HomeMy WebLinkAboutA0.00_TITLE SHEET_Rev.0BRACE WALL STUD FRAMING TO
STRUCTURE ABOVE
DEFLECTION SLIP TRACK
16GA.CR. BRIDGING
CHANNEL AS REQ'D. BY
MANUFACTURER FOR HEIGHT
LIMITS
SI
ADJUST CEILING TILE & GRID
AS NEEDED FOR NEW WALL
AND RE-FINISHING OF
EXISTING WALLS
1 LAYER OF 5/8" GYPSUM WALL
BOARD SHEATHING ON BOTH
SIDES OF METAL STUD FRAMING
ABOVE 8-0" FRP LEVEL
3 5/8" OR 6" METAL STUD FRAMING,
SEE SPECIFICATIONS FOR SPACING
& GAGE
EPOXY BASE AS NOTED
FINISHED FLOOR LINE
A 6A
INDICATED AS
ON PLANS
1 LAYER OF 5/8" FIRE TREATED
SHEATHING ON BOTH SIDES OF
METAL STUD FRAMING FROM
FLOOR TO 8'-0", FRP OVER TOP
CITY OF WATERLOO
5 SULLIVAN BROTHER CONVENTION
CENTER KITCHEN REMODEL ABBREVIATIONS:
ACT ACOUSTICAL CEILING TILE
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE
ALUM ALUMINUM
APROX APPROXIMATE
ARCH ARCHITECTURAL
AW ARCHITECTURAL WOODWORK
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BGC BY GENERAL CONTRACTOR
BO BY OTHER (THAN CONTRACTOR)
BOC BOTTOM OF CURB
CAB CABINET
CB CERAMIC BASE
CG CORNER GUARD
CLG CEILING
CJ CONTROL JOINT
CL CENTERLINE
CMU CONCRETE MASONRY UNIT
CONC CONCRETE
CONT CONTINUOUS
CPT CARPET
CT CERAMIC TILE
CTB CERAMIC TILE BASE
D DEPTH
DEMO DEMOLITION
DIA DIAMETER
DN DOWN
DTL DETAIL
DWG DRAWING
ELECT ELECTRICAL
ELEV ELEVATION
EM ENTRY MATT
EJ EXPANSION JOINT
EQ EQUAL
EXT EXTERIOR
EXIST EXISTING
FD FLOOR DRAIN
FEC FIRE EXTINGUISHER CABINET
FV FIELD VERIFY
GC GENERAL CONTRACTOR
GWB GYPSUM WALL BOARD
GYP GYPSUM
HM HOLLOW METAL
HOR HORIZONTAL
INSUL INSULATION
KS KNEE SPACE
LKR LOCKER
MANUF MANUFACTURER
MAX MAXIMUM
MECH MECHANICAL
MIN MINIMUM
MIL MILLIMETER
MTL METAL
MISC MISCELLANEOUS
NS NATRUAL STONE
NSB NATRUAL STONE BLEND
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OPGN OPENING
OD OVERFLOW ROOF DRAIN
OC ON CENTER
OPP OPPOSITE
PLAM PLASTIC LAMINATE
PLYWD PLYWOOD
PREFIN PREFINISHED
PT PAINT
PORCT PROCELAIN TILE
RAD RADIUS
RB RUBBER BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REQD REQUIRED
RF RESILIENT FLOORING
SC SEALED CONCRETE
SCHED SCHEDULE
SPECD SPECIFIED
STRUCT STRUCTURAL
SIM SIMILAR
T&G TONGUE AND GROOVE
THRU THROUGH
TYP TYPICAL
UL UNDERWRITERS LABORATORIES
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VCT VINYL COMPOSITE TILE
VIF VERIFY IN FIELD
VWC VINYL WALL COVERING
W/ WITH
W/O WITHOUT
WB WOOD BASE
WBL WOOD BLOCKING
WD WOOD
WSCT WAINSCOT
WWF WELDED WIRE FABRIC
WWM WELDED WIRE MESH
205 W 4TH ST
WATERLOO, IA 50701
BID DOCUMENTS
10.21.2019
VERIFY REQ'D. CLEARANCE
FOR DEFLECTION
PROJECT NO:
16021
DATE:
10.21.2019
SHEET SET:
BID DOCUMENTS
SHEET NAME:
TITLE SHEET
SHEET:
AO.00
Copyright fc) 2019
INVISION
PLANNING | ARCHITECTURE | INTERIORS
501 Sycamore Street
Suite 101
Waterloo, IA 50703
319.233.8419
319.233.9772 Fax
www.invisionarch.com
CONSULTANT:
MEP
MODUS ENGINEERING
REVISIONS:
Description Date No.
