HomeMy WebLinkAboutGREEN LEAF TOBACCO AND E-CIGS-1503 E SAN MARNAN STE CINVOICE DATE
DUE DATE
INVOICE #
TOTAL DUE
10/12/2026
11/16/2026
2027-00000183
$80.00
Customer #: 24828
GREEN LEAF TOBACCO AND E-CIGS
1608 UNIVERSITY AVE
WATERLOO, IA 50701
Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
715 Mulberry St
WATERLOO, IA 50703
Amount Enclosed.
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL FIRE INSPECTION - 1503 E SAN MARNAN STE C-
10/12/26
FOR BILLING INQUIRY: (319)291-4323
Description
Total Price
INSPECTION 2,000
OCCUPANCY FEE
$70.00
$10.00
CUSTOMER # BILLING DATE
24828
10/12/2026
DUE DATE
11/16/2026
City of Waterloo
INVOICE #
2027-00000183
Less Prepayment
Total Due
CHARGES
$80.00
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
INVOICE DATE
DUE DATE
INVOICE #
TOTAL DUE
10/27/2025
11/30/2025
2026-00000187
$80.00
C PAST L
Customer #: 24828
GREEN LEAF TOBACCO AND E-CIGS
1608 UNIVERSITY AVE
WATERLOO, IA 50701
Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
715 Mulberry St
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 1608 UNIVERSITY - 10-9-25
FOR BILLING INQUIRY: (319)291-4323
Description
INSPECTION 2,000
OCCUPANCY FEE
Total Price
$70.00
$10.00
CUSTOMER #
24828
BILLING DATE
DUE DATE
INVOICE #
CHARGES
10/27/2025
11/30/2025
City of Waterloo
2026-00000187
Less Prepayment
Total Due —>
$80.00
$0.00
$80.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
INVOICE DATE
DUE DATE
INVOICE #
TOTAL DUE
12/09/2025
01/10/2026
2026-00000249
$150.00
C PAST L
Customer #: 24828
GREEN LEAF TOBACCO AND E-CIGS
1608 UNIVERSITY AVE
WATERLOO, IA 50701
Please Make Check Payable and Remit To:
City of Waterloo
ATTN: City Clerk/Accounts Receivable
715 Mulberry St
WATERLOO, IA 50703
Amount Enclosed:
DETACH AND RETURN TOP PORTION WITH YOUR PAYMENT
KEEP THIS PORTION FOR YOUR RECORDS
COMMERCIAL INSPECTION - 1608 UNIVERSITY AVE - 12-5-25
FOR BILLING INQUIRY: (319)291-4323
Description
REINSPECTION 2
Total Price
$150.00
CUSTOMER #
24828
BILLING DATE
DUE DATE
INVOICE #
CHARGES
12/09/2025
01/10/2026
2026-00000249
$150.00
Less Prepayment
Total Due —>
City of Waterloo
$0.00
$150.00
Failure to pay in full debts listed herein within ninety days of the due date will result in an additional twenty-five percent
late fee applied to any outstanding balance. The delinquent account will be forwarded to Municipal Collections of
America for further collection efforts. Debts shall also be subject to collection through the Iowa Department of
Administrative Services Offset Program if not paid in full within ninety days.
Waterloo Fire Rescue
Inspection Report
Green Leaf Tobacco and E-Cigs - 1503 E San Marnan Suite C DR, BLDG 1503 E San
Marnan Dr, Waterloo IA 50702
INSPECTION DETAILS
Inspection Date
10/1212026
Inspection Type
Annual Inspection (1Yr)
Lead Inspector Shift Station
BRAD BALDWIN NIA NIA
Other lnspectors
NIA
425 E. 3rd Street
Inspection Number
r 10531
Unit
NIA
SUMMARY OF INSPECTION
0 30
Passed codes
NEXT STEPS
k 13 ® 38
Failed codes NIA codes
Please direct questions about your Inspection to:
BRAD BALDWIN
brad.baldwin@waterloo-ia.org, 3192914319
GENERAL NOTES
Reinspection Date
1111212026
BRAD BALDWIN - 1011312026 @ 08:21
• If all corrections are made before the scheduled re -inspection date, you can call to set up an earlier re -inspection. Normal operating hours for
inspections & re -inspections are Monday - Friday, 9:00 a.m. - 4:00 p.m. *****Re inspection fees may be assessed for subsequent re -inspections. Re -
inspection fees start at $100, then $150, and $200 for all subsequent re -inspections.
