HomeMy WebLinkAboutSTARBECK'S SMOKEHOUSE-250 WESTFIELD AVE OF W q rF INVOICE DATE DUE DATE INVOICE# TOTAL DUE
'cle 10/02/2026 11/06/2026 2027-00000164 $80.00
• '11 ■u i 111I I •
) *-= T 0
4S it'll'
Customer#: 24391 Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
STARBECK'S SMOKEHOUSE 715 Mulberry St
250 WESTFIELD AVE WATERLOO, IA 50703
WATERLOO, IA 50701
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION -250 WESTFIELD AVE-09/17/26 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 2,000 $70.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
24391 10/02/2026 11/06/2026 2027-00000164 $80.00
Less Prepayment $0.00
Total Due— $80.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
425 E.3rd Street
Starbeck's Smokehouse-250 Westfield AVE,BLDG 250 Westfield Ave,Waterloo IA
50701
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
09117/2026 Annual Inspection(1Yr) a43c1 18802
Lead Inspector Shift Station ��- Unit
BRAD BALDWIN N/A NIA NIA
Other Inspectors
N/A
SUMMARY OF INSPECTION
053 022 ® 10
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
1010912026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-09/18/2026 @ 09:10
Fire extinguishers due annually serviced in April 2027
BRAD BALDWIN-09/18/2026 @ 08:56
Kitchen hood cleaning due 11118/26
BRAD BALDWIN-09118/2026 @ 08:56
Kitchen hood suppression due for inspection on 10/27/26
BRAD BALDWIN-09/18/2026 @ 08:54
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and$200 for all subsequent re-inspections.
BRAD BALDWIN-0911812026 @ 08:54
•Provide corrections to avoid progressive re-inspection fees beginning at$100.Beer/Liquor application will not be signed until violations and hazards
corrected
BRAD BALDWIN-09/18/2026 @ 08:54
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#0)-Cell:319-230-1224
BRAD BALDWIN-09/18/2026 @ 08:54
•$80 annual inspection fee
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
GENERATED ON 0/18/26, 9:42 AM
1 OF 11
Corbin Burr-2026 Date: I-qM,
CHECKLISTS
Emergency Equipment BRAD BALDWIN 0911812026
Status Code Description
Fall 1203.2.15-Means of egress illumination.
OEmergency power shall be provided for means of egress Location:Kitchen exit
illumination in accordance with Sections 1008.3 and 1104.5.1. Comments:Storage on shelving shall be relocated to avoid
obstructing view of exit sign.
IP
rI ..-..,,,s.,,..1:
,Y . i
.._______
Fail 1203.2.6-Exit signs.
JEmergency power shall be provided for exit signs as required Location:East exit near patio seating
in Section 1013.6.3.The system shall be capable of powering Comments:Exit sign turned wrong direction,exit sign shall face
the required load for a duration of not less than 90 minutes. dining area to direct to exit door.
Fail 1203.4.3-Records.
Records of the inspection,testing and maintenance of Comments:All exit signage and emergency egress lighting shall be
emergency and standby power systems shall include the date tested and repaired if necessary to maintain working properly.
of service,name of the servicing technician,a summary of Provide documentation of testing to inspector.
conditions noted and a detailed description of any conditions
requiring correction and what corrective action was taken.
Such records shall be maintained.
1
GENERATED ON 9/18/26, 9:42 AN 2 OF 11
Fire Sprinkler System
Status Code Description
Fail 4.9-Support of nonsprinkler system components
1`; Sprinkler system components shall not be used to support Location:East dining area
non-sprinkler system components unless expressly permitted Comments:Remove signs supported by sprinkler system.
by NFPA 13.
11' Ir
-r R _�-
1 F c p }
Rath ~_ E Va.
Feed
t '„„%ft.. ,'-:"„Agli
AL ' ` \_.rr... -- y -
GENERATED ON 9/18/2G, 0:42 AM 3 OF 11
Fire Service Features
Status Code Description
Fail 509.2-Equipment access.