OWNER SIGN-OFF:
DATE NAME
SHEET INDEX:
1. ARCHITECTURAL
A0.00 TITLE SHEET
A1.10 LOWER LEVEL FLOOR PLAN
A1.40 LOWER LEVEL - ENLARGED FLOOR PLAN
2. MEP
ME001 COVER SHEET
PD101 PLUMBING DEMOLITION PLAN
P101 PLUMBING NEW WORK PLAN
GENERAL NOTES:
1. ALL WORK SHALL COMPLY WITH APPLICABLE CODES AND ORDINANCE IN FORCE AT TIME OF CONSTRUCTION.
2. VERIFY ALL DIMENSIONS, EXISTING AND NEW CONDITIONS ON THE JOB BEFORE PROCEEDING WITH THE WORK.
DISCREPANCIES, IF ANY, ARE TO BE REFERRED TO THE ARCHITECT IMMEDIATELY FOR DETERMINATION ON HOW
TO PROCEED.
3. UNLESS NOTED OTHERWISE, THE PLAN DIMENSIONS SHOWN ARE:
A. TYPICALLY TO THE CENTERLINE OF INTERIOR PARTITIONS
B. TO THE FACE OF WALLS IN HALLWAYS SHOWING CLEAR WIDTHS
C. TO THE FACE OF FURRED OUT WALLS
D. TO THE FACE OF MASONRY OR CONCRETE WHERE INDICATED
E. IF DIMENSION POINT IS IN QUESTION, CONTACT ARCHITECT
4. CONTRACTORS SHALL CONSULT PLANS OF ALL TRADES FOR OPENINGS AND ROUGH-OUTS THROUGH SLABS,
WALLS, CEILINGS, AND ROOFS FOR DUCTS, PIPES, CONDUITS, CABINETS AND EQUIPMENT, AND SHALL VERIFY SIZE
AND LOCATION BEFORE PROCEEDING WITH WORK.
5. PROVIDE FIRE RESISTIVE CLOSURE, MEETING THE REQUIREMENTS OF THE GOVERNING FIRE AUTHORITIES, AT
ALL GAPS AROUND THE PENETRATING DUCT, PIPES, CONDUITS, ETC, AT ALL FIRE RATED BUILDING PARTITIONS
AND CEILINGS.
6. THE CONTRACTOR SHALL VERIFY ALL ROUGH-IN DIMENSIONS AND EQUIPMENT, FURNISHED AND INSTALLED BY
HIMSELF/HERSELF OR OTHERS, PRIOR TO PROCEEDING WITH WORK.
7. ROOM FINISH SCHEDULE SHALL NOT BE TAKEN AS A COMPLETE SPECIFICATION FOR ALL INTERIOR ROOM
MATERIALS. HOWEVER, IT SHALL BE BINDING TO THE EXTENT OF THE MATERIAL IT DOES SPECIFY. THE
CONTRACTOR SHALL CHECK THE SCHEDULE WITH SPECIFICATIONS AND DRAWINGS FOR OTHER MATERIALS NOT
COVERED BY THE SCHEDULE.
8. REFER TO SPECIFICATIONS FOR ACCESS DOORS AND CONSULT WITH MECHANICAL CONTRACTOR FOR EXACT
LOCATIONS OF ACCESS REQUIRED BY THEIR WORK. ACCESS MUST BE PROVIDED FOR ALL CONCEALED VALVES,
DAMPER CONTROLS, FIRE DAMPER LINKAGE, ELECTRICAL JUNCTION BOXES, ETC. OBTAIN ARCHITECT'S APPROVAL
IN LOCATING ALL ACCESS DOORS PRIOR TO INSTALLATION.