BRAD BALDWIN - 1011312026 @ 08:21
• Commercial Fire Inspector - brad.baldwin@waterloo-ia.org - Work: 319-291-4319 (#0) - Cell: 319-230-1224
BRAD BALDWIN - 10113/2026 @ 08:21
• $80 annual inspection fee
SIGNATURES
Contact signature Inspector signature
No signature
Report completed post inspection
Mo Date: BRAD BALDWIN 10113/2026
CHECKLISTS
GENEAATEU
/26, 9:60 AM 1 OF 9
Additional Codes
Status Code
Fail
Fail
Fail
102.4 - Application of building code.
The design and construction of new structures shall comply
with the International Building Code , and any alterations,
additions, changes in use or changes in structures required
by this code, which are within the scope of the International
Building Code , shall be made in accordance therewith.
6603.1.1 - General.
The storage and use of unstable (reactive) materials in
amounts not exceeding the maximum allowable quantity per
control area indicated in Section 5003.1 shall be in
accordance with Sections 5001, 5003, 6601 and 6603.
807.2 - Combustible decorative materials.
In Groups A, B, E, I, M and R-1 and in dormitories in Group R-
2, curtains, draperies, fabric hangings and other similar
combustible decorative materials suspended from walls or
ceilings shall comply with Section 807.3 and shall not exceed
10 percent of the specific wall or ceiling area to which such
materials are attached. Fixed or movable walls and partitions,
paneling, wall pads and crash pads applied structurally or for
decoration, acoustical correction, surface insulation or other
purposes shall be considered to be interior finish, shall
comply with Section 803 and shall not be considered
decorative materials or furnishings. Exceptions: 1.In
auditoriums in Group A, the permissible amount of curtains,
draperies, fabric hangings and similar combustible decorative
material suspended from walls or ceilings shall not exceed 75
percent of the aggregate wall area where the building is
equipped throughout with an approved automatic sprinkler
system in accordance with Section 903.3.1.1, and where the
material is installed in accordance with Section 803.15 of the
International Building Code. 2.In Group R-2 dormitories,
within sleeping units and dwelling units, the permissible
amount of curtains, draperies, fabric hangings and similar
decorative materials suspended from walls or ceilings shall
not exceed 50 percent of the aggregate wall areas where the
building is equipped throughout with an approved automatic
sprinkler system installed in accordance with Section 903.3.1.
3.In Group B and M occupancies, the amount of combustible
fabric partitions suspended from the ceiling and not
supported by the floor shall comply with Section 807.3 and
shall not be limited. 4.The 10-percent limit shall not apply to
curtains, draperies, fabric hangings and similar combustible
decorative materials used as window coverings.
Description
Location: Cigar Room
Comments: Building and electrical permits shall be obtained for
"Cigar Room" constructed without permits.
Location: LED window lighting
Comments: Provide documentation of proper listing and use per
listing of lighting. Noted non -American listing label on lighting (see
photo). Lighting shall be removed if improperly listed or not used per
its approved listing.
• t
Location: Back storage room
Comments: Provide documentation of curtains over windows meet
proper flame spread index. Curtains may either be treated by licensed
contractor or remove.
GENERATED ON 10/13/26, 9:50 AM
2 OF 9
Fire Service Features
Status Code
Fail
505.1 • Address identification.
New and existing buildings shall be provided with approved
address Identification. The address identification shall be
legible and placed in a position that is visible from the street
or road fronting the property. Address identification
characters shall contrast with their background. Address
numbers shall be Arabic numbers or alphabetical letters.
Numbers shall not be spelled out. Each character shall be not
less than 4 inches (102 mm) high with a minimum stroke
width of 112 inch (12.7 mm). Where required by the fire code
official, address identification shall be provided in additional
approved locations to facilitate emergency response. Where
access is by means of a private road and the building cannot
be viewed from the public way, a monument, pole or other
sign or means shall be used to identify the structure. Address
identification shall be maintained.
Description
Comments: Provide permanent address Identification numbers on
the front side (north) of the building, easily visible from the road
GENERATED ON 10/13/26, 8:50 AM
3 OF 9
Electrical Safety
Stares Cod?
Fail
Fail
Fail
603.2 • Abatement of unsafe conditions and electrical
hazards.
Identified electrical hazards shall be abated. Identified
hazardous electrical conditions in permanent wiring shall be
brought to the attention of the responsible code official,
Electrical wiring, devices, appliances and other equipment
that is modified or damaged and constitutes Conditions that
constitute an electrical shock or fire hazard shall be abated
not be used.