Approved access shall be provided and maintained for all fire Location:East exit near patio seating
protection system equipment to permit immediate safe Comments:Remove obstructions to fire alarm pull station,maintain
operation and maintenance of such equipment.Storage,trash clear line of sight to pull station at all times.
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
•
F.!
Fail 509.2-Equipment access.
Approved access shall be provided and maintained for all fire Location:Fire department connection-North Exterior
protection system equipment to permit immediate safe Comments:Remove all storage from area as stated on signage.
operation and maintenance of such equipment.Storage,trash
and other materials or objects shall not be placed or kept in
such a manner that would prevent such equipment from
being readily accessible.
1
(i EEt, 9r
t
i i y S
V.
GENERATED ON 9/10/26, 0:42 MI 4 OF 11
Additional Codes
Status Code Description
Fail 5303.5,3-Securing compressed gas containers,cylinders
and tanks. Location:CO2 closet behind soda fountain machine
Compressed gas containers,cylinders and tanks shall be Comments:Secure compressed gas cylinders tightly with chain to
secured to prevent falling caused by contact,vibration or avoid tip over.Currently tanks are loosely chained and one tank
seismic activity,Securing of compressed gas containers, unchained.
cylinders and tanks shall be by one of the following methods:
1.Securing containers,cylinders and tanks to a fixed object
with one or more restraints.2.Securing containers,cylinders
and tanks on a cart or other mobile device designed for the
movement of compressed gas containers,cylinders or tanks.
3.Nesting of compressed gas containers,cylinders and tanks
at container filling or servicing facilities or in sellers'
warehouses not open to the public.Nesting shall be allowed
provided that the nested containers,cylinders or tanks,if
dislodged,do not obstruct the required means of egress.
4.Securing of compressed gas containers,cylinders and
tanks to or within a rack,framework,cabinet or similar
assembly designed for such use.Exception:Compressed gas
containers,cylinders and tanks in the process of
examination,filling,transport or servicing.
Fail 603.1-General.
Electrical equipment,wiring and systems required by this Location:Closet behind soda fountain machine
code or the International Building Code shall be installed, Comments:Appliances including motors or heating elements shall
used and maintained in accordance with NFPA 70 and plug directly to an outlet,currently plugged to a power strip.Remove
Sections 603.2 through 603.10. pump from power strip,if adding a new outlet,a licensed electrician
shall obtain permit and inspection
Fail 603.1.1-Equipment and fixtureswiring.
Electrical equipment and fixtures All electrical equipment, Location:Outdoor patio
wiring,devices and appliances shall be tested;and listed by Comments:Remove outlet improperly wired to create extension cord.
an approved agency and labeled;and installed,used and Cord and outlet shall be permanently removed from building.
maintained in accordance with NFPA 70 and all instructions
included as part of such listing.
,, `
tO ,V10 i .
7 y
/J�,
r
y.
i . .._
4 .?s,/,,..
GENERATED ON 0/1N/25, 0:42 AM 5 OF 11
Electrical Safety
St;ttus Code Description
Fall 603.2.2-Unapproved conditionsOpen electrical terminations.
Open junction boxes and open-wiring splices shall be Location:Ceiling above table#40
prohibited.Approved covers shall be provided for all switch Comments:Open wire connection shall be properly capped and
and electrical outlet boxes. contained in box with cover.
/).'
J rr
to f, }.<
/ '1/4 y s
�4,
Ais
Fail 603.2.2-Unapproved conditionsOpen electrical terminations.
Open junction boxes and open-wiring splices shall be Location:Ceiling above table#42
prohibited.Approved covers shall be provided for all switch
and electrical outlet boxes. Comments:Provide missing electrical box cover
GENERATED ON 9/18/26, 0:42 AM
6 OF 11.
Fail 603.5.2-Application and usePower supply.
Relocatable power taps and current taps shall be directly Location:East end of bar
connected to a permanently installed receptacle.Exceptions: Comments:Remove power strip plugged to extension cord,power
1.Where approved for use in a Group A occupancy or in a strips shall plug directly to an outlet.
meeting room in a Group B occupancy,not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment.2.Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
o al
,t
¢
1111:-.'.1111:1111:::
7 OF 11
GENERATED ON 9/18/26, 9:42 AM
Fail 603.5.2-Application and usePower supply.