9. ALL PIPING, CONDUITS, DUCTS, ETC, SHALL BE FURRED-IN, IN ALL ROOMS EXCEPT ELECTRICAL CLOSETS,
TELEPHONE CLOSETS, MECHANICAL ROOMS, AND ROOMS DESIGNATED IN THE ROOM FINISH SCHEDULE TO HAVE
EXPOSED ROOF STRUCTURE.
10. MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL NOTES AND SYMBOLS
11. CONTRACTOR SHALL COORDINATE WITH ALL OWNER FURNISHED ITEMS AND PROVIDE ALL REQUIRED
MECHANICAL AND ELECTRICAL CONNECTIONS, INCLUDING STUB OUTS FOR NEW OR FUTURE WORK.
12. PROVIDE CONSTRUCTION AND CONTROL JOINTS IN CONCRETE SLABS ON GRADE TO MATCH EXISTING
ADJACENT LOCATIONS.
13. ALL CONCEALED WOOD BLOCKING IN INTERIOR WALLS IS REQUIRED TO BE FIRE TREATED.
14. CONTRACTOR TO MOVE EXISTING EQUIPMENT AND PROTECT ALL OTHER EQUIPMENT AND AREAS WHERE
CONSTRUCTION IS NOT HAPPENING.
15. REMOVE AND REINSTALL CEILING TILE AND GRID AS NEEDED FOR ABOVE CEILING WORK, COORDINATE WITH
MEP DRAWINGS.
16. FLOOR DEMO IS SHOWN AS A REFERENCE/APPROXIMATE AMOUNT THAT NEEDS TO BE REMOVED.
COORDINATE WITH MEP DRAWINGS AND VERIRYING OF EXISTING PIPING LOCATIONS TO DETERMINE DEMO
AMOUNT.
CROSS REFERENCE LEGEND:
LETTERS OR NUMBERS
REFERS TO SECTION OR
DETAIL
SIM1 NUMBER REFERS TO THE
SHEET# ON WHICH THE
DETAIL APPEARS
A101
INDICATES WALL CONSTRUCTION TYPE
ALTERNATES:
COORDINATE W/ MEP DRAWINGS AND SPEC FOR MORE INFO:
BASE BID: PVC PIPING FOR SANITARY SEWER PIPING AND COPPER TUBING FOR DOMESTIC WATER PIPING
ALTERNATE #1 : STAINLESS STEEL PIPING FOR SANITARY SEWER PIPING AND PEX PIPING FOR DOMESTIC WATER
ALTERNATE #2: CHEMDRAIN POLY PROPYLENE PIPING FOR SANITARY SEWER PIPING.
I hereby certify that the portion of this technical submission described
below was prepared by me or under my direct supervision and
responsible charge. I am a duly registered architect under the laws of the
State of Iowa.
MICHAEL R BROSHAR
m- ■%%
S£?a MICHAEL R
= BROSHAR= ?
°0V s Printed or typed name
' Q
Signature
02463 JUNE 30, 2020 SEPTEMBER 9, 1983
Date issued
_ o
Doc,uTV Registration expireso
° o O O O o °
">//,„ iowfc ////////iminm"V ARCHITECTURAL SERIES
Pages or sheets covered by this seal
6" MIN.
td
5 SULLIVAN BROTHER CONVENTION
CENTER KI
T
C
HE
N
REMODEL
205 W 4TH ST
WATERLOO, IA 50
7
01
CITY OF WATERLOO
1 0/15/2019 1 1 :41 :03 AM
C:\RevitLocalFiles\16021_5 Sullivan Brother Convention C enter_R 1 5_cody m. rvt
CROSS REFERENCE LEGEND:
LETTERS OR NUMBERS
REFERS TO SECTION OR
DETAIL NUMBER REFERS TO THE
SHEET # ON WHICH THE
DETAIL APPEARS
INDICATES WALL CONSTRUCTION TYPE
A101
1 SIM
XXX
GENERAL NOTES:
1. ALL WORK SHALL COMPLY WITH APPLICABLE CODES AND ORDINANCE IN FORCE AT TIME OF CONSTRUCTION.
2. VERIFY ALL DIMENSIONS, EXISTING AND NEW CONDITIONS ON THE JOB BEFORE PROCEEDING WITH THE WORK.
DISCREPANCIES, IF ANY, ARE TO BE REFERRED TO THE ARCHITECT IMMEDIATELY FOR DETERMINATION ON HOW
TO PROCEED.