603.4 - Working space and clearancesclearance.
A working space of not Working space around electrical
equipment shall be provided in accordance with Section
110.26 of NFPA 70 for electrical equipment rated 1,000 volts or
less, and Section 110.33 of NFPA 70 for electrical equipment
rated over 1,000 volts. The minimum required working space
shall be not less than 30 inches (762 mm) in width, 36 inches
(914 mm) in depth and 78 inches (1981 mm) in height shall be
providedin front of electrical service equipment. Where the
electrical service equipment is wider than 30 inches (762
mm), the minimum working space shall be not less than the
width of the equipment. Storage of materials shall not be
located within the designated working space. Exceptions: 1.
Where other dimensions are required or allowed by NFPA 70.
2. Access openings into attics or under -floor areas that
provide a minimum clear opening of 22 inches (559 mm) by 30
inches (762 mm).
603.4.1 - Labeling.
Doors into electrical control panel rooms shall be marked
with a plainly visible and legible sign stating "ELECTRICAL
ROOM" or similar approved wording. The disconnecting
means for each service, feeder or branch circuit originating
on a switchboard or panelboard shall be legibly and durably
marked to indicate its purpose unless such purpose is clearly
evident. Where buildings or structures are supplied by more
than one power source, markings shall be provided at each
service equipment location and at all interconnected electric
power production sources identifying all electric power
sources at the premises in accordance with NFPA 70.
Description
Location: Back storage - office
Comments: Remove microwave and small fridge plugged to daisy
chained power strips. Appliances including motors or heating
elements shall plug directly to an outlet. Power strips shall plug
directly to an outlet and for low wattage electronics only. Staff noted
electrical issues throughout building when using microwave,
inspector directed staff on -site to unplug appliances as currently
installed immediately,
Location: Back storage
Comments: Remove obstructions to electric panel, maintain 36" in
front of panel for clear access at all times.
Location: Back storage room door
Comments: Provide permanent approved signage indicating
"ELECTRIC PANEL" or other approved wording on door. Laminated
paper will not be accepted as permanent.
GENEPATEO ON 40/11/2G, 5;50 AM
4 OF 9
Fail
603.5.2 - Application and usePower supply.
Relocatable power taps and current taps shall be directly
connected to a permanently installed receptacle. Exceptions:
1. Where approved for use In a Group A occupancy or in a
meeting room in a Group B occupancy, not more than five
relocatable power taps shall be permitted to be connected
together or connected to an extension cord for temporary use
to supply power to electronic equipment. 2. Current taps and
relocatable power taps shall not be required to connect
directly to a permanently installed receptacle outlet where
used for 90 days or less for the purpose of testing the
performance of such devices.
Location: Below register counter
Comments: Power strips shall plug directly to an outlet and shall be
properly supported to avoid hanging by wires.
GENERATED ON 10/13/28, 8:50 AM
5 OF 9
Fall
603.6 • Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Behind register counters
Comments: Multiple locations noted of cords strung across walk
paths, a listed cord protector shall be installed for cords in walk
paths to avoid possible damage.
GENERATED ON 10/13/20, 0:50 AN
6 OF 9
Fail
Fail
603.6 - Extension cords,
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Near register - behind display counters
Comments: Remove black multi -plug extension cord,
Location: ATM
Comments: Remove extension cord plugged to ATM.
GENERATED ON 10/13/20, 9:5O AN
/ OF 9
Fail 603.6 • Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Fail 603.6 - Extension cords.
Extension cords and flexible cordsshall not be a substitute
for permanent wiring and shall be listed and labeled in
accordance with UL 817. Extension cords and flexible
cordsshall not be affixed to structures, extended through
walls, ceilings or floors, or under doors or floor coverings,
nor shall such cords be subject to environmental damage or
physical impact. Extension cords shall be used only with
portable appliances. Extension cords marked for indoor use
shall not be used outdoors.
Location: Glass Room
Comments: All extension cords shall be removed, extension cords
shall not be used as a substitute for permanent wiring. If adding new
outlets, a licensed electrical contractor shall obtain permit and
inspection. Also, cords across walk paths shall be protected by listed
cord protectors.
Location: Cigar Room
Comments: Humidifier appliance shall be directly plugged to a
permanent outlet, remove from extension cord. Adding a new outlet
requires a licensed electrical contractor to obtain permit and
inspection.