Relocatable power taps and current taps shall be directly Location:Kitchen-below ordering counter
connected to a permanently installed receptacle.Exceptions: Comments:Power strip currently plugged to extension cord,power
1.Where approved for use In a Group A occupancy or In a strips shall plug directly to an outlet.Extension cord shall be
meeting room in a Group B occupancy,not more than five removed.
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment.2.Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
i
v
I.
r►
...,... ,,,,4_ . ,
%. __.... ,„ ... .
....,- ., sfircjor r -
4,-
- ._ 1 .,_ ,r. tl,
,„
4.s. ..„
I _
044
: __. /4 .,
-/,* :: ,- 0 . _ ..-.,:„.
..„ _ I'-i!, ,, ,, 1--- , , .
Fail 603.5.3-Installation.
Relocatable power tap cords shall not extend through walls, Location:East end of bar-Below"Shiner"sign
ceilings,floors,under doors or floor coverings,or be subject Comments:Power stripshall be properly supported
to environmental or physical damage. p p Y to avoid hanging
by wires.
Fail 603.5.3-Installation.
Relocatable power tap cords shall not extend through walls, Location:Kitchen office
ceilings,floors,under doors or floor coverings,or be subject Comments:Properly mount power strip below IT rack currently
to environmental or physical damage. hanging by wires.
GENERATED ON 9/18/26, 9:42 AM 8 OF 11
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:East end of bar-Below"Miller Lite"neon sign
for permanent wiring and shall be listed and labeled in Comments:Extension cords shall not be used as permanent wiring,
accordance with UL 817.Extension cords and flexible remove multi-plug extension cord.
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact,Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
wri, _ _
I _ ,, ,
! t ; '.„ ---'?'"
F.
r
t � t
IS
it ,
4F
kr i1.
f
a
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:"Founders"window sign near bar
for permanent wiring and shall be listed and labeled in Comments:Extension cords shall not be used as permanent wiring,
accordance with UL 817.Extension cords and flexible remove sign plugged to extension cord.
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Closet behind soda fountain machine
for permanent wiring and shall be listed and labeled in Comments:Extension cords shall not be used as permanent wiring.
accordance with UL 817.Extension cords and flexible Remove orange extension cord to"Beverage Control System".If
cordsshall not be affixed to structures,extended through adding a new outlet,a licensed electrical contractor shall obtain a
walls,ceilings or floors,or under doors or floor coverings, permit and inspection.Also,provide inspector information of cords
nor shall such cords be subject to environmental damage or extending through wall
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 9/18/28, 9:42 AM 9 OF 11
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Soda fountain machine
for permanent wiring and shall be listed and labeled In Comments:Remove green extension cord behind machine.
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Bar TV near"Rainbow"sign
for permanent wiring and shall be listed and labeled in Comments:Remove TV from plugged to extension cord.
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
Commercial Cooking Hood Suppression System
C: Ole Code Description
Fail 606.3.3-Cleaning.
Hoods,grease-removal devices,fans,ducts and other Location:Kitchen hood filters
appurtenances shall be cleaned at intervals as required by Comments:Filters above fryers need cleaned to avoid the
Sections 606.3.3.1 through 606.3.3.3.
accumulation of grease.
Portable Fire Extingusihers
Code Descnpdon
Fail 906.6-Unobstructed and unobscured.
Portable fire extinguishers shall not be obstructed or Location:Kitchen-below ordering counter
obscured from view.In rooms or areas in which visual
obstruction cannot be completely avoided,means shall be Comments:Remove shelf obstructing clear access to fire
extinguisher or relocate extinguisher to an approved readily
provided to indicate the locations of extinguishers.
accessible location.
r
a
GENERATED ON 9/18/26, 9:42 AM
10 OF 11
r'® Statement of Fees
FEE
Invoice Date Inspection Fee Date Paid Amount Paid
NIA $80.00
Invoice Number Check Number Transaction Number
NIA NIA NIA
GENERATED ON 9/19/28, 9:42 AM 11 OF 11