HomeMy WebLinkAboutCOUNTRY INN & SUITES-4025 HAMMOMD AVE OF W A 7. INVOICE DATE DUE DATE INVOICE# TOTAL DUE
0 o 10/02/2026 11/06/2026 2027-00000148 $100.00
• •IA III II •
Customer#: 7011 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
COUNTRY INN & SUITES 715 Mulberry St
4025 HAMMOND AVE WATERLOO, IA 50703
WATERLOO, IA 50702
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION -4025 HAMMOND AVE-09/21/26 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 20,000 $90.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
7011 10/02/2026 11/06/2026 2027-00000148 $100.00
Less Prepayment $0.00
Total Due—* $100.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report 425 E.3rd Street
Country Inn&Suites-4025 Hammond AVE,BLDG 4025 Hammond Ave,Waterloo IA
50702
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
09/2112026 Annual Inspection(1Yr) .()' I U 1���JJJ���1"' cyo
22961
Lead Inspector Shift //! Station Unit
BRAD BALDWIN N/A NIA NIA
Other Inspectors
NIA
SUMMARY OF INSPECTION
C 43 39 ® 19
Passed codes Failed codes NIA codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN 10/15/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-09/2212026 @ 14:07
Annual fire alarm inspection and report to be uploaded to Compliance Engine due 1113126.
BRAD BALDWIN-0912212026 @ 13:18
House laundry dryer vent annual cleaning-Done by Harris cleaning November 2025
BRAD BALDWIN-0912212026 @ 08:26
Fire extinguishers due annually serviced January 2027
BRAD BALDWIN-09/2212026 @ 08:26
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-09122/2026 @ 08:26
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-09122/2026 @ 08:25
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#0)-Cell:319-230-1224
BRAD BALDWIN-09122/2026 @ 08:25
•$100 annual inspection fee
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GENERATED ON 9/22/26, 2:10 PM 1 OF 14
Jay Patel-2028 Date:
CHECKLISTS
BRAD BALDWIN 09122/2026
GENERATED ON 9/22/28, 2:10 PM
2 OF 14
Additional Codes
an, Code Description
Fail 1028.3•Exit discharge width or capacity.
The minimum width or required capacity of the exit discharge Location:NW exit
shall be not less than the minimum width or required capacity Comments:Trim bushes to avoid obstructing full width of exit
of the exits being served. discharge.
Fall 610.1.2-Maintenance.
OThe lint trap,mechanical and heating components,and the Location:Guest laundry dryer vent
exhaust duct system of a clothes dryer shall be maintained in Comments:Provide documentation of dryer vent cleaned from the
accordance with the manufacturer's operating appliance to the exterior of the building.
instructions to prevent the accumulation of lint or debris that
prevents the exhaust of air and products of combustion.
Fail 704.2-Repair of joints and voids.
>C9 Where damaged,materials used to protect joints and voids Location:Room 202
shall be replaced or restored with materials or systems that Comments:Missing escutcheons or improper escutcheons shall be
meet or exceed the code requirements applicable at the time replaced.
when the assembly was constructed,remodeled or altered.
Fail 901.6-Inspection,testing and maintenance.
Fire detection and alarm systems,emergency alarm systems, Location:Sprinkler system
gas detection systems,fire-extinguishing systems, Comments:Licensed contractor shall make repairs to deficiencies
mechanical smoke exhaust systems and smoke and heat (see attached)noted in Black Hawk Sprinkler inspection report
vents protection and life safety systems shall be maintained #10143710.Repair report shall then be uploaded to Compliance
in an operative condition at all times,and shall be replaced or Engine.
repaired where defective.Nonrequired fire protection and life
safety systems and equipment shall be inspected,tested and
maintained or removed in accordance with Section 901.8.
en o
Fail 907.2.11.1-Group R-1.
