COMMERCIAL FIRE INSPECTION -2022 FALLS AVE-09/28/26 FOR BILLING INQUIRY: (319)291-4323
Description Total Price
INSPECTION 1 $40.00
OCCUPANCY FEE $10.00
CUSTOMER# BILLING DATE DUE DATE INVOICE# CHARGES
•
25093 10/02/2026 11/06/2026 2027-00000165 $50.00
Less Prepayment $0.00
Total Due -* $50.00
City of Waterloo
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Is Inspection Report 425 E.3rd Street
440 Sunny Spa Massage-2022 Fails AVE,BLDG 2022 Falls Ave,Waterloo IA 50701
INSPECTION DETAILS
Inspection Date Inspection Type Inspection Number
0912812026 Annual Inspection(1Yr) 0
C Et ,4 24439
Lead Inspector Shift Station Unit
BRAD BALDWIN N/A NIA N/A
Other Inspectors
NIA
SUMMARY OF INSPECTION
0 30 0 8 ® 39
Passed codes Failed codes N/A codes
NEXT STEPS
Please direct questions about your Inspection to: Reinspection Date
BRAD BALDWIN
11/03/2026
brad.baldwin@waterloo-ia.org,3192914319
GENERAL NOTES
BRAD BALDWIN-09128/2026 @ 13:55
Space heaters shall be commercially listed,residentially listed heaters are prohibited.
BRAD BALDWIN-0912812026 @ 13:55
•If all corrections are made before the scheduled re-inspection date,you can call to set up an earlier re-inspection.Normal operating hours for
inspections&re-inspections are Monday-Friday,9:00 a.m.-4:00 p.m.*****Re inspection fees may be assessed for subsequent re-inspections.Re-
inspection fees start at$100,then$150,and S200 for all subsequent re-inspections.
BRAD BALDWIN-0912812026 @ 13:55
•Commercial Fire Inspector-brad.baldwin@waterloo-ia.org-Work:319-291-4319(#0)-Cell:319-230-1224
BRAD BALDWIN-09/28/2026 @ 13:55
•$50 annual inspection fee
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Dajuan Cao-2026 Date: _ BRAD BALDWIN 09/28/2026
CHECKLISTS
GENERATED ON 0/28/2e, 2:36 PM 1 OF 7
Additional Codes
Status Code Description
Fall 1010.2.4-Locks and latches,
O Locks and latches shall be permitted to prevent operation of Location:Front exit door
doors where any of the following exist:1.Places of detention Comments:Update door hardware to comply with single motion
or restraint.2.In Group I.1,Condition 2 and Group 1.2 requirement.Door hardware shall require no more than(1)single
occupancies where the clinical needs of persons receiving motion to unlock and unlatch door,currently deadbolt and door knob
care require containment or where persons receiving care requires 2 motions.
pose a security threat,provided that all clinical staff can
readily unlock doors at all times,and all such locks are keyed
to keys carried by all clinical staff at all times or all clinical
staff have the codes or other means necessary to operate the
locks at all times.2.3.In buildings in occupancy Group A
having an occupant load of 300 or less,Groups B,F,M and S,
and In places of religious worship,the main door or doors are
permitted to be equipped with key-operated locking devices
from the egress side provided:2.1.3.1.The locking device is
readily distinguishable as locked.2.2.3.2.A readily visible
durable sign is posted on the egress side on or adjacent to
the door stating:"THIS DOOR TO REMAIN UNLOCKED WHEN
THIS SPACE IS OCCUPIED."The sign shall be in letters 1 inch
(25 mm)high on a contrasting background.2.3.3.3.The use
of the key-operated locking device is revocable by the fire
code official for due cause.3.4.Where egress doors are used
in pairs,approved automatic flush bolts shall be permitted to
be used,provided that the door leaf having the automatic
flush bolts does not have a doorknob or surface-mounted
hardware.4.5.Doors from individual dwelling or sleeping
units of Group R occupancies having an occupant load of 10
or less are permitted to be equipped with a night latch,dead
bolt or security chain,provided such devices are openable
from the inside without the use of a key or tool.5.6.Fire
doors after the minimum elevated temperature has disabled
the unlatching mechanism in accordance with listed fire door
test procedures.6.7.Doors serving roofs not intended to be
occupied shall be permitted to be locked,preventing entry to
the building from the roof.8.0ther than egress courts,where
occupants must egress from an exterior space through the
building for means of egress,exit access doors shall be
permitted to be equipped with an approved locking device
where installed and operated in accordance with all of the
following:8.1.The maximum occupant load shall be posted
where required by Section 1004.9.Such sign shall be
permanently affixed inside the building and shall be posted in
a conspicuous space near all the exit access doorways.8.2.A
weatherproof telephone or two-way communication system
installed in accordance with Sections 1009.8.1 and 1009.8.2
shall be located adjacent to not less than one required exit
access door on the exterior side.8.3.The egress door locking
device is readily distinguishable as locked and shall be a key-
operated locking device.8.4.A clear window or glazed door
opening,not less than 5 square feet(0.46 m2)in area,shall
be provided at each exit access door to determine if there are
occupants using the outdoor area.8.5.A readily visible
durable sign shall be posted on the Interior side on or
adjacent to each locked required exit access door serving the
exterior area stating:"THIS DOOR TO REMAIN UNLOCKED
WHEN THE OUTDOOR AREA IS OCCUPIED."The letters on
the sign shall be not less than 1 inch(25.4 mm)high on a
contrasting background.8.e.The occupant load of the
occupied exterior area shall not exceed 300 occupants in
accordance with Section 1004.9.Locking devices are
permitted on doors to balconies,decks or other exterior
spaces serving individual dwelling or sleeping units.
