAGES - (MBH)
(MBOH)-
(°F)
(°F) (FPM)_ _
(SQ. FT.) '.. STAGESTI, (PER FOOT)
MATERIAL
FILTERS
MCA M_OCP
MCA
MOCP
PHASE
AHU 3 -RA\E CSAA014 '�. 7L0"x144 6 x4L5"
! 2,053 6.400 2.61 ..00 3.69
5.0
45.E 78.0
56.8 - 11.7
0._
4 229 3
1
77.0/6S.0 54.1/52.9 476
13. 114
ALUMINUM
2 MERV 8
84.07 j 90
6.83
15
460V/30
NU I t:
1. PRO VIDE UNDER A-D ALTER'ATES #8 AND #9.
2. U^::T SHALL HA • E' ;N. SCCR RATING OF 65,000 A.
EXHAUST FAN SCHEDULE
AIRFLOW S.P.-FAN VOLTAGE/
UNIT !MANUFACTURER MODEL (CFM) (IN.) RPM i BHP HP SONES MCA MOCP PHASE
EF = GREEN-- -e I G-143-• -- ! 2,220 0.25 1,296 1 0.44 0.75 13.0 8.25 15 208V'10
NOTE-
1. F]VIDE UNDEF=U ALTERNATE =9 ONLY.
2. FR=VIDE FAN V+T- GRAVITY TYFE _'ACKDRAFT DAM=ER.
3. PF= 1IDE UNIT V, T-- SHAFT GROU'•= ING KIT OR IN'• r-RTER DUTY MOTOR FOR USE WITH VFD.
AIR-COOLED CONDENSING UNIT SCHEDULE
UNIT
MANUFAC_TUR_ER
MODEL
TTA120
TTA120
. CAPACITY
(TON--S>�-----------������TAGES
1D
_0
_REFRIGERANT CIRCUITS
_ R 4' = 1
! R 41-= 1
WEIGHT
(LBS)
T
MCA
MOCP
VOLTAGE/PHASE
ACCU-3A
TRANE
416.5
416.5
20
20
25
25
460V/30
460V/30
ACCU-3B
TRANE
No I t]:
1. PROVIDE UNDER BASE-D AND ADD ALTERNATES.
2. UNITS SHALL HAVE MI'• SCCR RATINGS OF 65,000 A.
COOLING COIL SCHEDULE
COIL PERFORMANCE
COIL FINS
AIRFLOW
TOTAL CAPACITY SENSIBLE CAPACITY EADB/WB LADB/WB FACE VELOCITY
APD (IN.
DIMENSIONS SPACING FACE AREA
UNIT MANUFACTURER MODE
(CFM)
6,400
_ (MBH) _ (M_BH) (°F) (°F) _ (FPM)
236.4 168 - 77.0/65 0-3.0/52.6 457
H2O)
-.73
(H"xL") (FINS/IN.) (SQ. FT.) ROWS MATERIAL
1 31.5"x64.0" 12 14.0 1 4 ALUMINUM
CC-3 PRECISION COILS DMSSr4S12
NOTES',
1. PROVIDE UNDER BASE BID ONLY,
NOTE: ALL MECHANICAL EQAPMENT FEED COMPONENT SH(c.- CIRCUIT CURRENT RATINGS SCCR) SHALL MEET CR EXCEED -HE MA\IMUM AIC RATING OF THE ELECTRICAL
PANEL IN VMICH IT IS SER, ED. REFER TO ELECTRICAL PANE_ SCHEDULES FOR REQUIRED PA',EL AIC RATINGS. AL RNATIV ELY, THE CONTRACTOR MAY PROVIDE THE
NECESSARY CALCULATIO'.S TO PROVE THE MECHANICAL EQ_:�MENT SCCR RATING PROVIDE) EXCEEDS THE SHOR- CIRCUIT CURREG' AVAILABLE AT THE EQUIPME"•-.
NOTE:
VERIFY BUILDING DIMENSIONS FOR ROUGH -IN'
WORK WITH ARCHITECTS DRAWINGS.
INVISION
11N.INc IA•Rcr;rEcruRE I iNreRioas
501 Sycamore Street
Suite 101
Waterloo, IA 50703
's 319.233.8419
319-233.9772 Fax
www.invisionarch.com
CONSULTANT:
mvuuzno
WATERLOODES MOINES IOWA CITY
REVISIONS:
Description Date No.
OWNER SIGN -OFF:
DATE NAME
U_ o
Z 0
Q
ry
=
U-i
U
w
3
I
F-
(/)
Z
Q
Z
LLJ
W
V)
Q
Z
0
Z
::D
(�
U
�
O
N
PROJECT NO:
19053
DATE:
2019.08.06
SHEET SET:
BID DOCUMENTS
SHEET NAME:
DETAILS & SCHEDULES
SHEET:
ME5.00
19-068 YOUNG ARENA MECHANICAL UPGRADES