Single-or multiple-station smoke alarms shall be installed in Location:All sleeping rooms
all of the following locations in Group R-1:1.In sleeping Comments:Provide documentation of smoke detectors in all rooms
areas.2.In every room in the path of the means of egress are present,have been tested and are working properly.Document
from the sleeping area to the door leading from the sleeping shall be emailed to inspector.
unit.3.In each story within the sleeping unit,including
basements.For sleeping units with split levels and without an
intervening door between the adjacent levels,a smoke alarm
installed on the upper level shall suffice for the adjacent
lower level provided that the lower level is less than one full
story below the upper level.
GENERATED ON 9/22/28, 2:10 PM 3 OF 14
Fail 907.8.4-Inspection,testing and maintenance.
The building owner shall be responsible to maintain the fire Location:Pool room storage
and life safety systems in an operable condition at all times. Comments:Fire alarm device shall be corrected to avoid hanging by
Service personnel shall meet the qualification requirements wires.
of NFPA 72 for inspection,testing and maintenance of such
systems.Records of inspection,testing and maintenance
shall be maintained.
.5 h
- r
.
•
Emergency Equipment
Status lode Description
Fail 1203.2.15-Means of egress illumination.
Ox Emergency power shall be provided for means of egress Location:Pool-Above hot tub
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Repair or replace egress light that failed to illuminate
during test
GENERATED ON 9/22/28, 2:10 PM 4 OF 14
Fire Sprinkler System
5[ cc, Description
Fail 903.3.3-Obstructed locations.
Automatic sprinklers shall be installed with regard to Location:Near main front doors
obstructions that will delay activation or obstruct the water Comments:Licensed contractor shall replace plugged sprinkler
distribution pattern and shall be in accordance with the head
applicable automatic sprinkler system standard that is being
used.Automatic sprinklers shall be installed in or under
covered kiosks,displays,booths,concession stands or
equipment that exceeds 4 feet(1219 mm)in width.Not less
than a 3-foot(914 mm)clearance shall be maintained between
automatic sprinklers and the top of piles of combustible
fibers.Exception:Kitchen equipment under exhaust hoods
protected with a fire-extinguishing system in accordance with
Section 904.
Q� P
GENERATED ON 0/22/20, 2:10 PM 5 OF 14
Fire Service Features
Status Gorse Description
Fail 505.1•Address identification.
New and existing buildings shall be provided with approved Location:Front of building(facing Hammond Ave)
address Identification.The address identification shall be Comments:Install permanent address identification numbers in
legible and placed in a position that is visible from the street contrast with the building,easily visible from the road(minimum 4"in
or road fronting the property.Address identification height)
characters shall contrast with their background.Address
numbers shall be Arabic numbers or alphabetical letters.
Numbers shall not be spelled out.Each character shall be not
less than 4 inches(102 mm)high with a minimum stroke
width of 112 inch(12.7 mm).Where required by the fire code
official,address identification shall be provided in additional
approved locations to facilitate emergency response.Where
access is by means of a private road and the building cannot
be viewed from the public way,a monument,pole or other
sign or means shall be used to identify the structure.Address
identification shall be maintained.
Fail 506.2-Key box maintenance.
The operator of the building shall immediately notify the fire Location:Knox Box
code official and provide the new key where a lock is changed Comments:Contact Waterloo Fire Department at 319-291-4460 and
or rekeyed.The key to such lock shall be secured in the key provide copy of all master keys for Knox Box
box.
Fail 509.2-Equipment access.
Approved access shall be provided and maintained for all fire Location:3rd floor-Dry Sprinkler Riser Room
protection system equipment to permit immediate safe Comments:Remove storage within 36"of sprinkler equipment and
operation and maintenance of such equipment.Storage,trash maintain clear ready access at all times.
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
Fail 509.2-Equipment access.
Approved access shall be provided and maintained for all fire Location:1st floor-Sprinkler Riser Room
protection system equipment to permit immediate safe Comments:Remove storage(ladder,softener salt and snow blower)
operation and maintenance of such equipment.Storage,trash within 36"of sprinkler equipment and maintain clear ready access to
and other materials or objects shall not be placed or kept in equipment at all times.
such a manner that would prevent such equipment from
being readily accessible.