3. UNLESS NOTED OTHERWISE, THE PLAN DIMENSIONS SHOWN ARE:
A. TYPICALLY TO THE CENTERLINE OF INTERIOR PARTITIONS
B. TO THE FACE OF WALLS IN HALLWAYS SHOWING CLEAR WIDTHS
C. TO THE FACE OF FURRED OUT WALLS
D. TO THE FACE OF MASONRY OR CONCRETE WHERE INDICATED
E. IF DIMENSION POINT IS IN QUESTION, CONTACT ARCHITECT
4. CONTRACTORS SHALL CONSULT PLANS OF ALL TRADES FOR OPENINGS AND ROUGH-OUTS THROUGH SLABS,
WALLS, CEILINGS, AND ROOFS FOR DUCTS, PIPES, CONDUITS, CABINETS AND EQUIPMENT, AND SHALL VERIFY SIZE
AND LOCATION BEFORE PROCEEDING WITH WORK.
5. PROVIDE FIRE RESISTIVE CLOSURE, MEETING THE REQUIREMENTS OF THE GOVERNING FIRE AUTHORITIES, AT
ALL GAPS AROUND THE PENETRATING DUCT, PIPES, CONDUITS, ETC., AT ALL FIRE RATED BUILDING PARTITIONS
AND CEILINGS.
6. THE CONTRACTOR SHALL VERIFY ALL ROUGH-IN DIMENSIONS AND EQUIPMENT, FURNISHED AND INSTALLED BY
HIMSELF/HERSELF OR OTHERS, PRIOR TO PROCEEDING WITH WORK.
7. ROOM FINISH SCHEDULE SHALL NOT BE TAKEN AS A COMPLETE SPECIFICATION FOR ALL INTERIOR ROOM
MATERIALS. HOWEVER, IT SHALL BE BINDING TO THE EXTENT OF THE MATERIAL IT DOES SPECIFY. THE
CONTRACTOR SHALL CHECK THE SCHEDULE WITH SPECIFICATIONS AND DRAWINGS FOR OTHER MATERIALS NOT
COVERED BY THE SCHEDULE.
8. REFER TO SPECIFICATIONS FOR ACCESS DOORS AND CONSULT WITH MECHANICAL CONTRACTOR FOR EXACT
LOCATIONS OF ACCESS REQUIRED BY THEIR WORK. ACCESS MUST BE PROVIDED FOR ALL CONCEALED VALVES,
DAMPER CONTROLS, FIRE DAMPER LINKAGE, ELECTRICAL JUNCTION BOXES, ETC. OBTAIN ARCHITECT'S APPROVAL
IN LOCATING ALL ACCESS DOORS PRIOR TO INSTALLATION.
9. ALL PIPING, CONDUITS, DUCTS, ETC., SHALL BE FURRED-IN, IN ALL ROOMS EXCEPT ELECTRICAL CLOSETS,
TELEPHONE CLOSETS, MECHANICAL ROOMS, AND ROOMS DESIGNATED IN THE ROOM FINISH SCHEDULE TO HAVE
EXPOSED ROOF STRUCTURE.
10. MECHANICAL, AND ELECTRICAL DRAWINGS FOR ADDITIONAL NOTES AND SYMBOLS
11. CONTRACTOR SHALL COORDINATE WITH ALL OWNER FURNISHED ITEMS AND PROVIDE ALL REQUIRED
MECHANICAL AND ELECTRICAL CONNECTIONS, INCLUDING STUB OUTS FOR NEW OR FUTURE WORK.
12. PROVIDE CONSTRUCTION AND CONTROL JOINTS IN CONCRETE SLABS ON GRADE TO MATCH EXISTING
ADJACENT LOCATIONS.
13. ALL CONCEALED WOOD BLOCKING IN INTERIOR WALLS IS REQUIRED TO BE FIRE TREATED.
14. CONTRACTOR TO MOVE EXISTING EQUIPMENT AND PROTECT ALL OTHER EQUIPMENT AND AREAS WHERE
CONSTRUCTION IS NOT HAPPENING.
