COMMERCIAL FIRE INSPECTION -820 W 5TH ST-09/18/26 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
21883 10/02/2026 11/06/2026 2027-00000149 $80.00
Less Prepayment $0.00
Total Due-p $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
"a Waterloo Fire Rescue
IPIC1 }
k Inspection Report 425 E.3rd Street
Dollar General-820 W 5th ST,BLDG 820 W 5th St,Waterloo IA 50701
INSPECTION DETAILS
1
Inspection Date Inspection Type
Inspection Number
0911812026 Annual Inspection(1Yr) c /3 0 3 ��E- 24323
Lead Inspector Shift Station
Unit
BRAD BALDWIN NIA NIA N/A
Other Inspectors
N/A
SUMMARY OF INSPECTION
030 05 ® 38
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to:
Reinspection Date
BRAD BALDWIN
brad.baldwin@waterloo-ia.org,3192914319 10/16/2026
GENERAL NOTES
BRAD BALDWIN-09118/2026 @ 14:29
Fire extinguishers due annually serviced April 2027
BRAD BALDWIN-09118/2026 @ 14:28
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-09/18/2026 @ 14:28
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#0)-Cell:319-230-1224
BRAD BALDWIN-09/18/2026 @ 14:28
•$80 annual inspection fee
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Tina Peterson-District Manager Date: BRAD BALDWIN 09118/2026
CHECKLISTS
GENERATED ON 9/18/26, 2:35 PM
1 OF 4
Emergency Equipment
SI.rl, F.4412 Description
Fail 1203.2.15-Means of egress Illumination.
Emergency power shall be provided for means of egress Location:Above kleenex
Illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Relocate merchandise obstructing emergency egress
light.
Fall 1203.2.6-Exit signs.
Emergency power shall be provided for exit signs as required Location:Main exit(interior door)
in Section 1013.6.3.The system shall be capable of powering Comments:Repair or replace exit signlegress light combo that tailed
the required load for a duration of not less than 90 minutes. to illuminate during test
General Housekeeping
Stair, Code Deer:option
Fail 315.3.1-Ceiling clearance,
Storage shall be maintained 2 feet(610 mm)or more below Location:Sales floor
the ceiling in nonsprinkleretl areas of buildings or not less Comments:Lower merchandise within 24"of ceiling.Maintain proper
than 18 inches(457 mm)below sprinkler head deflectors in clearance at all times.
sprinklered areas of buildings.Exceptions:1.The 2-foot(610
mm)ceiling clearance is not required for storage along walls
in nonsprinklered areas of buildings.2.The 18-inch(457 mm)
ceiling clearance is not required for storage along walls in
areas of buildings equipped with an automatic sprinkler
system in accordance with Section 903.3.1.1,903.3.1.2 or
903.3.1.3.
Electrical Safety
Status Code Description
Fail 603.5.2-Application and usePower supply.
Relocatable power taps and current taps shall be directly Location:Office
connected to a permanently installed receptacle.Exceptions: Comments:Remove power strip daisy chained(front one strip to
1.Where approved for use in a Group A occupancy or in a another).Each power strip shall plug directly to a wall outlet
meeting room in a Group B occupancy,not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment.2.Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
2 OF 4
GENERATED ON 0/18/26, 2:35 PH
Fire Resistant Construction Maintenance
Status Code Description
Fail 704.1 - Maintaining protection.
Where required when the building was originally constructed, Location: Bathroom
materials and systems used to protect joints and voids in the Comments: Replace missing ceiling tile
following locations shall be maintained. The materials and
systems shall be securely attached to or bonded to the
adjacent construction, without openings visible through the
construction. 1.Joints in or between fire-resistance-rated
walls, floors or floorlceiling assemblies and roof or
roof/ceiling assemblies. 2.Joints in smoke barriers. 3.Voids at
the intersection of a horizontal floor assembly and an exterior
curtain wall. 4.Voids at the intersection of a horizontal smoke
barrier and an exterior curtain wall. 5.Voids at the intersection
of a nonfire-resistance-rated floor assembly and an exterior
curtain wall. 6.Voids at the intersection of a vertical fire
barrier and an exterior curtain wall. 7.Voids at the intersection
of a vertical fire barrier and a nonfire-resistance-rated roof
assembly. Unprotected joints and voids do not need to be
protected where such joints and voids were not required to
be protected when the building was originally
constructed. Where the system design number is known, the
system shall be inspected to the listing criteria and
manufacturer's installation instructions.