GENERATED ON 9/22/26, 2:10 PM 6 OF 14
Electrical Safety
States Cone Description
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
Open junction boxes and open-wiring splices shall be Location:Pool equipment room
prohibited.Approved covers shall be provided for all switch Comments:Blower electrical installation shall be contained as
and electrical outlet boxes. manufactured to avoid exposed wire connection.
.rt
tor- qk : .
t
a
Fail 603.5.2-Application and usePower supply.
ORelocatable power taps and current taps shall be directly Location:Office-1st floor
connected to a permanently installed receptacle.Exceptions: Comments:Remove power strip plugged to another power strip
1.Where approved for use in a Group A occupancy or in a behind computer,must plug directly to a wall outlet
meeting room in a Group B occupancy,not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment.2.Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
GENERATED ON 9/22/20, 2:10 PM 7 OF 14
Fire Resistant Construction Maintenance
Status Code Description
Fail 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:2nd floor electric room-near vending
materials and systems used to protect joints and voids in the Comments:Pipe penetration through ceiling and floor shall be sealed
following locations shall be maintained.The materials and to maintain proper fire rating.
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floor/ceiling assemblies and roof or
rooflceiling assemblies.2.3oints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Y 1
�< M1I f tt
1 ` r - d t .i`r !.
4 i' e
-. r r
tit ' 4 .� 6 t� t;t / c r:f
C -.ti
y' 1 ,.5(ti' .,.r 1.
a;
� a
'
I
Y
GENERATED ON 9/22/26, 2:10 PM 8 OF 14
Fail 704.1-Maintaining protection.
Where required when the building was originally constructed, Location:Pool equipment room
materials and systems used to protect joints and voids in the Comments:Hole in ceiling needs repaired to maintain proper fire
following locations shall be maintained.The materials and rating.A building
systems shall be securely attached to or bonded to the permit and inspection will be required If repair is
larger than 1 Sq Ft in size due to hole in fire wall.
adjacent construction,without openings visible through the
construction.1.Joints in or between fire-resistance-rated
walls,floors or floorlceiling assemblies and roof or
roof/ceiling assemblies.2.Joints in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
j
411�r 4, 1�3i� • 4,7 0' 4, I-
S
e
•
•
iv `Y
§.k. ; :*fit .#:xk.• e
GENERATED ON 9/22/2G, 2:10 PM 9 OF 14
Fall 704.1-Maintaining protection.
0 Where required when the building was originally constructed, Location:Pool mechanical room
materials and systems used to protect joints and voids In the Comments:Pipe penetration through walls shall he sealed to
following locations shall be maintained.The materials and maintain proper fire rating.
systems shall be securely attached to or bonded to the
adjacent construction,without openings visible through the
construction.1.Joints In or between lire-resistance-rated
walls,floors or floor/ceiling assemblies and roof or
rooffceiling assemblies.2.Jolnts in smoke barriers.3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall.4.Volds at the Intersection of a horizontal smoke
barrier and an exterior curtain wall.5.Voids at the intersection
of a nonfiire-resistance-rated floor assembly and an exterior
curtain wall.6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall.7.Voids at the intersection
of a vertical fire barrier and a nonf ire-resistance-rated roof
assembly.Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed.Where the system design number is known,the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.
Fail 705.2-Inspection and maintenance.
OOpening protectives in fire-resistance-rated assemblies shall Location:3rd floor elevator fire drop doors
be inspected and maintained in accordance with NFPA 80.
Opening Comments:Carefully remove paint covering frame fire rating labels.
p g protectives in smoke barriers shall be inspected and Removal of label of information on label requires re-certification or
maintained in accordance with NFPA 80 and NFPA 105. replacement.
Openings in smoke partitions shall be inspected and
maintained in accordance with NFPA 105.Fire doors and
smoke and draft control doors shall not be blocked,
obstructed,or otherwise made inoperable.Fusible links shall
be replaced promptly whenever fused or damaged.Opening
protectives and smoke and draft control doors shall not be
modified.
Fail 705.2-Inspection and maintenance.