15. REMOVE AND REINSTALL CEILING TILE AND GRID AS NEEDED FOR ABOVE CEILING WORK, COORDINATE WITH
MEP DRAWINGS.
16. FLOOR DEMO IS SHOWN AS A REFERENCE/APPROXIMATE AMOUNT THAT NEEDS TO BE REMOVED.
COORDINATE WITH MEP DRAWINGS AND VERIRYING OF EXISTING PIPING LOCATIONS TO DETERMINE DEMO
AMOUNT.
ABBREVIATIONS:
ACT ACOUSTICAL CEILING TILE
AFF ABOVE FINISHED FLOOR
ALT ALTERNATE
ALUM ALUMINUM
APROX APPROXIMATE
ARCH ARCHITECTURAL
AW ARCHITECTURAL WOODWORK
BD BOARD
BLDG BUILDING
BLKG BLOCKING
BGC BY GENERAL CONTRACTOR
BO BY OTHER (THAN CONTRACTOR)
BOC BOTTOM OF CURB
CAB CABINET
CB CERAMIC BASE
CG CORNER GUARD
CLG CEILING
CJ CONTROL JOINT
CL CENTER LINE
CMU CONCRETE MASONRY UNIT
CONC CONCRETE
CONT CONTINUOUS
CPT CARPET
CT CERAMIC TILE
CTB CERAMIC TILE BASE
D DEPTH
DEMO DEMOLITION
DIA DIAMETER
DN DOWN
DTL DETAIL
DWG DRAWING
ELECT ELECTRICAL
ELEV ELEVATION
EM ENTRY MATT
EJ EXPANSION JOINT
EQ EQUAL
EXT EXTERIOR
EXIST EXISTING
FD FLOOR DRAIN
FEC FIRE EXTINGUISHER CABINET
FV FIELD VERIFY
GC GENERAL CONTRACTOR
GWB GYPSUM WALL BOARD
GYP GYPSUM
HM HOLLOW METAL
HOR HORIZONTAL
INSUL INSULATION
KS KNEE SPACE
LKR LOCKER
MANUF MANUFACTURER
MAX MAXIMUM
MECH MECHANICAL
MIN MINIMUM
MIL MILLIMETER
MTL METAL
MISC MISCELLANEOUS
NS NATRUAL STONE
NSB NATRUAL STONE BLEND
NIC NOT IN CONTRACT
NTS NOT TO SCALE
OPGN OPENING
OD OVERFLOW ROOF DRAIN
OC ON CENTER
OPP OPPOSITE
PLAM PLASTIC LAMINATE
PLYWD PLYWOOD
PREFIN PREFINISHED
PT PAINT
PORCT PROCELAIN TILE
RAD RADIUS
RB RUBBER BASE
RCP REFLECTED CEILING PLAN
RD ROOF DRAIN
REQD REQUIRED
RF RESILIENT FLOORING
SC SEALED CONCRETE
SCHED SCHEDULE
SPECD SPECIFIED
STRUCT STRUCTURAL
SIM SIMILAR
T&G TONGUE AND GROOVE
THRU THROUGH
TYP TYPICAL
UL UNDERWRITERS LABORATORIES
UNO UNLESS NOTED OTHERWISE
VERT VERTICAL
VCT VINYL COMPOSITE TILE
VIF VERIFY IN FIELD
VWC VINYL WALL COVERING
W/ WITH
W/O WITHOUT
WB WOOD BASE
WBL WOOD BLOCKING
WD WOOD
WSCT WAINSCOT
WWF WELDED WIRE FABRIC
WWM WELDED WIRE MESH
ALTERNATES:
COORDINATE W/ MEP DRAWINGS AND SPEC FOR MORE INFO:
BASE BID: PVC PIPING FOR SANITARY SEWER PIPING AND COPPER TUBING FOR DOMESTIC WATER PIPING
ALTERNATE #1: STAINLESS STEEL PIPING FOR SANITARY SEWER PIPING AND PEX PIPING FOR DOMESTIC WATER
ALTERNATE #2: CHEMDRAIN POLY PROPYLENE PIPING FOR SANITARY SEWER PIPING.