10.Locking devices are permitted on doors to balconies,
decks or other exterior spaces of 250 square feet(23.23
m2)or less,serving a private office space.
GENERATED ON a/28/26, 2:36 PR 2 OF 7
a
Fall 603.1 - General.
OElectrical equipment, wiring and systems required by this Location: Front room
code or the International Building Code shall be installed, Comments: Remove microwave plugged to multi-plug adapter.
used and maintained in accordance with NFPA 70 and Appliances including heating elements shall plug directly to a wall
Sections 603.2 through 603.10. outlet.
Fall 807.3 -Acceptance criteria and reports.
OWhere required to exhibit improved fire performance, Location: Entire space
curtains, draperies, fabric hangings and other similar Comments: Provide documentation of all curtains and draperies in
combustible decorative materials suspended from walls or building meet proper flame spread index. Curtain & draperies not in
ceilings shall be tested by an approved agency and meet the compliance shall be permanently removed.
flame propagation performance criteria of Test Method 1 or
Test Method 2, as appropriate, of NFPA 701 or exhibit a
maximum rate of heat release of 100 kW when tested in
accordance with NFPA 289, using the 20 kW ignition source.
0: -,. 4 iii:& . . ,
Reports of test results shall be prepared in accordance with
the test method used and furnished to the fire code official
upon request.
""�
.. ....Ana.M.._e.. '`
zed i
a �t _ ..
..... _ .
, Y ' .1:4"t# tihts*,0 1-1' ‘)
lit . ,
{ ' ' .;gip ..! E: y'. oaX�y�. --.� IT y �� ei
r „� ...Tics.- lvdelfrapviv ,
. • .
1 '..
I.
IhI
GENERATED ON 9/28/26, 2:36 PM 3 OF 7
Electrical Safety
S:a:us Code Description
Fail 603.4•Working space and clearancesclearance.
A working space of not Working space around electrical Location:Mechanical room
equipment shall be provided in accordance with Section Comments:Remove all storage within 36 inches of electrical panel
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or and maintain clear path of access at all times.
less,and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts.The minimum required working space
shall be not less than 30 Inches(762 mm)in width,36 inches
(914 mm)in depth and 78 inches(1981 mm)in height shall be
providedin front of electrical service equipment.Where the
electrical service equipment is wider than 30 inches(762
mm),the minimum working space shall be not less than the
width of the equipment.Storage of materials shall not be
located within the designated working space.Exceptions:1.
Where other dimensions are required or allowed by NFPA 70.
2.Access openings into attics or under-floor areas that
provide a minimum clear opening of 22 inches(559 mm)by 30
inches(762 mm),
•
' 7.
t MF
•
Fail 603.4.1-Labeling.
Doors into electrical control panel rooms shall be marked Location:Mechanical room
with a plainly visible and legible sign stating"ELECTRICAL Comments:Provide permanent signage on closet doors indicating
ROOM"or similar approved wording.The disconnecting "MECHANICAL ROOM"or other approved wording.Laminated paper
means for each service,feeder or branch circuit originating will not be accepted as permanent.
on a switchboard or panelboard shall be legibly and durably
marked to indicate its purpose unless such purpose is clearly
evident.Where buildings or structures are supplied by more
than one power source,markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
GENERATED ON 0/28/26, 2:36 PM 4 OF 7
Fall 603.6•Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Front room below window
for permanent wiring and shall be listed and labeled In Comments:Remove all extension cords.Also,please note:
accordance with UL817.Extension cords and flexible Christmas lighting is approved for temporary use only(maximum 90
affixed not be affixed to structures,extended through days)
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical Impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
tiy.f a
.t
.
i 4
j
4 .1
\\,..........)
Fail 603.6-Extension cords.
Extension cords and flexible cordsshall not be a substitute Location:Near back door
for permanent wiring and shall be listed and labeled in Comments:Remove extension cord plugged to candle warmer.
accordance with UL 817.Extension cords and flexible
cordsshall not be affixed to structures,extended through
walls,ceilings or floors,or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact.Extension cords shall be used only with
portable appliances.Extension cords marked for indoor use
shall not be used outdoors.
GENERATED ON 9/28/28, 2:38 PM 5 OF 7
Portable Fire Extingusihers
Status Code Description
Fall 906.2-General requirements.
C Portable fire extinguishers shall be selected,installed and Location:Extinguisher
maintained in accordance with this section and NFPA 10. Comments:Provide required annual service to extinguisher,no
Exceptions:1.The distance of travel to reach an extinguisher current date of last service.If self-purchasing,a minimum of a 2-A:10-
shall not apply to the spectator seating portions of Group A-5 B:C extinguisher with receipt shall be installed on a wall bracket 4"to
occupancies.2.Thirty-day inspections shall not be required 5'off the floor,tape receipt to bottom of extinguisher
and maintenance shall be allowed to be once every 3 years
for dry-chemical or halogenated agent portable fire
extinguishers that are supervised by a listed and approved
electronic monitoring device,provided that all of the
following conditions are met:2.1.Electronic monitoring shall
confirm that extinguishers are properly positioned,properly
charged and unobstructed.2.2.Loss of power or circuit
continuity to the electronic monitoring device shall initiate a
trouble signal.2.3.The extinguishers shall be installed inside
of a building or cabinet in a noncorrosive environment.
2.4.Electronic monitoring devices and supervisory circuits
shall be tested every 3 years when extinguisher maintenance
is performed.2.5.A written log of required hydrostatic test
dates for extinguishers shall be maintained by the owner to
verify that hydrostatic tests are conducted at the frequency
required by NFPA 10.3.In Group 1-3,portable fire
extinguishers shall be permitted to be located at staff
locations.