OOpening protectives in fire-resistance-rated assemblies shall Location:All required fire rated door frames in building.
be inspected and maintained in accordance with NFPA 80. Comments:Frames missing properly rated smoke seals shall be
Opening protectives in smoke barriers shall be inspected and installed.Retain documents of smoke seals to provide to inspector.
maintained in accordance with NFPA 80 and NFPA 105.
Openings in smoke partitions shall be inspected and
maintained in accordance with NFPA 105.Fire doors and
smoke and draft control doors shall not be blocked,
obstructed,or otherwise made inoperable.Fusible links shall
be replaced promptly whenever fused or damaged.Opening
protectives and smoke and draft control doors shall not be
modified.
Fail 705.2-Inspection and maintenance.
OOpening protectives in fire-resistance-rated assemblies shall Location:New key reader door hardware for all sleeping rooms
be inspected and maintained in accordance with NFPA 80. Comments:Provide documentation of hardware includes proper fire
Opening protectives in smoke barriers shall be inspected and
maintained in accordance with NFPA 80 and NFPA 105. rating,email documents to inspector.
Openings in smoke partitions shall be inspected and
maintained In accordance with NFPA 105.Fire doors and
smoke and draft control doors shall not be blocked,
obstructed,or otherwise made inoperable.Fusible links shall
be replaced promptly whenever fused or damaged.Opening
protectives and smoke and draft control doors shall not be
modified.
uesenaTED ON g/22/26, 2:10 PM
10 OF 14
� 4
Fail 705.2.4• Door operation.
O Swinging fire doors shall close from the full-open position Location: 3rd floor elevator drop doors
and latch automatically, Comments: Repair or replace fire doors that failed to self-close and
latch.
Fail 705.2.4- Door operation.
OSwinging fire doors shall close from the full-open position Location: Room 320
and latch automatically. Comments: Repair or replace fire doors that failed to self-close and
latch.
Fail 705.2.4 - Door operation.
Ox Swinging fire doors shall close from the full-open position Location: Room 310
and latch automatically. Comments: Repair or replace fire doors that failed to self-close and
latch.
Fail 705.2.4 - Door operation.
OSwinging fire doors shall close from the full-open position Location: Room 301
and latch automatically. Comments: Repair or replace fire doors that failed to self-close and
latch.
Fail 705.2.4 - Door operation.
0 V Swinging fire doors shall close from the full-open position Location: 3rd floor stairwell door - near room #391
and latch automatically. Comments: Repair or replace fire doors that failed to self-close and
latch.
Fail 705.2.4 - Door operation.
0 Swinging fire doors shall close from the full-open position Location: 2nd floor stairwell door - near room #203
and latch automatically. Comments: Repair or replace fire doors that failed to self-close and
latch.
Fail 705.2.4 - Door operation.
Ux Swinging fire doors shall close from the full-open position Location: 2nd floor electric room - near vending machines
and latch automatically. Comments: Remove door hold-open device, required fire rated doors
shall self-close and latch.
Fail 705.2.4 - Door operation.
Swinging fire doors shall close from the full-open position Location: 2nd floor elevator fire drop doors
and latch automatically. Comments: Repair or replace fire doors that failed to self-close and
latch.
Fail 705.2.4 - Door operation.
0 Swinging fire doors shall close from the full-open position Location: 1st floor stairwell door - near room #129
and latch automatically. Comments: Repair or replace fire doors that failed to self-close and
latch.
Fail 705.2.4- Door operation.
Swinging fire doors shall close from the full-open position Location: 1st floor closet near room #129
and latch automatically. Comments: Repair or replace fire doors that failed to self-close and
latch. Door missing closure, closure and all door hardware shall
include proper fire rating.
Fail 705.2.4 - Door operation.
Swinging fire doors shall close from the full-open position Location: Room 119
and latch automatically. Comments: Repair or replace fire doors that failed to self-close and
latch.
GENERATED ON 9/22/2G, 2:1A PM 11 OF 14
Fail 705.2.4-Door operation.