ADJUST CEILING TILE & GRID
AS NEEDED FOR NEW WALL
AND RE-FINISHING OF
EXISTING WALLS
16 GA. C.R. BRIDGING
CHANNEL AS REQ'D. BY
MANUFACTURER FOR HEIGHT
LIMITS
BRACE WALL STUD FRAMING TO
STRUCTURE ABOVE
VERIFY REQ'D. CLEARANCE
FOR DEFLECTION
3 5/8" OR 6" METAL STUD FRAMING,
SEE SPECIFICATIONS FOR SPACING
& GAGE
EPOXY BASE AS NOTED
FINISHED FLOOR LINE
1 LAYER OF 5/8" GYPSUM WALL
BOARD SHEATHING ON BOTH
SIDES OF METAL STUD FRAMING
ABOVE 8'-0" FRP LEVEL
6"
M
I
N
.
INDICATED AS
ON PLANS
A
DEFLECTION SLIP TRACK
1 LAYER OF 5/8" FIRE TREATED
SHEATHING ON BOTH SIDES OF
METAL STUD FRAMING FROM
FLOOR TO 8'-0", FRP OVER TOP
6A
PLANNING ARCHITECTURE INTERIORS
Copyright C 2019
OWNER SIGN-OFF:
SHEET NAME:
PROJECT NO:
DATE:
SHEET SET:
REVISIONS:
DATE
SHEET:
NAME
501 Sycamore Street
Suite 101
Waterloo, IA 50703
319.233.8419
319.233.9772 Fax
www.invisionarch.com
CONSULTANT:
10
/
1
5
/
2
0
1
9
1
1
:
4
1
:
0
3
A
M
C:
\
R
e
v
i
t
L
o
c
a
l
F
i
l
e
s
\
1
6
0
2
1
_
5
S
u
l
l
i
v
a
n
B
r
o
t
h
e
r
C
o
n
v
e
n
t
i
o
n
C
e
n
t
e
r
_
R
1
5
_
c
o
d
y
m
.
r
v
t
CITY OF WATERLOO
5 SULLIVAN BROTHER CONVENTION
CENTER KITCHEN REMODEL
205 W 4TH ST
WATERLOO, IA 50701
BID DOCUMENTS
10.21.2019
A0.00
10.21.2019
TITLE SHEET
16021
5
S
U
L
L
I
V
A
N
B
R
O
T
H
E
R
C
O
N
V
E
N
T
I
O
N
CE
N
T
E
R
K
I
T
C
H
E
N
R
E
M
O
D
E
L
20
5
W
4
T
H
S
T
WA
T
E
R
L
O
O
,
I
A
5
0
7
0
1
CI
T
Y
O
F
W
A
T
E
R
L
O
O
BID DOCUMENTS
MODUS ENGINEERING
MEP
SHEET INDEX:
REGISTE R E D P R OFESSIONAL
A
R
C
H
I
TECT
O WI A
I hereby certify that the portion of this technical submission described
below was prepared by me or under my direct supervision and
responsible charge. I am a duly registered architect under the laws of the
State of Iowa.
Pages or sheets covered by this seal
Printed or typed name
Signature
Registration expires Date issued
MICHAEL R
BROSHAR
02463
MICHAEL R BROSHAR
ARCHITECTURAL SERIES
JUNE 30, 2020 SEPTEMBER 9, 1983
1. ARCHITECTURAL
A0.00 TITLE SHEET
A1.10 LOWER LEVEL FLOOR PLAN
A1.40 LOWER LEVEL - ENLARGED FLOOR PLAN
2. MEP
ME001 COVER SHEET
PD101 PLUMBING DEMOLITION PLAN
P101 PLUMBING NEW WORK PLAN
Description Date No.
Alternate #1 : Below grade sanitary sewer piping shall be stainless steel in lieu of PVC andcopper piping for domestic water.
Alternate #2: Below grade sanitary sewer piping shall be CPVC (Chemdrain) in lieu of PVC
and copper piping for domestic water.
Alternate #3: Above grade domestic water piping shall be PEX (in sticks) in lieu of copper.
Addendum 2.pdf