Swinging fire doors shall close from the full-open position Location:Room 116
and latch automatically. Comments:Repair or replace fire doors that failed to self-close and
latch.
Fail 705.2.4-Door operation.
Swinging fire doors shall close from the full-open position Location:1st floor laundry
and latch automatically. Comments:Remove door hold-open device,required fire rated doors
shall self-close and latch
Fail 705.2.4-Door operation.
Swinging fire doors shall close from the full-open position Location:1st floor stairwell door-near pool entry
and latch automatically. Comments:Repair or replace fire doors that failed to self-close and
latch.
Fail 705.2.4-Door operation.
() Swinging fire doors shall close from the full-open position Location:2nd floor electric room-near vending machine
and latch automatically. Comments:Remove door hold-open device,required fire doors shall
self-close and latch.
Fail 705.2.4-Door operation.
OSwinging fire doors shall close from the full-open position Location:1st floor-Sprinkler Riser Room
and latch automatically. Comments:Repair or replace fire doors that failed to self-close and
latch.
Fail 705.2.4-Door operation.
Swinging fire doors shall close from the full-open position Location:Guest laundry room
and latch automatically. Comments:Repair or replace fire doors that failed to self-close and
latch,door missing latch
GENERATED ON 9/22/28, 2:10 PM 12 OF 14
Portable Fire Extingusihers
orI, Description
Fail 906.1-Where required.
Portable fire extinguishers shall be installed in all of the Location:Front desk
following locations:1.In new and existing Group A,B,E,F,H, Comments:Remove residential listed extinguisher.Current required
I,M,R-1,R-2,R-4 and S occupancies.Exceptions:1.In Group extinguishers are in place as needed.
R-2 occupancies,portable fire extinguishers shall be required
only in locations specified in Items 2 through 6 where each
dwelling unit is provided with a portable fire extinguisher
having a minimum rating of 1-A:10-B:C.2.In Group E
occupancies,portable fire extinguishers shall be required
only in locations specified in Items 2 through 6 where each
classroom is provided with a portable fire extinguisher having
a minimum rating of 2-A:20-B:C.3.In storage areas of Group
S occupancies where forklift,powered industrial truck or
powered cart operators are the primary occupants,fixed
extinguishers,as specified in NFPA 10,shall not be required
where in accordance with all of the following:3.1.Use of
vehicle-mounted extinguishers shall be approved by the fire
code official.3.2.Each vehicle shall be equipped with a 10-
pound,40A:80B:C extinguisher affixed to the vehicle using a
mounting bracket approved by the extinguisher manufacturer
or the fire code official for vehicular use.3.3.Not less than
two spare extinguishers of equal or greater rating shall be
available on-site to replace a discharged extinguisher.3.4.
Vehicle operators shall be trained in the proper operation,use
and inspection of extinguishers.3.5.Inspections of vehicle-
mounted extinguishers shall be performed daily.2.Within 30
feet(9144 mm)distance of travel from commercial cooking
equipment and from domestic cooking equipment in Group I-
1;1-2,Condition 1;and R-2 college dormitory occupancies.
3.In areas where flammable or combustible liquids are stored,
used or dispensed.4.On each floor of structures under
construction,except Group R-3 occupancies,in accordance
with Section 3316.1.5.Where required by the sections
indicated in Table 906.1.6.Special-hazard areas,including but
not limited to laboratories,computer rooms and generator
rooms,where required by the fire code official.Exception:
Portable fire extinguishers are not required at normally
unmanned Group U occupancy buildings or structures where
a portable fire extinguisher suitable to the hazard of the
location is provided on the vehicle of visiting personnel.
Fail 906.7-Hangers and brackets.
Hand-held portable fire extinguishers,not housed in cabinets, Location:Pool mechanical room
shall be installed on the hangers or brackets supplied. Comments:Fire extinguisher on shelf shall be mounted on wall
Hangers or brackets shall be securely anchored to the bracket 4"above floor and maximum 5'from floor in height
mounting surface in accordance with the manufacturer's
installation instructions.